Technical data sheet: F01424EN/01

Catalogue number(s):  0 463 00/06/12/18/19/21/22/23 

0 463 28/29/30/33/34/35/41/42/43

Updated on: 24/10/2014

Created on: 21/02/2012

1/31

19" LCS

2

 freestanding cabinets

1. GENERAL FEATURES

19" LSC

2

 freestanding cabinets are intended for digital infrastructures.

19" LCS

2

 cabinets are metal and provide IP20 - IK08 protection. They 

have a single or double screen-printed curved glass door and are 
finished throughout in charcoal grey RAL 7016.
19" LSC

2

 cabinets can be joined together, either directly or via a 

cabling unit, and can be equipped with a modular plinth.
Equipment and accessories for cable management, vertical extension, 
thermal management, etc. complete the range.

1.1 Presentation
The main parts of 19" LCS

2

 freestanding cabinets are:

- A framework consisting of 4 uprights and 2 end plates
- A single or double screen-printed curved glass front door
- 2 side panels (excluding extension cabinets)
- A rear panel
- 4 x 19" uprights

CONTENTS                              Page

1.    General  features. . . . . . . . . . . . . . . . .1
2. Range. . . . . . . . . . . . . . . . . . . . . . . . .3
3. Technical features  . . . . . . . . . . . . . . .4
4. Dimensions. . . . . . . . . . . . . . . . . . . . .5
5. Baying. . . . . . . . . . . . . . . . . . . . . . . .10
6. Plinths. . . . . . . . . . . . . . . . . . . . . . . .12
7.  Cable management  . . . . . . . . . . . . .17
8. Vertical extension . . . . . . . . . . . . . . .20
9. Thermal management  . . . . . . . . . . .21

10. Accessories  . . . . . . . . . . . . . . . . . . .22
11. 19" equipment  . . . . . . . . . . . . . . . . .24
12. Power distribution. . . . . . . . . . . . . . .27

1. GENERAL FEATURES 

(continued)

1.1 Presentation 

(continued)

The 4 structural uprights and the 2 end plates form a metal framework 
that is screwed together. The cabinet can be dismantled completely if 
access is difficult.
The end plates contain the cabinet's cable entries. Their configuration, 
which is identical for the top and the bottom, is dependent on the 
dimensions of the cabinet:

(mm)

Width 600

Width 800

Depth 600

Depth 800

Depth 1000

Each cable entry is pre-cut in 19" format in order to be equipped with 
a cable entry plate (see section 7.1).

The whole structure stands on 4 levelling feet that can be adjusted 
from the inside and the outside of the cabinet.

Summary of Contents for LCS2

Page 1: ...4 uprights and 2 end plates A single or double screen printed curved glass front door 2 side panels excluding extension cabinets A rear panel 4 x 19 uprights CONTENTS Page 1 General features 1 2 Rang...

Page 2: ...fascia trims clipped onto the end plates continue the pixel design from the door The upper trim carries the Legrand name The side and rear metal panels are equipped with A 2433A locking bolt A stainle...

Page 3: ...lation ISO IEC 11801 Information technology Generic cabling for customer premises NF C 15 100 Part 4 41 Low voltage electrical installations recommendations IEC 60364 4 41 Low voltage electrical insta...

Page 4: ...base 3 4 Corrosion resistance Corrosion class of the environment C2 according to EN ISO 12944 2 3K3 according to IEC EN 60721 3 3 Salt spray test according to ISO 9227 NSS test and IEC EN 60068 2 11 t...

Page 5: ...71 810 857 1525 1608 0 463 23 42U 800 1000 2026 2041 2071 810 1057 1525 1808 0 463 28 47U 800 800 2248 2263 2293 810 857 1525 1608 0 463 29 47U 800 1000 2248 2263 2293 810 1057 1525 1808 Extension cab...

Page 6: ...33U 42U Usable space 1086 1308 1486 1886 70 70 A A 600 Usable space 450 Usable space 490 4 DIMENSIONS continued 4 2 Usable dimensions continued 4 2 1 600 mm wide freestanding cabinets continued 600 m...

Page 7: ...ts 2 Continuous adjustment with markings at 12 5 mm intervals 3 See front view on page 6 75 600 451 600 800 90 96 296 133 133 79 213 346 9 5 x 9 5 118 193 max 87 162 max 41 600 600 800 487 687 425 max...

Page 8: ...2 5 mm Fixing centre 391 max 591 max 791 max Fixing centre 337 max 537 max 737 max Usable space 490 690 890 Oblongs 7 x 50 Fixing centre 1838 2060 4 DIMENSIONS continued 4 2 Usable dimensions continue...

Page 9: ...OM ABOVE 90 213 346 133 133 96 296 496 79 9 5 x 9 5 Note The dimensions of the upper and lower end plates are identical 52 32 31 25 23 5 9 44 45 44 45 44 45 15 87 15 87 23 8 16 8 25 52 17 25 10 5 46 4...

Page 10: ...COMBINATION FROM ABOVE Cat No For cabinets depth mm 0 463 37 600 0 463 38 800 0 463 39 1000 800 800 1600 1610 overall 5 BAYING continued 5 2 Baying via cabling unit 5 2 1 Presentation The LCS2 cablin...

Page 11: ...nabling attractive assemblies to be created 5 2 2 Features IK08 IP20 maintained when joined Doors with handle equipped with a 2433A key lock same as single door cabinets End plates 1 5 mm thick galvan...

Page 12: ...120 65 INTERNAL CROSS SECTION VIEW 600 800 160 260 570 770 Usable space 250 1 288 1 Usable height 1922 mm 6 PLINTHS 6 1 Freestanding cabinet plinths 6 1 1 Presentation 19 LCS2 cabinets can be equippe...

Page 13: ...0 464 50 W 800 Cat No 0 464 51 H 200 W 600 Cat No 0 464 52 W 800 Cat No 0 464 53 W D Ventilated trap Trap with brushes W D 600 Cat No 0 464 60 Cat No 0 464 62 W D 800 Cat No 0 464 61 Cat No 0 464 63...

Page 14: ...zinc plated M6 fixing screws The ventilated traps have 5 mm perforations The traps with brushes are supplied with a black stiff brush and a black flexible brush polyamide fibres The usable feedthrough...

Page 15: ...rotection and a finish for the link between freestanding cabinets and cable ducts It is positioned to the right or left of a 600 mm deep cabinet equipped with a 200 mm high plinth It is mechanically j...

Page 16: ...s continued 6 4 2 Features For floor tiles 30 or 38 mm thick Height adjustable from 200 to 350 mm in 25 mm steps fine adjustement by levelling feet Permissible load 1000 kg Direct fixing to the end pl...

Page 17: ...etal 1U 0 465 31 Metal 2U CLICK 7 CABLE MANAGEMENT continued 7 1 Cable entry plates continued 7 1 1 Presentation continued The metal plates are equipped with 2 quick fixings that do not require any sc...

Page 18: ...aped tray is that the cables flow more easily no edges P L Cat No Set of 3 supports 0 464 72 For cabinet width depth 600 mm 0 464 73 For cabinet width depth 800 mm 0 464 74 For cabinet depth 1000 mm C...

Page 19: ...e paint ABS PC latches Supplied with screws Black RAL 9005 Cat No Overall dimensions mm Wire diameter mm 0 464 76 1405 x 255 4 4 0 464 77 1805 x 255 4 4 42U 19 LCS2 cabinets can also be joined via a c...

Page 20: ...HB Black high impact PBT 7 5 2 Self locking cable ties Self locking cable ties are repositionable textile ties that do not damage cables Tensile strength 220 N Fire resistance UL 94 V2 Double sided t...

Page 21: ...nish same as cabinets Charcoal grey RAL 7016 133 3U 89 482 465 19 60 45 200 133 3U 89 482 324 60 45 162 465 19 9 THERMAL MANAGEMENT continued 9 2 1U ventilation drawers The ventilation drawers are 19...

Page 22: ...runners 570 mm projection P 600 P 800 P 1000 P 600 800 1000 P 600 P 800 P 600 800 570 100 Kg max P 600 P 800 P 1000 P 600 800 1000 P 600 P 800 P 600 800 570 100 Kg max P 600 P 800 P 1000 P 600 800 10...

Page 23: ...ing cabinet to the floor permanently The 4 lugs in the kit when screwed to the floor lock the levelling feet of the cabinet A B 10 mm max 570 100 Kg max 40 2 5 60 12 12 10 ACCESSORIES continued 10 2 F...

Page 24: ...pped with 2 ergonomic fixings that do not require any screws or tools The quick fixing for metal panels is compatible with 1 4 to 2 75 mm thick 19 uprights with 8 25 to 9 5 mm square perforations An a...

Page 25: ...32 Plastic 1U 0 465 33 Plastic 2U 0 465 38 Metal 1U 0 465 39 Metal 2U 0 465 40 Metal 3U 11 19 EQUIPMENT continued 11 2 Fixed shelves 11 2 1 Projecting mounting fixed shelf For direct screw free fixin...

Page 26: ...uprights Cat No For cab depth mm Depth mm Width mm 0 465 17 1000 820 425 Height 1U Max load 100 kg Supplied with screws and cage nuts with pins 50 x 7 mm oblong perforations possibility of clamping us...

Page 27: ...5 12 5 7 7 15 6 5 12 5 29 C 674 D 12 POWER DISTRIBUTION 12 1 Vertical PDUs Designed to provide 230 V power supply for active products For mounting in 42U 47U LCS2 freestanding cabinets with a PDU sup...

Page 28: ...22 British 1 Clamping capacity 12 to 18 mm Features Cat No Power supply Use Voltage Max current Power 1 Protection 1 0 465 81 230V 250V 50 60 Hz 16A 3680 W 16A circuit breaker Single pole neutral C t...

Page 29: ...2P E sockets Additional function Colour Number Standard 0 332 78 6 French Belgian Surge protector Switch with indicator Alumin grey White sockets Features Cat No Power supply Use Voltage Max current P...

Page 30: ...nting of the vertical PDU in 19 LCS2 cabinets see section 12 1 Can receive 19 PDU vertically Many possibilities of fixing by screw PDU with buttons can be fixed by hanging all 7U Cat No For cabinet ca...

Page 31: ...2A 12 4 1 DIN profile rail with front panel Cat No 0 465 46 Comprises a front panel and 15 mm deep rail equipped with brackets for 19 fixing centre IPXXC front part only Supplied with a 24 modules bla...

Reviews: