background image

Montageanleitung

EDKZN3B024

.Oe$

Ä.Oe$ä

Global Drive 

1.5 ... 24 A

l

EZN3B2400H002, EZN3B1500H003,
EZN3B0900H004, EZN3B0750H005,
EZN3B0500H007, EZN3B0400H009,
EZN3B0300H013, EZN3B0250H015,
EZN3B0150H024

Netzfilter

Mains filter

Filtre réseau

Mounting Instructions

Instructions de montage

     

  

Summary of Contents for 1.5 24 A Series

Page 1: ... ä Global Drive 1 5 24 A l EZN3B2400H002 EZN3B1500H003 EZN3B0900H004 EZN3B0750H005 EZN3B0500H007 EZN3B0400H009 EZN3B0300H013 EZN3B0250H015 EZN3B0150H024 Netzfilter Mains filter Filtre réseau Mounting Instructions Instructions de montage ...

Page 2: ...enen Sicherheitshinweise Please read these instructions and the documentation of the standard device before you start working Observe the safety instructions given therein Lire le présent fascicule et la documentation relative à l appareil de base avant toute manipulation de l équipement Respecter les consignes de sécurité fournies ...

Page 3: ... Produktbeschreibung 10 3 1 Bestimmungsgemäße Verwendung 10 3 2 ZuordnungFilter Grundgerät 10 3 3 Lieferumfang 11 3 4 Übersicht 11 3 5 Identifikation 12 4 TechnischeDaten 13 4 1 Allgemeine Daten und Einsatzbedingungen 13 4 2 Bemessungsdaten 15 4 3 MechanischeDaten 16 5 MechanischeInstallation 18 5 1 Wichtige Hinweise 18 5 2 Bohrplan 19 5 3 Montageschritte 20 6 ElektrischeInstallation 21 6 1 Wichti...

Page 4: ...007 ƒ Netzfilter EZN3B0400H009 ƒ Netzfilter EZN3B0300H013 ƒ Netzfilter EZN3B0250H015 ƒ Netzfilter EZN3B0150H024 1 2 Zielgruppe Diese Dokumentation richtet sich an qualifiziertes Fachpersonal nach IEC 60364 Qualifiziertes Fachpersonal sind Personen die für die auszuführenden Tätigkei ten bei der Aufstellung Montage Inbetriebsetzung und dem Betrieb des Pro dukts über entsprechende Qualifikationen ve...

Page 5: ...tung 13216453 1 0 10 2007 TD29 Erstausgabe 1 4 Verwendete Konventionen Informationsart Auszeichnung Beispiele Hinweise Zahlenschreibweise Dezimaltrennzeichen Punkt Es wird generell der Dezimalpunkt verwendet Zum Beispiel 1234 56 Warnhinweise UL Warnhinweise J Werden in englischer und französi scher Sprache verwendet UR Warnhinweise O Textauszeichnung Programmname PC Software Zum Beispiel Engineer ...

Page 6: ...eis auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folge haben kann wenn nicht die entsprechenden Maßnahmen getroffen werden Danger Gefahr von Personenschäden durch eine allgemeine Gefahrenquelle Hinweis auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folge haben kann wenn nicht die entsprechenden Maßnahmen getroffen werden Stop Gefahr...

Page 7: ... der beiliegenden und zugehörigen Dokumentation beachten Dies ist Voraussetzung für einen sicheren und störungsfreien Betrieb sowie für das Erreichen der angegebenen Produkteigenschaften Die in diesem Dokument dargestellten verfahrenstechnischen Hinweise und Schaltungsausschnitte sind Vorschläge deren Übertragbarkeit auf die jeweilige Anwendung überprüft werden muss Für die Eignung der angege bene...

Page 8: ...n ob alle Leistungsanschlüsse spannungsfrei sind Danger Gefährliche elektrische Spannung Der Ableitstrom gegen Erde PE ist 3 5 mA AC bzw 10 mA DC Mögliche Folgen ƒ Tod oder schwere Verletzungen beim Berühren des Gerätes im Fehlerfall Schutzmaßnahmen Die in der EN 61800 5 1 geforderten Maßnahmen umsetzen Insbesondere ƒ Festinstallation PE Anschluss normgerecht ausführen PE Leiter doppelt auflegen o...

Page 9: ... zu hohe Netzspannung Der Netzeingang ist intern nicht abgesichert Mögliche Folgen ƒ Zerstörung des Gerätes bei zu hoher Netzspannung Schutzmaßnahmen ƒ Beachten Sie die maximal zulässige Netzspannung ƒ Sichern Sie das Gerät netzseitig fachgerecht gegen Netzschwankungen und Spannungsspitzen ab ...

Page 10: ...ten zu einer Maschine ƒ sind elektrische Betriebsmittel zum Einbau in Schaltschränke oder ähnliche abgeschlossene Betriebsräume ƒ erfüllen die Schutzanforderungen der EG Richtlinie Niederspannung ƒ sind keine Maschinen im Sinne der EG Richtlinie Maschinen ƒ sind keine Haushaltsgeräte sondern als Komponenten ausschließlich für die Weiterverwendung zur gewerblichen Nutzung bestimmt Antriebssysteme m...

Page 11: ...reibung Lieferumfang 3 l 11 EDKZN3B024 DE EN FR 3 0 3 3 Lieferumfang Anzahl Beschreibung 1 Filter 1 Montageanleitung 3 4 Übersicht EZN 051 Position Beschreibung 0 Netzanschluss 1 Anschluss Grundgerät 3 Typenschild ...

Page 12: ...rzen Made in Germany Type 8200vec080 Abb 3 1 Typenschild Typenschlüssel E Z N 3 x xxxx H xxx xxxx Produktreihe Zubehör Filtertyp N Netzfilter Anzahl Phasen 3 3 Phasen Grenzwertklasse nach EN 61800 3 A Grenzwertklasse C2 B Grenzwertklasse C1 Induktivität z B 0055 0 55 mH Bemessungsstrom z B 060 60 A Filter Variante opt ...

Page 13: ...Betrieb uneingeschränkt erlaubt Andere Netzformen Anweisungen über besondere Maßnahmen in der Dokumentation zum Grundgerät beachten Schutz Schutzart EN 60529 IP 20 nicht im Anschlussbe reich der Klemmen Isolationsfestigkeit EN 61800 5 1 Überspannungskategorie III Reduzierung ab 2000 m Überspannungskategorie II Ableitstrom EN 61800 5 1 3 5 mA Bestimmungen und Sicherheitshinweise beachten Umweltbedi...

Page 14: ... und Einsatzbedingungen 4 l 14 EDKZN3B024 DE EN FR 3 0 Montagebedingungen Montageort im Schaltschrank Montageposition oberhalb des Grundgerätes Einbaulage senkrecht Netzanschluss oben Einbaufreiräume oben und unten 85 mm seitlich 20 mm ...

Page 15: ...900H004 400 480 50 60 4 0 2 5 3 EZN3x0750H005 400 480 50 60 5 0 3 1 3 EZN3x0500H007 400 480 50 60 7 0 4 4 3 EZN3x0400H009 400 480 50 60 9 0 5 6 3 EZN3x0300H013 400 480 50 60 13 0 8 1 3 EZN3x0250H015 400 480 50 60 15 0 9 4 3 EZN3x0150H024 400 480 50 60 24 0 15 0 3 Temperatur im Schaltschrank Verlustleistung Induktivität Spannungsabfall PV W L mH DU V EZN3x2400H002 17 24 20 EZN3x1500H003 18 15 20 EZ...

Page 16: ...Technische Daten Mechanische Daten 4 l 16 EDKZN3B024 DE EN FR 3 0 4 3 Mechanische Daten EZN 052 Alle Maße in Millimeter ...

Page 17: ... 3 0 Typ Maße Masse a a1 b b1 e m n mm kg EZN3x2400H002 150 120 230 125 78 135 2 5 EZN3x1500H003 3 1 EZN3x0900H004 3 2 EZN3x0750H005 180 150 97 165 5 2 EZN3x0500H007 5 6 EZN3x0400H009 5 9 EZN3x0300H013 260 230 135 245 92 11 5 EZN3x0250H015 12 4 EZN3x0150H024 12 5 ...

Page 18: ...Technischen Daten genannten Einsatzbedingungen immer entsprechen 13 Ggf zusätzliche Maßnahmen ergreifen ƒ Die Montageplatte des Schaltschranks muss folgende Eigenschaften aufweisen elektrisch leitfähig lackfrei ƒ Die mechanischen Verbindungen müssen immer gewährleistet sein ƒ Eine ungehinderte Luftzirkulation zum Abführen der Wärme muss gewährleistet sein ...

Page 19: ... EDKZN3B024 DE EN FR 3 0 5 2 Bohrplan EZN 053 Alle Maße in Millimeter Typ Maße e1 m n mm EZN3x2400H002 39 135 EZN3x1500H003 EZN3x0900H004 EZN3x0750H005 48 5 165 EZN3x0500H007 EZN3x0400H009 EZN3x0300H013 21 5 245 92 EZN3x0250H015 EZN3x0150H024 ...

Page 20: ...ritte 5 l 20 EDKZN3B024 DE EN FR 3 0 5 3 Montageschritte EZN 054 So montieren Sie das Filter 1 Montageplatte gemäß Bohrplan vorbereiten 2 Filter je nach Ausführung mit 2 bzw 4 Schrauben M6 und Unterlegscheiben auf Montageplatte montieren ...

Page 21: ...en immer entsprechen 13 nach EN 60204 1 ausgeführt werden ƒ Bei der Auswahl des Leitungstyps beachten Die verwendeten Leitungen müssen den geforderten Approbationen am Einsatzort entsprechen z B VDE UL usw Absicherung und Leitungsquerschnitte gemäß den Vorgaben in der Dokumentation zum Grundgerät bemessen ƒ Beim Verlegen der PE Leitung beachten Der PE Anschluss muss nach EN 61800 5 1 ausgeführt we...

Page 22: ...Elektrische Installation Anschlussplan 6 l 22 EDKZN3B024 DE EN FR 3 0 6 2 Anschlussplan L1 L1 L1 L2 L2 L2 Load Line EZN L3 L3 L3 PE PE PE L3 N PE L1 L2 F K1 GN YE BK BK BK 0 EZN003 0 Antriebsregler ...

Page 23: ...x0500H007 EZN3x0400H009 EZN3x0300H013 EZN3x0250H015 0 2 6 0 25 6 0 5 4 24 8 9 1 5 1 8 13 2 15 9 EZN3x0150H024 6 4 Montageschritte EZN 055 So verdrahten Sie das Filter 1 Schaltschrank spannungsfrei schalten und gegen Wiedereinschalten sichern 2 Anschlussleitungen zum Grundgerät an Klemme Load anschließen 2 Montageanleitung des Grundgerätes beachten 3 Netzleitungen an Klemme Line 0 anschließen Anzug...

Page 24: ...Elektrische Installation Montageschritte 6 l 24 EDKZN3B024 DE EN FR 3 0 ...

Page 25: ...Product description 32 3 1 Application as directed 32 3 2 Filter controller assignment 32 3 3 Scope of supply 33 3 4 Overview 33 3 5 Identification 34 4 Technical data 35 4 1 General data and operating conditions 35 4 2 Rated data 37 4 3 Mechanicaldata 38 5 Mechanical installation 40 5 1 Important notes 40 5 2 Drilling pattern 41 5 3 Mounting steps 42 6 Electrical installation 43 6 1 Important not...

Page 26: ...documentation is directed at qualified skilled personnel according to IEC 60364 Qualified skilled personnel are persons who have the required qualifications to carry out all activities involved in installing mounting commissioning and operating the product I Tip Information and tools concerning the Lenze products can be found in the download area under www lenze com 1 3 Document history Material n...

Page 27: ...Spelling of numbers Decimal separator Point In general the decimal point is used For instance 1234 56 Warnings UL warnings J Given in English and French UR warnings O Text Program name PC software For example Engineer Global Drive Control GDC Icons Page reference Reference to another page with additional information For instance 16 see page 16 ...

