background image

Model 17A00 

Expansion Enclosure

Installation Manual

W

EB VER

S

ION

www.

.com

information@itm.com

1.800.561.8187

Summary of Contents for 17A00

Page 1: ...Model 17A00 Expansion Enclosure Installation Manual WEB VERSION www com information itm com 1 800 561 8187 ...

Page 2: ...1HYHU SXVK REMHFWV RI DQ NLQG LQWR WKLV SURGXFW WKURXJK RSHQLQJV DV WKH PD WRXFK GDQJHURXV YROWDJHV 1HYHU LQVWDOO FRPPXQLFDWLRQV ZLULQJ RU FRPSRQHQWV GXULQJ D OLJKWQLQJ VWRUP XVH LQ ZHW ORFDWLRQV 1HYHU WRXFK XQLQVXODWHG ZLUHV RU WHUPLQDOV XQOHVV WKH ZLULQJ KDV EHHQ GLVFRQQHFWHG DW WKH QHWZRUN LQWHUIDFH 8VH FDXWLRQ ZKHQ LQVWDOOLQJ RU PRGLI LQJ FRPPXQLFDWLRQV ZLULQJ RU FRPSRQHQWV 6 9 7 6 16758 7 216...

Page 3: ...2 POWER SUPPLY CHECKOUT 12 COMMUNICATIONS CHECKOUT 13 BURGLARY ZONE CHECKOUT 13 FIRE ZONE CHECKOUT 14 OUTPUT CHECKOUT 14 TROUBLE CONDITIONS 14 UNDERWRITER S LABORATORIES UL REQUIREMENTS 15 FEDERAL COMMUNICATIONS COMMISSION FCC NOTICE 16 SMOKE DETECTOR INSTALLATION GUIDELINES 16 FIGURE 1 MODEL 17A00 HOOKUP 3 FIGURE 2 OVERALL CONNECTIONS DIAGRAM 5 FIGURE 3 FIRE ZONE CONNECTIONS 7 FIGURE 4 RELAY MODU...

Page 4: ...le two conductor cable Each of the zone inputs may be used as a burglary zone a fire zone a temperature zone or an auxiliary input Each zone may also be used for connection of a Model 1101 Programmable Energy Saver Module PESM The Expansion Enclosure provides 16 general purpose voltage outputs These voltage outputs can be used to operate 12VDC relays or other low voltage switching applications The...

Page 5: ...mps ADDRESS SETTINGS DIP switch S1 is used to set the communications address for the Expansion Enclosure Up to four Expansion Enclosures can be addressed and used with OmniPro and up to eight Expansion Enclosures can be addressed and used with OmniPro II Expansion Enclosures 1 4 are addressed by setting the corresponding switch to on and all others off For example to set the address for the first ...

Page 6: ...Page 3 FIGURE 1 MODEL 17A00 HOOKUP WEB VERSION www com information itm com 1 800 561 8187 ...

Page 7: ...rs and other security devices meet this requirement An external 1000 ohm end of line resistor must be used for all burglary zones Connect the loop to the and terminals for the desired zone 1 When using a normally open switch a 1000 ohm end of line resistor must be in parallel with the zone being used Maximum loop resistance excluding end of line resistor should not exceed 150 ohms 2 When using a n...

Page 8: ...Page 5 NOTE FIGURE 2 OVERALL CONNECTIONS DIAGRAM WEB VERSION www com information itm com 1 800 561 8187 ...

Page 9: ...losed for alarm 4 wire SYSTEM type smoke detectors ESL Model 445AT or equivalent rated 8 14 VDC 2 Power smoke detectors from SWITCH 12 VDC 3 End of line resistor 1000 ohms The maximum loop resistance EXCLUDING the end of line resistor is 150 ohms 4 Use LEVITON Model 1503A0011 End Of Line Resistor Assembly in UL Listed Installations 5 End of Line Relay Module ESL Model 204B or equiv required for UL...

Page 10: ...Page 7 FIGURE 3 FIRE ZONE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...

