Series TSF-DF Digital Thermocouple Limit Alarm
Specifications - Installation and Operating Instructions
Bulletin T-TSF-DFA/M
The
Series TSF-DF Digital Thermocouple Limit Alarm
is a UL approved temperature
limit control that provides visual alarm status, along with a 16 amp SPST relay output
when a process temperature limit has been reached. After the input temperature
returns to normal conditions, the alarm can be either manually or automatically reset
depending on how the unit is programmed.
INSTALLATION
Note:
Unit must be mounted away from vibration, impacts, water and corrosive gases.
• Cut hole in panel 2.80 x 1.14 inches (71 X 29 mm).
• Use the included gasket, or apply silicone around the perimeter of the hole to
prevent leakage.
• Insert unit into the hole in panel, and secure using the included mounting clips.
• Wire the unit per the wiring diagram on the product label or in IOM.
SPECIFICATIONS
Probe Range:
32 to 999°F (0 to 700°C) for thermocouple Type J; 32 to 999°F (0 to
999°C) for thermocouple Type K.
Input:
Type J or K thermocouple.
Output:
NO SPST relay rated 16A @ 240 VAC resistive.
Horsepower Rating (HP):
1 HP.
Control Type:
ON/OFF; manual/automatic reset.
Power Requirements:
115 VAC, 230 VAC, 12 VAC/VDC or 24 VAC/VDC
(depending on model).
Power Consumption:
4 VA @ 230 VAC.
Accuracy:
±1% FS.
Display:
3-digit, red, blue, 1/2˝ (12.7 mm) digits, plus sign depending on model.
Resolution:
1°.
Memory Backup:
Nonvolatile memory.
Ambient Operating Temperature:
32 to 140°F (0 to 60°C).
Storage Temperature:
-4 to 176°F (-20 to 80°C).
Weight:
2.3 oz (65 g).
Front Panel Rating:
IP64.
Agency Approvals:
DF Models: CE, cUR, UR.
1-3/8
[33.99]
3
[76.20]
1-1/8
[27.94]
2-3/8
[60.33]
Wiring Diagram
1
2
3
4
5
6
8
9
PROBE
INPUT
TS2-K
KEY PORT
POWER
SUPPLY
COM
OUTPUT
NO
+
-
LOVE CONTROLS
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
A DIVISION OF
DWYER INSTRUMENTS, INC.
www.lovecontrols.com
e-mail: love@love-controls.com