READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING LUMINAIRE 

This luminaire is intended for installation in accordance with the National Electrical Code and local regulations.  

To assure full compliance with local codes and regulations, check with your local electrical inspector before  

installation.  To prevent electric shock, turn off electricity at fuse box before proceeding. 

Retain these instructions for maintenance reference. 

IS:EMBW

 

INSTRUCTION SHEET NO. 

C0512

 

Page 1 of 2

 

IMPORTANT SAFEGUARDS 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

 

WHEN USING ELECTRICAL EQUIPMENT , BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED INCLUDING: 

1. 

Turn off AC power before proceeding.

 

2.  Be sure all electrical connections are complete and outlet box is closed before inverter connector on emergency pack is connected. 
3.  Do not use outdoors. 
4.  Do not mount near gas or electrical heaters. 
5.  Do not attempt to service the battery. A sealed, rechargeable, no maintenance battery is used. Do not incinerate or mutilate; may 

burst or release toxic materials. Do not short circuit; may cause burns. Battery acid can cause burns to skin and eyes. If acid is spill 
on skin or eyes, flush with water and contact a physician immediately. 

6.  Equipment should be mounted in locations and at a height where it will not readily be subject to tampering by unauthorized           

personnel. 

7.  The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition. 
8.  Do not use equipment for other than intended use. 
9.  This unit has more than one power supply connection point. To reduce the risk of electrical shock , disconnect both the normal and 

the emergency power supplies before servicing. 

10.  Before servicing to prevent electrical shock, disconnect the battery connector on the emergency pack (located inside the ballast 

housing). Make certain that the switch (if luminaire is switched) and the unswitched lines to the emergency pack are turned off at the 
fuse box. Servicing should be performed by qualified personnel only. 

1.  Make sure AC power is off at fuse box. 

2.  Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required for the emergency pack. 

3.  The emergency pack must be fed from the same branch circuit as the AC ballast. 

4.  In switched luminaires, “unswitched” lead must be connected ahead of any local switching. 

5.  Make supply wire connections. Use wire nuts (local hardware item). SEE PAGE 2 FOR WIRING DIAGRAM. Unhook LOOP and 

BACKPLATE ASSEMBLY. Push supply wires and connections back into outlet box. 

6.  Connect battery pack before supplying power to emergency ballast. 

7.  Inverter connector is joined last.  

SAVE THESE INSTALLATION INSTRUCTIONS 

WARNING: 

TO PREVENT  DAMAGE  TO  THE EMERGENCY BALLAST, JOIN THE BATTERY CONNECTOR 

BEFORE SUPPLYING AC POWER TO THE EMERGENCY BALLAST. 
TO  PREVENT  HIGH  VOLTAGE  ON  THE  BLUE/RED  &  YELLOW/RED  OUTPUT  LEADS  PRIOR  TO 
INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN INVERTER CONNECTOR UNTIL 
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. 

INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT  

EMERGENCY LIGHTING DECORATIVE LUMINAIRES 

NOTE:   THIS INSTRUCTION SHEET IS TO BE USED IN CONJUNCTION WITH INSTRUCTIONS SUPPLIED FOR THE                     
 

INSTALLATION  OF SPECIFIC MODEL BEING INSTALLED. 

A. WIRING — READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE PROCEEDING. 

® 