background image

www.numericups.com

NEW ENERGY

TO POWER

Onfiniti

1-3 kVA

USER AND 

INSTALLATION 

MANUAL

NEW ENERGY

TO POWER

Cover Page_Front

Regional Offices

New Delhi

A 25, 1st Floor, Mohan Co-Operative 
Industrial Estate, Mathura Road,
New Delhi - 110 044
Phone: +91 11 4754 8505/511

Mumbai

C/203, Corporate Avenue, Atul Projects,
Near Mirador Hotel, Andheri-Ghatkopar
Link Road, Chakala, Andheri (East),
Mumbai - 400 099.
Phone: +91 22 3385 6201

Coimbatore

No. B-15, Thirumalai Towers,
No. 723, 4th Floor, Avinashi Road,
Coimbatore - 641 018.
Phone: +91 422 420 4018

Bengaluru

First Floor, Feroze White House,
No. 58, Bowring Hospital Road,
Shivajinagar, Bengaluru – 560 001.
Phone: +91 80 2286 1081/78

Head Office

10th Floor, Prestige Center Court,
Office Block, Vijaya Forum Mall,
183, N.S.K. Salai, Vadapalani,
Chennai - 600 026.
Phone: +91 44 4656 5555

Kolkata

Plot No. KB22, Bhakta Tower,
2nd & 3rd Floor, Salt Lake City,
Sector - III, Kolkata - 700 098.
Phone: +91 33 4021 3535/3536

Chennai

10th Floor, Prestige Center Court,
Office Block, Vijaya Forum Mall,
183, N.S.K. Salai, Vadapalani,
Chennai - 600 026.
Phone: +91 44 3024 7236/200

Hyderabad

No. 205-208, 2nd Floor, Block 2,
White House Kundan Bag, Begumpet,
Hyderabad - 500 016.
Phone: +91 40 4567 1732

Kochi

Door No. 50/1107A9, JB Manjooran Estate,
3rd Floor, Bye Pass Junction, Edappally,
Kochi - 682 024.
Phone: +91 484 2801 921

10th Floor, Prestige Center Court, Office Block,
Vijaya Forum Mall, 183, N.S.K. Salai, Vadapalani,
Chennai - 600 026, India. | 

Phone

: +91 44 4656 5555

Sales - enquiry.numeric

@

numericups.com

Service - support.numeric

@

numericups.com

TOLL FREE No.: 1800 425 3266

www.numericups.com

NP/DSG/UM/10001/RE

V03

Cover Page_Back

*NUMERIC reserves at any time the right to modify the contents 

of this booklet and to communicate, in any form and modality, 

the changes brought to the same.

Summary of Contents for NUMERIC 1 kVA FM

Page 1: ...www numericups com NEW ENERGY TO POWER Onfiniti 1 3 kVA USER AND INSTALLATION MANUAL NEW ENERGY TO POWER ...

Page 2: ...perations 8 5 1 Button operation 8 5 2 LCD panel 9 5 3 Audible alarm 11 5 4 LCD display wordings index 11 5 5 UPS setting 12 5 6 Charging current setting 16 5 7 Operating mode description 16 5 8 Fault reference codes 17 5 9 Warning indicator 17 6 Troubleshooting 18 7 Storage and Maintenance 20 7 1 Operation 20 7 2 Storage 20 7 3 Disposal 20 8 Specifications 21 8 1 UPS without ISO transformer 21 8 ...

Page 3: ...d patronage in the years to come This manual provides general information regarding installation and operation of Onfiniti 1 Disclaimer The contents of this manual are bound to change without prior notice We have exercised reasonable care to give you an error free manual Numeric disclaims liability for any inaccuracies or omissions that may have occurred If you find information in this manual that...

Page 4: ...wer Quality with optimal Total Cost of Ownership TCO The Onfiniti range of UPS is a true online double conversion topology UPS designed with IGBT based rectifier and inverter to suit customer requirements Onfiniti provides maximum protection and power quality for entry level servers workstations communication equipment ATMs etc 2 ...

Page 5: ...o direct sunlight or near a heater Do not block ventilation holes in the UPS housing 3 3 Installation Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Do not place cables in such a way that one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any...

Page 6: ...people adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept away from the batteries Caution Risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltag...

Page 7: ...utput receptacles 8 Output terminal 5 1 kVA FM 2 kVA FM 3 kVA FM 1 kVA FMI 2 kVA FMI 3 kVA FMI 4 INSTALLATION AND SETUP Note Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 4 1 Rear panel view UPS without ISO transformer UPS with ISO transformer ...

Page 8: ... the small cover of the terminal block b Use AWG14 or 2 1 mm2 power cords c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 3 Communication connection To allow for unattended UPS shutdown start up and status monitoring connect one end of then communication cable to the USB RS 232 port and the other to...

Page 9: ...If not please follow the on screen instructions to install the software When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock Step 6 External battery connection This UPS series is not including batteries Batteries are connected in a separate cabinet with protection Please connect external batteries as below chart TO EXTERNA...

Page 10: ...o Bypass mode if the Bypass setting is enabled by pressing OFF Enter button this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Select button S...

Page 11: ...ng backup time in pie chart Indicates the remaining backup time in numbers H hours M minute S second Indicates the warning and fault occurs Indicates that the UPS alarm is disabled Indicates the warning and fault codes The codes are listed in details in section 3 5 Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency H M S 88 88 O U T P U T ...

Page 12: ...tes the battery level by 0 25 26 50 51 75 and 76 100 Indicates the battery is faulty Indicates low battery level and low battery voltage Indicates the input voltage or frequency or battery voltage Vac Input voltage Vdc battery voltage Hz input frequency Load information Mode operation information Battery information Input and battery voltage information BATT FAULT LOW BATT OVER LOAD SHORT I P O P ...

Page 13: ... Fault Sounds continuously Bypass mode Sounds every 10 seconds 11 5 4 LCD display wordings index Abbreviation ENA DIS ESC HLS LLS BAT CF TP CH FU EE Display content Meaning Enable Disable Escape High loss Low loss Battery Converter Temperature Charger Bypass frequency unstable EEPROM error EnA dIS ESC HLS LLS CF CH FU EE ...

Page 14: ...requency is 60 Hz Parameter 3 Output voltage For 200 208 220 230 240 Vac models you may choose the following output voltage 200 Presents output voltage is 200 Vac 208 Presents output voltage is 208 Vac 220 Presents output voltage is 220 Vac 230 Presents output voltage is 230 Vac Default 240 Presents output voltage is 240 Vac Parameter 2 3 Enable or disable converter mode You may choose the followi...

Page 15: ...Bypass enable disable when UPS is off Parameter 2 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down or Up key HLS High loss voltage in ECO mode in Parameter 2 For 200 208 220 230 240 VAC models the setting range in Parameter 3 is from 7 V to 24 V of the nominal voltage Default 12 V LLS Low loss voltage in ECO mode in Parameter 2 For 200 208 220 230 240 VAC...

Page 16: ... time setting will be disabled Default Parameter 2 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 200 208 220 230 240 Vac models 230 264 Setting the high voltage point in Parameter 3 from 230 Vac to 264 Vac Default 264 Vac LLS Bypass low voltage point For 200 208 220 230 240 Vac models 17...

Page 17: ...ceptable battery minimum cut off voltage point by pressing the Down key or Up key 167 190 Setting the minimum battery cut off voltage point in parameter 3 from 167 to 190 Unit 0 01 V CELL Default 175 Parameter 3 Set up the charger float voltage 220 233 Setting the charger float voltage point in Parameters from 220 to 233 Unit 0 01 V CELL Default 228 09 167 bC0 Vdc 10 236 Cb u Vdc Interface Setting...

Page 18: ...age is within voltage regulation range UPS will bypass voltage to output for energy saving Frequency converter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm sounds every 4 seconds UPS wi...

Page 19: ...t of Bypass voltage range Sounds every second Bypass frequency unstable Sounds every second EEPROM error Sounds every second OVER LOAD BATT FAULT LOW BATT BYPASS CH FU EE OVER LOAD SHORT Fault event Fault code Icon Fault event Fault code Icon BUS start fail 01 x Inverter voltage low 13 x BUS over 02 x Inverter output short 14 BUS under 03 x Battery voltage too high 27 x BUS unbalance 04 x Battery ...

Page 20: ...oads from UPS output and restart it The UPS shutdown automatically because short circuit occurs on the UPS output Check output wiring and if connected devices are in short circuit status After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Byp...

Page 21: ...attery faulty Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Contact your dealer to replace the battery If the problem persists contact our nearest after sales service department by visiting www numericups com or call Toll Free no 18004253266 with the following information 1 Model number Serial number 2 Date on which the problem ...

Page 22: ...uthorized recycler Batteries when found faulty damaged must be handed over to identified authorized recycler or to NUMERIC where it is disposed properly Battery contains harmful metals and chemicals such as nickel cadmium alkaline mercury nickel metal hydride and lead acid which contaminates if it is not disposed properly When batteries containing cadmium is used in fills they will eventually diss...

Page 23: ... 70 70 60 60 0 185 VAC 165 VAC 145 VAC 135 VAC 5 based on load percentage 100 80 80 70 70 60 60 0 300 Vac 5 290 Vac 5 40 Hz 70 Hz Single phase with ground 0 99 nominal input voltage 200 208 220 230 240 Vac 1 47 53 Hz or 57 63 Hz 50 Hz 0 25 Hz or 60 Hz 0 3 Hz 105 110 UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110 130 UPS shuts down after 1 min at ba...

Page 24: ...evel 20 90 RH 0 40 C non condensing Less than 50 dBA 1 Meter AVG Smart RS 232 or USB Optional SNMP 3 150 30 A max 1 0A 2 0A 4 0A 8 0A 41 0 Vdc 1 6 200 30 A max 82 1 Vdc 1 8 200 30 A max 109 5 Vdc 1 6 200 45 A max 82 1 Vdc 1 8 200 32 A max 109 5 Vdc 1 Dimension D x W x H mm 405x145x235 435 x 190 x 335 Net weight kgs 6 2 11 5 12 0 PHYSICAL 1 0A 2 0A 4 0A 6 0 A Derate capacity to 80 of capacity in Fr...

Page 25: ...based on load percentage 100 80 80 70 70 60 60 0 300 Vac 5 290 Vac 5 40 Hz 70 Hz Single phase with ground 0 99 nominal input voltage 200 208 220 230 240 Vac 1 47 53 Hz or 57 63 Hz 50 Hz 0 25 Hz or 60 Hz 0 3 Hz 105 110 UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110 130 UPS shuts down after 1 min at battery mode or transfer to Bypass when the utility...

Page 26: ...EMENT Operation humidity Noise level 20 90 RH 0 40 C non condensing Less than 50 dBA 1 Meter AVG Smart RS 232 or USB Optional SNMP 3 150 30 A max 1 0A 2 0A 4 0A 8 0A 41 0 Vdc 1 6 200 30 A max 82 1 Vdc 1 8 200 30 A max 109 5 Vdc 1 6 200 45 A max 82 1 Vdc 1 Dimension D x W x H mm Net weight kgs 465x190x465 21 3 435 x 190 x 595 35 5 PHYSICAL 1 0A 2 0A 4 0A 6 0 A Derate capacity to 80 of capacity in F...

Page 27: ... Mirador Hotel Chakala Andheri Ghatkopar Link Road Andheri East Mumbai 400 099 Phone 91 22 3385 6201 Chennai 10th Floor Prestige Center Court Office Block Vijaya Forum Mall 183 N S K Salai Vadapalani Chennai 600 026 Phone 91 44 3024 7236 200 Chandigarh SCO 4 First Floor Sector 16 Panchkula Chandigarh 134 109 Phone 91 93160 06215 Dehradun First Floor Plot No 1 2 679 1 Vijay Park Colony Main Chakrat...