Zone Leak Detection Module With Cable

Product Specification Sheet

Description 

The Liebert Liqui-tect 460 (LT460) provides zone 

detection of leaks, protecting equipment by con-

stantly monitoring the area for leaking liquids. The 

LT460 is the ideal solution for perimeter sensing or 

serpentine coverage of areas requiring up to 100 feet 

of cable.
Selectable modes of 

operation provide flexi-

ble alarming options 

and protection for the 

cable. The LT460 con-

stantly monitors a zone 

for leaks, internal 

faults and power fail-

ures and warns of any 

abnormal conditions. 

Top cover LEDs provide 

status indication and also ensure the cable is prop-

erly installed and operational under raised floors.
Two independent outputs provide a signal to a local 

alarm panel, Liebert environmental unit,

 

remote 

building management system or external equip-

ment, such as motorized water shut-off valves.
The LT460 kit is ideally suited for the following: 

Applications

• Glycol, Condenser Water and Chilled Water 

Cooling Piping Leak

• Humidification Feed Water Piping
• Condensate Pumps and Drains
• Unit and Ceiling Auxiliary Drip Pans
• Overhead Piping Troughs

Locations

• Large-Scale Network Control Centers
• Data Centers
• MRI, CAT Scan Rooms
• Server Rooms - Closets
• Unattended Remote Shelters
• Sensitive Areas With Overhead Piping
• Mechanical Equipment Rooms
• Industrial Process Control Rooms

Components

Liqui-tect 460 Module

The LT460 consists of a metal enclosure with a 

hinged top door providing access to the internal cir-

cuit board for wiring termination and configuration 

of DIP switches. The LT460 will monitor up to 100 

feet of connected LT500Y leak detection cable.

LT500Y Leak Detection Cable

The cable material and construction allow the cable 

to lie flat when used with hold-down clips. The 

LT500Y is plenum-rated and UL-listed for safe 

operation.

If obtained separately,

 

cables are available in 

lengths of 15, 35 and 50 feet. These cables can be 

connected incrementally to monitor from 15 feet 

up to 100 feet. An end terminator and hold-down 

clips (two clips required for each 6-8 ft. of cable) 

must be ordered separately.

If obtained in a kit,

 

cables are available in 

lengths of 20, 25, 30, 35 and 45 feet. Cables in kits 

cannot be lengthened. Hold-down clips are 

provided.
Refer to the matrix on page 2 (

Prepackaged 

Sizes for Liebert Units

) to select a 

preconfigured kit sized to specific lengths for 

Liebert environmental units.

Configuration Switch Settings

A four-position DIP switch is used to select two 

alarm (filter) delays and three mutually exclusive 

alarm modes. The switches are located next to the 

wiring termination blocks.

Switch Settings

OFF

ON

S1

1. Leak Detect Filter

10sec 2min

2. Alarm Latch

No

Yes

3. Alarm Retest Delay

No

1hr

4. Not Used

Contacts

Rating:

24V,3A

CONNECT ENCLOSURE TO EARTH GROUND

TB3-3
TB3-2
TB3-1

TB2-3
TB2-2
TB2-1

TB1-2

TB1-1

Contacts

Rating:

24V,3A

24V 

50/60Hz

0.12A

2

1

N.C.
C

N.O.

N.C.
C

N.O.

ALL CIRCUITS: CLASS 2

Contacts shown in POWERED, NON-ALARM state

Summary of Contents for Liqui-tect 460 Kits

Page 1: ...nts Liqui tect 460 Module The LT460 consists of a metal enclosure with a hinged top door providing access to the internal cir cuit board for wiring termination and configuration of DIP switches The LT460 will monitor up to 100 feet of connected LT500Y leak detection cable LT500Y Leak Detection Cable The cable material and construction allow the cable to lie flat when used with hold down clips The ...

Page 2: ... 1 ft 6 ft No cable 1 ft 6 ft Unit footprint in PART NUMBER Challenger 32 5 x 32 5 LT460 Z30 LT460 Z20 LT460 Z30 LT460 Z25 Himod 69 x 35 LT460 Z35 LT460 Z20 LT460 Z35 LT460 Z25 Deluxe System 3 50 x 35 LT460 Z30 LT460 Z20 LT460 Z35 LT460 Z25 74 x 35 LT460 Z35 LT460 Z20 LT460 Z35 LT460 Z25 99 x 35 LT460 Z45 LT460 Z25 LT460 Z45 LT460 Z30 122 x 35 LT460 Z45 LT460 Z25 LT460 Z45 LT460 Z30 DS 73 x 35 LT4...

Page 3: ...TB1 2 TB1 1 TB1 Liebert Mini Mate2 1 to 5 ton LT460 Requires a 24V external transformer there are no designated terminal connections on the unit Challenger Himod or MM2 8 Ton TB1 T5 24V G5 Ground LT460 TB1 TB1 1 TB1 2 Transformer LT460 TB1 TB1 1 TB1 2 From 24V transformer 24V from Transformer to LT460 Liebert MM2 1 to 5 Ton LT460 TB1 TB1 1 TB1 2 4V transformer of here are no ated terminal tions 24...

Page 4: ... Liebert contact monitor panel Liebert Deluxe Sys 3 Challenger Himod or MM2 8 Ton 24 24V 51 LT460 TB2 TB2 2 C TB2 1 N O TB2 3 N C Env Unit Liebert MM2 1 to 5 Ton TB1 1 24V TB1 2 LT460 TB2 TB2 2 C TB2 1 N O TB2 3 N C Env Unit OR TB2 TB2 2 C TB2 1 N O TB2 3 N C Env Unit TB1 1 24V TB1 3 Liebert MM2 1 to 5 Ton LT460 TB2 3 N C TB2 Liebert DS LT460 TB2 2 C TB2 1 N O Environmental unit 24 24V 50 51 55 or...