Page 11: ...cuit breakers silent relays for high voltage current applications sprinkler valves pool pump controls and various other low voltage switching applications Connect the green pigtail wire J1 to ground GND on the Expansion Enclosure Each relay on the Relay Module will use one voltage outputs on the Expansion Enclosure Each output is connected to one of the trigger inputs T1 T8 When an output unit is ...

Page 12: ...Page 9 FIGURE 4 RELAY MODULE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...

Page 13: ...VDC GND Terminal 2 Red Wire to AUXILIARY 12VDC terminal Terminal 3 Yellow Wire to the ZONE terminal An outdoor temperature sensor mounts in an outdoor location usually under an overhang and sends the outdoor temperature the Expansion Enclosure It is coated with a sealant to withstand outdoor moisture The outdoor temperature can be displayed on the console spoken over the telephone or displayed on ...

Page 14: ...Page 11 24 HOUR STANDBY Maximum current ratings for 24 hours Auxiliary 12V Switch 12 V and Outputs 1 16 400 Ma WEB VERSION www com information itm com 1 800 561 8187 ...

Page 15: ...puts Bypass all panic tamper and fire zones POWER SUPPLY CHECKOUT 1 Disconnect the positive red wire to the battery Make sure that it is not touching anything 2 Plug in the power transformer The AC ON LED should illuminate The STATUS LED should begin blinking which indicates that the processor and software are working properly 3 Unplug the power transformer to turn off the system Connect the red b...

Page 16: ...all doors and windows are closed all motion detectors and security devices are normal and all fire sensors are reset 1 Restore all security zones Verify that the console reads SYSTEM OK 2 Check the wiring for any zones that are in alarm or in trouble 3 Have a partner go around the house and trip each sensor one at a time The display should indicate the correct zone when the zone is tripped then re...

Page 17: ...CHECKOUT Command each voltage output individually Verify that the correct device is activated Verify that the device is turned on when an ON command is issued and turned off when an OFF command is issued For a complete list of output unit numbers refer to the controller Owner s Manual that was supplied with the system TROUBLE CONDITIONS The Expansion Enclosure reports the following trouble conditi...

Page 18: ...l be the Revere P N RT 2440SL and 2 12 V 7 amp hour batteries 2 If used in UL applications the Model 17A00 and the controller shall be configured for 24 hour Standby Time as shown under 24 HOUR STANDBY CONNECTIONS diagram in this manual Maximum current ratings for 24 hours must be observed 3 Burglary Zone Hookup using LEVITON P N 393 1K 1000 ohm EOL resistor 4 Fire Zone Hookup using LEVITON P N 15...

Page 19: ... Do not install smoke detectors where normal ambient temperatures are above 100 F 37 8 C or below 40 F 4 C Also do not locate the detector in front of air conditioners heating registers or other locations where normal air circulation will keep smoke form entering the detector 3 Additional information on Household Fire Warning is available at nominal cost from The National Fire Protection Associati...

Page 20: ...LJQHG WR SURYLGH UHDVRQDEOH SURWHFWLRQ DJDLQVW KDUPIXO LQWHUIHUHQFH LQ D UHVLGHQWLDO LQVWDOODWLRQ 7KLV HTXLSPHQW JHQHUDWHV XVHV DQG FDQ UDGLDWH UDGLR IUHTXHQF HQHUJ DQG LI QRW LQVWDOOHG DQG XVHG LQ DFFRUGDQFH ZLWK WKH LQVWUXFWLRQV PD FDXVH KDUPIXO LQWHUIHUHQFH WR UDGLR FRPPXQLFDWLRQV RZHYHU WKHUH LV QR JXDUDQWHH WKDW LQWHUIHUHQFH ZLOO QRW RFFXU LQ D SDUWLFXODU LQVWDOODWLRQ I WKLV HTXLSPHQW GRHV FD...

Page 21: ...LER OR AN EXPERIENCED RADIO 46 TECHNICIAN FOR HELP LEVITON LIMITED WARRANTY Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that products manufactured by Leviton under the Leviton brand name Product will be free from defects in material and workmanship for the time periods indicated below whichever is shorter s MNI0R O AND UMINA 0R O three 3 years from ins...

Reviews: