We thank you for choosing an LAE controller. Before proceeding to the installation of the RDC 12, please  read this instructions sheet carefully;
only in this way you will obtain maximum performances and safety.

1. INSTALLATION

1.1 

The instrument has got a size of 77x35x97 mm (WxHxD). It’s inserted into the panel through a 71x29 mm hole and secured via the suitable

brackets exerting corret strength. The rubber gasket must be placed between the panel and the instrument front, so please make sure that there are
no gaps allowing liquid infiltrations.

1.2 

The unit works with an ambient temperature between -10°...+50°C and 15%...80% relative Humidity. To reduce the effects of electro-magnetic

interference, place the cables carrying signals (probes and serial connections) and the controller as away as possible from power lines.

1.3

Probes, power supply and outputs/inputs must be wired strictly following the diagram indicated on the enclosure, where the maximum loads also

appear.  For supply voltage,  the suitable transformer (mod. TRxxx) must be used. 

1.4

Probe T1 measures air temperature and is used for the thermostat function; probe T2 measures the evaporator temperature and must be secured

to it in the place where the maximum frost growth occurs. Probe T3 is for measuring and displaying product temperature and is used for the night
thermostat. It must therefore be located in the position indicated by the manufacturer of the refrigerator -typically in the return air-.

1.5

The RS485 serial communication or TTL output  for the remote display is available on the DATA connector. PIN 1 is identified by a dot. 

Caution

: • If the relays switch a large load frequently, we suggest you contact us to obtain information about the relay contact life.

•Where delicate or valuable products have to be maintained under strict conditions, please use a different controller for limit and alarm functions.

2. CONTROL PARAMETERS

The adaptation of the RDC 12 to the the system that it controls is achieved through the parameters in the SETUP. Access to the parameters is obtained
by pressing  + +

for 4 seconds. Scroll through the parameters by pressing 

or 

until you select the desired one. Check its value by means

of 

and change it via  +

or  . Exit from the SETUP occurs after 10 sec. of no key activation. To help yourself during programming, refer to the

table annexed.

3. DISPLAYS

3.1 D

URING ORDINARY

C

ONTROL

. At the power up, the display shows "---" for 5 sec. during which the unit carries out a self-check; then the temperature

T3 appears. In some cases, owing to the structure of the cabinet or air stratification, the probes can not measure the desired temperature. If necessary,
through the parameters 

oS1

oS2

and 

oS3

the temperatures 

t1

t2

and 

t3 

measured by the probes can be adjusted in order to obtain the desired

values for computing: thermostat 

T1=t1+oS1

; defrost 

T2=t2+oS2

; display 

T3=t3+oS3

.

Through the 

SiM 

parameter it’s possible to reduce the fluctuations of the displayed temperature by simulating the behaviour of product core

SPL

minimum programmable temperature

[-50 ... +150°]

SPh

maximum programmable temperature

[SPL ... +150°]

hyS

thermostat on switching hysteresis

[+01 ... +20°K]

coF

cooler minimum off time

[00 ... 10 minutes]

con

cooler minimum on time

[00 ... 10 minutes]

cdc

cooler safety run in case of probe failure

[00=off ... 10(0)%=always on]

crS

cooler re-start delay after power failure

[00 ... 120 seconds]

dLi

defrost limit temperature

[+01 ... +70°]

dto

defrost time out

[01 ... 120 minutes]

drP

drain time

[00 ... 10 minutes]

diS

display control during defrost

[-01=”dEF”; 00=”T3”; 1... 30 minutes=timed “dEF”]

dty

defrost type

[Fan=off cycle; ELE=electrical; GAS=hot gas]

Fct

evaporator fan control

[-01=always on; 00=on/off with cooler; 1... 10 minutes=delayed off]

FrS

fan re-start after defrost

[-50 ... +150°]

Fid

ventilation during defrost

[00=off; 01=T2<FrS; 02=always on]

Alo

low alarm threshold

[-50 ... +150°]

Ahi

high alarm threshold

[ALo ... +150°]

AdL

temperature alarm delay

[-01=excluded; 00... 120 minutes]

Ain

alarm input selection

[probe 1, 2, 3]

oS1

thermostat probe offset 

[-20 ... +20°K]

oS2

evaporator probe offset 

[-20 ... +20°K]

oS3

displayed probe offset 

[-20 ... +20°K]

SiM

slowdown of displayed temperature

[00 ... 200]

Adr

peripheral number

[00 ... 255]

INSTRUCTIONS FOR INSTALLATION AND USE.

RDC123T1R3C

RDC123T1R3J