background image

 

RFM-Setup tipps

 

Leuze 

electronic

 

Page 1 of 3 

Leuze 

electronic

 

Notes for Installation and Setting up 
 

RFM 12/ RFM 32/ RFM 62 with Leuze multiNet at MA 21 100.2 

 

Installation 

 

For RS 485 networks it is important to avoid A-/B-wire interchanges. A separat 
network ground line is recommended, too. The shield should be connected 
only on one side. At the last slave in line, the network has to be terminated by a 
220 

 resistor. After mounting the RFM and MA, turn the address switch of 

each MA 21 100.2 to the dedicated address and set DIP-switch 1 to ON 
(„Transparent-Mode“), for network operation set DIP-switch 3 („Service“) to 
OFF. At the multiNet master (MA 31) the total number of slaves has to be set. 
Before switching on the power supply please check the wiring.  
 
 

Setting Up 

 

When the firmware is started, the MA 21 and the RFM give a ready sign on the 
network with „XXs“ (XX is the slave address). The parameter setting can be 
done either with each device via Service interface or via multiNet master and 
the slave address in front of the command („01V“). If all slaves should be set to 
the same parameters, you can set a“00B“ in front of the parameter string and 
send it to the master device. After the setting of the parameter, please make 
sure that all DIP switches are set to „HOST„ („operation“). 
For more details concerning the MA 21 please see the technical manual of the 
MA 21.  
 

Troubleshooting 

 

Error 

Possible causes 

Remedy 

Master reports, 
connected slaves  
Don't 

1-  A/B-interchange 
     or interruption 
     / net resistors 
      false installed 
2-  Number of slaves 

not set 

3-  DIP switch 3 / 4    

set false 

1-  Check wiring and correct it, if 

necessary install 220 

 

resistors at end of line 

 
2-  Set Number with switch in  

master device (MA31)  

3-  Set DIP switch 3 to HOST/ 

OFF, DIP switch 4 to BCL/RFM 
/ ON 

On Service interface MA 31 with 
terminal use command „00BV“ 
to check Slaves     

No message or error 
while Read /Write 
transponders 

MA 21: DIP 1 or 4  
setting is on OFF 
RFM: invalid 
commands  

MA 21: Set DIP 1 and 4 to ON 
 
RFM: Restart with „00BH“ 
command on service interface of 
master device 

 
 

5
0
1
1
9
5
5

Reviews: