background image

Page 1 

 

MSU-DFX SERIES 

Installation Instruction  

ERP: IIS00344 

03/11/2022  

Rev1.0 

IMPORTANT SAFEGUARDS 

 

When using electrical equipment, basic safety precautions should always be followed including the following: 

 

 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

 

a) This equipment is designed for use with germicidal UV radiation sources and must be installed in compliance 

with competent technical directions to prevent risk of personal injury from UV radiation. 

 

b) UV radiation can pose a risk of personal injury. Overexposure can result in damage to eyes and bare skin. To 

reduce the risk of overexposure this equipment must be installed in accordance with the manufacturer’s site plan-

ning recommendations. This may include instructions on the relative location of each germicidal system compo-

nent, the minimum distances between UV-generating devices and other objects or surfaces, and protection from 

line-of-sight exposure to UV radiation in occupied spaces located above the equipment mounting area (e. g. upper 

floor balconies, open staircases, etc.) 

 

c) UV and optical radiation can be reflected by surrounding surfaces such as ceilings and walls. Since the reflec-

tive properties of surfaces can vary widely, it should be considered as part of site planning. Follow the manufactur-

er’s recommendations for selecting appropriate ceiling and wall finishes. 

 
d) 

IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT PERSONS WILL 

NOT BE EXPOSED TO EXCESSIVE UV OR OPTICAL RADIATION DURING EQUIPMENT 

OPERATION. THIS WILL REQUIRE THE INSTALLER TO CONDUCT AN ASSESSMENT OF 

IRRANDIANCE OR ILLUMINANCE LEVELS IN THE SURROUNDING OCCUPIED SPACES 

PRIOR TO OCCUPANCY. 

 

e) Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by 

unauthorized personnel. 

 

f) Maintenance and servicing of this UV generating equipment shall be performed by authorized personnel. Ser-

vice personnel must wear appropriate Personal Protective Equipment (PPE) if the equipment will be in operation 

during the maintenance or servicing work. Contact the equipment manufacturer for PPE recommendations and 

guidance. 

 

g) The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 

 

h) Do not use this equipment for other than intended use. 

 

i) 

This fixture is not suitable for residential use.

 

 

 

SAVE THESE INSTRUCTIONS

 

Summary of Contents for MSU-DFX Series

Page 1: ...e reflected by surrounding surfaces such as ceilings and walls Since the reflec tive properties of surfaces can vary widely it should be considered as part of site planning Follow the manufactur er s recommendations for selecting appropriate ceiling and wall finishes d IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT PERSONS WILL NOT BE EXPOSED TO EXCESSIVE UV OR OPTICAL RADIATION DURING E...

Page 2: ...ling Burn Allow luminaire to cool before handling luminaire Personal Injury Wear safety glasses and gloves when handling the luminaire to avoid physical injury Avoid direct eye contact with light source Always support the weight of the luminaire Note The models requires an accurate cutout of the luminaire opening It is essential that the opening room side edge be flat to ensure the integrity of th...

Page 3: ... IIS00344 03 11 2022 Rev1 0 Hard Ceiling Flange Cont d Size Width Length 2x2 22 7 8 in 22 7 8 in 2x4 22 7 8 in 46 7 8 in Ceiling Cut Out Dimensions Frame not supplied 1 5 8 Unistrut or equal Ceiling cut out Swing out Support Brackets 4 pcs Width Length ...

Page 4: ...ge This step may require two workers 8 Adjust mounting Swing out support bracket s on housing to overlap T bar and support fixture on center web of T bar Tighten 20 screws to transfer weight to T bar making sure gasket is com pressed and grid is level without deformation 9 Secure to structure using seismic support cables wires to holes on Swing out support brackets Consult local code for requireme...