HOT WATER HEAT KIT

KITS COMMON TO AIR HANDLERS

INSTALLATION INSTRUCTION FOR HOT WATER HEAT KIT (90W84)

E

2012 Lennox Industries Inc.

Dallas, Texas, USA

WARNING

Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.

Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.

CAUTION

Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.

WARNING

Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.

Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.

Shipping and Packing List

Check unit for shipping damage. Consult last carrier
immediately if damage is found.

Catalog

Number

Part Names

Part

Numbers

Qty.

90W84

DC Relay, 22VDC

102297-01

1

3PDT Relay

67K6601

1

Delay-On-Make Relay

99P41

1

9-Pin Wiring Harness

609345-01

1

Wiring Diagram

537516-01

1

Field-Provided Supplies

The following field-provided supplies may be required.

S

1/4” quick connects

S

Control wiring (various lengths)

General

Hot water heat kit (90W84) adapts CBX32MV and
CBX40UHV units for use with a boiler to provide hot water
heating in select applications. When used with an air
conditioner, the hot water provides first-stage heating.
When used with a heat pump, the hot water provides
second-stage heating.
This kit is only approved for use in systems using either the
ComfortSense

®

 7000 thermostat or icomfort

t

thermostat. Wiring modifications shown are in addition to
field wiring detailed in the instructions provided with the air
handler.

Thermostat Configuration 

HEAT PUMP APPLICATIONS

The ComfortSense

®

 7000 will need to be reconfigured for

use with:

S

Heat pump with hot water heat (see figure 7).

S

Compressor low balance set point of 40ºF.

Since the hot water coil is downstream of the coil, the heat
pump and boiler can be operated simultaneously. In
emergency heat mode, the blower CFM drops to the lower
heat table CFM setting.

AIR CONDITIONER APPLICATIONS

In applications with condensing units, configure
ComfortSense

®

 7000 for hot water heat (see figure 7).

In icomfort

t

-enabled systems, see figure 7 for heat

discovery procedures and the icomfort

t

 thermostat

installer guide to configure the thermostat.

Kit Installation 

This kit can be installed for any of the following variations:

S

Air handler - hot water heat and air conditioner

S

Air handler - hot water heat and heat pump

FREEZESTAT INSTALLATION

Since the hot water coil is downstream of the indoor  a
freezestat will need to be installed to protect the indoor
coil during summer air conditioning operation.

1. All units will require one field-provided properly sized

freezestat (S49) for use with this kit. Order part using
table 1.