CSU3000 Chiller For CTI PETNet Cyclotron w/o Redundancy 1
Keeping Business in Business
CSU3000 Chiller
For CTI PETNet Cyclotron w/o Redundancy
• Dedicated cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• Standard product ETL/CSA certified.
• ISO 9001 certified company.
PETNet Cyclotron Specifications
Fluid Specified
Water/Glycol
Max Heat Dissipation—BTUH (kW)
60,000 (17.6)
Fluid Temperature Range—°F (°C)
40-50 (4.4-10)
Fluid Flow Rate—GPM (l/m)
10 (38)
Fluid Pressure Drop—PSI (kPa)
5 (34)
CSU Chiller Specifications
Model Number
CS109A
Fluid Circulated
Water
Net Cooling Capacity—BTUH (kW)
121,900 (35.7)
Leaving Fluid Temperature—°F (°C)
45 (7.2)
Fluid Flow Rate—GPM (l/m)
24 (91)
PETNet Cyclotron Pressure Drop—PSI (kPa)
5 (34)
Chiller Pressure Drop—PSI (kPa)
8.4 (58.1)
Pump Total Head—PSI (kPa)
35.9 (247.7)
Pump HP (kW)
1.5 (1.1)