Page 28: ...gh dangerous electrical voltage Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken Danger Danger of personal injury through a general source of danger Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken Stop Danger of property damage Reference to ...

Page 29: ...tions of the corresponding enclosed documentation must be observed This is vital for a safe and trouble free operation and for achieving the specified product features The procedural notes and circuit details provided in this document are proposals which the user must check for suitability for his application The manufacturer does not accept any liability for the suitability of the specified proce...

Page 30: ...l power terminals are deenergised Danger Hazardous electrical voltage The leakage current to earth PE is 3 5 mA AC or 10 mA DC Possible consequences ƒ Death or severe injuries when touching the device in the event of an error Protective measures Implement the measures required in EN 61800 5 1 Especially ƒ Fixed installation Implement PE connection in compliance with standards Connect PE conductor ...

Page 31: ...s voltage is too high The mains input is not internally fused Possible consequences ƒ Destruction of the device if the mains voltage is too high Protective measures ƒ Observe the maximally permissible mains voltage ƒ Fuse the device correctly on the supply side against mains fluctuations and voltage peaks ...

Page 32: ...omponents to form a machine ƒ are electrical equipment for the installation into control cabinets or similar closed electrical operating areas ƒ comply with the requirements of the LowVoltage Directive ƒ are not machines for the purpose of the EC Machinery Directive ƒ are no household appliances but are intended exclusively as components for further commercial use Drive systems with filters ƒ The ...

Page 33: ...e of supply 3 l 33 EDKZN3B024 DE EN FR 3 0 3 3 Scope of supply Quantity Description 1 Filter 1 Mounting Instructions 3 4 Overview EZN 051 Position Description 0 Mains connection 1 Connection of the standard device 3 Nameplate ...

Page 34: ...rzen Made in Germany Type 8200vec080 Fig 3 1 Nameplate Type code E Z N 3 x xxxx H xxx xxxx Product series Accessories Type of filter N mains filter Number of phases 3 3 phases Limit class according to EN 61800 3 A limit class C2 B limit class C1 Inductance e g 0055 0 55 mH Rated current e g 060 60 A Filter variant opt ...

Page 35: ...Other mains types Observe instructions for special measures in the documentation for the basic device Protection Degree of protection EN 60529 IP 20 Not in the wire range of the terminals Insulation resistance EN 61800 5 1 Overvoltage category III 2000 m Overvoltage category II Leakage current EN 61800 5 1 3 5 mA Observe regulations and safety instructions Ambient conditions Temperature Storage 25...

Page 36: ... 4 l 36 EDKZN3B024 DE EN FR 3 0 Mounting conditions Mounting location In the control cabinet Mounting position Above the standard device Mounting position Vertical mains connection on top Free spaces at the top and at the bottom 85 mm to the sides 20 mm ...

Page 37: ...x0900H004 400 480 50 60 4 0 2 5 3 EZN3x0750H005 400 480 50 60 5 0 3 1 3 EZN3x0500H007 400 480 50 60 7 0 4 4 3 EZN3x0400H009 400 480 50 60 9 0 5 6 3 EZN3x0300H013 400 480 50 60 13 0 8 1 3 EZN3x0250H015 400 480 50 60 15 0 9 4 3 EZN3x0150H024 400 480 50 60 24 0 15 0 3 Temperature in the control cabinet Power loss Inductance Voltage drop Ploss W L mH DU V EZN3x2400H002 17 24 20 EZN3x1500H003 18 15 20 ...

Page 38: ...Technical data Mechanical data 4 l 38 EDKZN3B024 DE EN FR 3 0 4 3 Mechanical data EZN 052 All dimensions in millimetres ...

Page 39: ...Type Dimensions Mass a a1 b b1 e m n mm kg EZN3x2400H002 150 120 230 125 78 135 2 5 EZN3x1500H003 3 1 EZN3x0900H004 3 2 EZN3x0750H005 180 150 97 165 5 2 EZN3x0500H007 5 6 EZN3x0400H009 5 9 EZN3x0300H013 260 230 135 245 92 11 5 EZN3x0250H015 12 4 EZN3x0150H024 12 5 ...

Page 40: ...ays comply with the operating conditions specified in the technical data 35 Take additional measures if necessary ƒ The mounting plate of the control cabinet must have the following properties electrically conductive free of lacquer ƒ The mechanical connections must always be ensured ƒ A free air circulation must be ensured for dissipating the heat ...

Page 41: ...B024 DE EN FR 3 0 5 2 Drilling pattern EZN 053 All dimensions in millimetres Type Dimensions e1 m n mm EZN3x2400H002 39 135 EZN3x1500H003 EZN3x0900H004 EZN3x0750H005 48 5 165 EZN3x0500H007 EZN3x0400H009 EZN3x0300H013 21 5 245 92 EZN3x0250H015 EZN3x0150H024 ...

Page 42: ...42 EDKZN3B024 DE EN FR 3 0 5 3 Mounting steps EZN 054 How to mount the filter 1 Prepare the mounting plate as shown in the drilling pattern 2 Mount the filter to the mounting plate using 2 or 4 M6 screws and washers respectively design dependent ...

Page 43: ...ta 35 be carried out to EN 60204 1 ƒ Please observe the following when selecting the cable type The cables used must comply with the approvals required for the application e g VDE UL etc Fuses and cable cross sections must be dimensioned in accordance with the specifications in the documentation for the basic device ƒ Please observe the following when laying the PE cable The PE connection must com...

Page 44: ...Electrical installation Connection plan 6 l 44 EDKZN3B024 DE EN FR 3 0 6 2 Connection plan L1 L1 L1 L2 L2 L2 Load Line EZN L3 L3 L3 PE PE PE L3 N PE L1 L2 F K1 GN YE BK BK BK 0 EZN003 0 Controller ...

Page 45: ...00H007 EZN3x0400H009 EZN3x0300H013 EZN3x0250H015 0 2 6 0 25 6 0 5 4 24 8 9 1 5 1 8 13 2 15 9 EZN3x0150H024 6 4 Mounting steps EZN 055 How to wire the filter 1 Deenergise the control cabinet and fuse it against re energisation 2 Connect the connection cables of the standard device to terminal Load 2 Observe the documentation of the standard device 3 Connect the mains cables to terminal Line 0 Obser...

Page 46: ...Electrical installation Mounting steps 6 l 46 EDKZN3B024 DE EN FR 3 0 ...

Page 47: ...nction 54 3 2 Combinaisons filtre appareil de base 54 3 3 Équipement livré 55 3 4 Présentationgénérale 55 3 5 Identification 56 4 Spécificationstechniques 57 4 1 Caractéristiques générales et conditions d utilisation 57 4 2 Caractéristiques assignées 59 4 3 Caractéristiques mécaniques 60 5 Installationmécanique 62 5 1 Remarques importantes 62 5 2 Modèle de perçage 63 5 3 Opérations de montage 64 6...

Page 48: ...rmément à la norme CEI 60364 On entend par personnel qualifié et habilité des personnes compétentes en matière d installation de montage de mise en service et de fonctionnement du produit et possédant les qualifications correspondant à leurs activités I Conseil Toutes les informations relatives aux produits Lenze peuvent être téléchargées sur notre site à l adresse suivante www Lenze com 1 3 Histo...

Page 49: ...Point Le point décimal est généralement utilisé Exemple 1234 56 Consignes préventives Consignes préventives UL J En anglais et en français Consignes préventives UR O Mise en évidence de textes spéciaux Nom de programme Logiciel pour PC Exemple Engineer Global Drive Control GDC Pictogrammes Renvoi à la page Renvoi à une autre page contenant des informations complémentaires Exemple 16 voir page 16 ...

Page 50: ...r conséquences des blessures mortelles ou très graves en cas de non respect des consignes de sécurité correspondantes Danger Situation dangereuse pour les personnes en raison d un danger d ordre général Indication d un danger imminent qui peut avoir pour conséquences des blessures mortelles ou très graves en cas de non respect des consignes de sécurité correspondantes Stop Risques de dégâts matéri...

Page 51: ...ions contenues dans la documentation concernée Il s agit de la condition préalable pour garantir un fonctionnement sûr et fiable et pour obtenir les caractéristiques du produit indiquées Les procédures à suivre et les plans de raccordement fournis constituent des recommandations dont l adéquation avec l application concernée doit être vérifiée Lenze n assumera aucune responsabilité pour les dommag...

Page 52: ...uissance sont hors tension Danger Tension électrique dangereuse Le courant de fuite vers la terre PE est 3 5 mA CA ou 10 mA CC Risques encourus ƒ Mort ou blessures graves en cas de contact accidentel avec l appareil en défaut Mesures de protection Mettre en œuvre les mesures prescrites par la norme EN 61800 5 1 notamment ƒ Installation fixe Prévoir un raccordement PE conformément à la norme Prévoi...

Page 53: ...e Il n y a pas de protection intégrée de l entrée réseau Risques encourus ƒ Dommages irréversibles de l appareil en cas de tension réseau trop élevée Mesures de protection ƒ Respecter la tension réseau maximale admissible ƒ Protéger l appareil de manière adaptée côté réseau contre les fluctuations du réseau et les pointes de tension ...

Page 54: ...semblés avec d autres composants pour former une machine ƒ sont des équipements électriques destinés à être montés dans les armoires électriques ou d autres locaux de service clos ƒ remplissent les exigences de sécurité de la directive CE Basse tension ƒ ne sont pas des machines au sens de la directive CE relative aux machines ƒ ne sont pas des appareils ménagers mais des composants destinés exclu...

Page 55: ...3 l 55 EDKZN3B024 DE EN FR 3 0 3 3 Équipement livré Nombre Description 1 Filtre 1 Instructions de montage 3 4 Présentation générale EZN 051 Position Description 0 Alimentation réseau 1 Raccordement de l appareil de base 3 Plaque signalétique ...

Page 56: ...Germany Type 8200vec080 Fig 3 1 Plaque signalétique Codification des types E Z N 3 x xxxx H xxx xxxx Série d appareils Accessoires Type de filtre N filtre réseau Nombre de phases 3 3 phases Classe d antiparasitage suivant EN 61800 3 A classe C2 B classe C1 Inductance Ex 0055 0 55 mH Courant nominal Ex 060 60 A Variante de filtre opt ...

Page 57: ...e tension Conformité eurasienne RT UD Règlement technique de l Union Douanière Informations sur les réseaux Configurations réseau Avec point Y à la terre réseaux TT TN Utilisation sans restriction Autres configurations réseau Respecter les indications concernant les mesures particulières dans la documentation de l appareil de base Protection Indice de protection EN 60529 IP 20 Pas dans la zone de ...

Page 58: ... au dessus du niveau de la mer 1000 4000 m au dessus du niveau de la mer réduction de courant de 5 1000 m Pollution ambiante admissible EN 61800 5 1 Degré de pollution 2 Résistance aux chocs EN50178 IEC61800 5 1 Germanischer Loyd Conditions générales Résistance à l accélération jusqu à 0 7 g Conditions de montage Lieu de montage Armoire électrique Position de montage Au dessus de l appareil de bas...

Page 59: ...60 2 5 1 6 3 EZN3x0900H004 400 480 50 60 4 0 2 5 3 EZN3x0750H005 400 480 50 60 5 0 3 1 3 EZN3x0500H007 400 480 50 60 7 0 4 4 3 EZN3x0400H009 400 480 50 60 9 0 5 6 3 EZN3x0300H013 400 480 50 60 13 0 8 1 3 EZN3x0250H015 400 480 50 60 15 0 9 4 3 EZN3x0150H024 400 480 50 60 24 0 15 0 3 Température dans l armoire électrique Puissance dissipée Inductance Chute de tension PV W L mH DU V EZN3x2400H002 17 ...

