1
INSTALLATION,
MAINTENANCE, AND
SERVICE INSTRUCTION
MANUAL
SPACE SAVER
ELECTRIC HOT WATER
BOILERS
General Information
…………………………….Page 1
Installation ………………………...……………..Page 2
Start Up
…………………………………………..Page 3
Maintenance
……………………….……………..Page 3
Control ……………………………………………..Page 4
Service Instructions
…………………………….Page 5
Limited Warranty
………………………………Page 6
INDEX
GENERAL INFORMATION
Application
UL Listed under File No. E30432 to 600 volts and
120 KW as primary heat source, secondary heat
source, or as standby heat source for solar,
hydronic, and water source heat pump systems.
Vessel
ASME Code, Section IV “H” stamped, National
Board registered, rated to 160 psig and 250
degrees Fahrenheit.
Insulation
4” fiberglass blanket on vessel.
Elements
Incoloy sheathed, 75 watts per inch, mounted in
150 pound ASA steel flange, individually
removable.
Enclosure
Ventilated integral control panel constructed of
heavy gauge steel contains line terminals, fuses,
contactor(s), temperature controller, and safety
high limit devices. All surfaces are phosphatized
and protected against corrosion with factory
applied finish.