Page 60: ...Spécifications techniques Caractéristiques mécaniques 4 l 60 EDKZN3B024 DE EN FR 3 0 4 3 Caractéristiques mécaniques EZN 052 Cotes en mm ...

Page 61: ...DE EN FR 3 0 Type Cotes Poids a a1 b b1 e m n mm kg EZN3x2400H002 150 120 230 125 78 135 2 5 EZN3x1500H003 3 1 EZN3x0900H004 3 2 EZN3x0750H005 180 150 97 165 5 2 EZN3x0500H007 5 6 EZN3x0400H009 5 9 EZN3x0300H013 260 230 135 245 92 11 5 EZN3x0250H015 12 4 EZN3x0150H024 12 5 ...

Page 62: ...ions d utilisation décrites dans les spécifications techniques 57 Si nécessaire prendre des mesures complémentaires ƒ La plaque de montage de l armoire électrique doit présenter les caractéristiques suivantes Conductivité électrique Pas de vernis ƒ Les liaisons mécaniques doivent toujours être assurées ƒ Veiller à assurer une bonne circulation de l air en vue de la dissipation de la chaleur ...

Page 63: ...l 63 EDKZN3B024 DE EN FR 3 0 5 2 Modèle de perçage EZN 053 Cotes en mm Type Cotes e1 m n mm EZN3x2400H002 39 135 EZN3x1500H003 EZN3x0900H004 EZN3x0750H005 48 5 165 EZN3x0500H007 EZN3x0400H009 EZN3x0300H013 21 5 245 92 EZN3x0250H015 EZN3x0150H024 ...

Page 64: ...EDKZN3B024 DE EN FR 3 0 5 3 Opérations de montage EZN 054 Pour monter le filtre 1 Préparer la plaque de montage conformément au plan d alésage 2 Monter le filtre sur la plaque de montage à l aide de 2 ou 4 vis M6 selon les versions et de rondelles plates ...

Page 65: ...rme EN 60204 1 ƒ Lors du choix du type de câble tenir compte des points suivants Les câbles utilisés doivent être conformes aux homologations requises sur le lieu d utilisation exemples VDE UL etc Les fusibles et les sections de câble doivent être dimensionnés conformément aux prescriptions figurant dans la documentation de l appareil de base ƒ Lors de la pose du câble PE tenir compte du point sui...

Page 66: ...allation électrique Schéma de câblage 6 l 66 EDKZN3B024 DE EN FR 3 0 6 2 Schéma de câblage L1 L1 L1 L2 L2 L2 Load Line EZN L3 L3 L3 PE PE PE L3 N PE L1 L2 F K1 GN YE BK BK BK 0 EZN003 0 Variateur de vitesse ...

Page 67: ...N FR 3 0 6 3 Données de raccordement mm2 AWG mm Nm lb in EZN3x2400H002 0 2 4 0 25 4 0 5 1 5 24 10 8 0 6 0 8 5 3 7 1 EZN3x1500H003 EZN3x0900H004 EZN3x0750H005 EZN3x0500H007 EZN3x0400H009 EZN3x0300H013 EZN3x0250H015 0 2 6 0 25 6 0 5 4 24 8 9 1 5 1 8 13 2 15 9 EZN3x0150H024 ...

Page 68: ...der le filtre 1 Couper la tension dans l armoire électrique et s assurer que toute mise sous tension est exclue 2 Relier les câbles de raccordement de l appareil de base au bornier Load 2 Respecter les instructions de montage de l appareil de base 3 Relier les câbles réseau au bornier Line 0 Respecter le couple de serrage ...

Page 69: ...Installation électrique Opérations de montage 6 l 69 EDKZN3B024 DE EN FR 3 0 ...

Page 70: ...Str 1 D 31855 Aerzen Germany Service Lenze Service GmbH Breslauer Straße 3 D 32699 Extertal Germany 49 5154 82 0 008000 2446877 24 h helpline Ê 49 5154 82 2800 Ê 49 5154 82 1112 lenze lenze com service lenze com ü www lenze com EDKZN3B024 Oe DE EN FR 3 0 TD29 10 9 8 7 6 5 4 3 2 1 ...