© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
ZEB2-1_DBL_LST_EN_0826.PDF • PAGE 1
A
Building Safety. Building Security.
Description
With the Zone Extension Board ZEB2-1 a Fire Detection
Control Panel BC06-1 or BC06-2 can be extended from
four to six detector zones. In the event of an alarm, the
fi re detection control panel indicates the activation of
the detector zone via LED. Depending on the detector
type, each of the two detector lines can be individually
parameterised as detector zone for fi re alarms or as
detector zone for fault messages.
Alarms from manual call points and from automatic de-
tectors that are connected together to a detector line
can be differentiated and thus evaluated differently by
the fi re detection control panel, by means of an optional
coding module.
Each input of the zone extension board is protected
against overvoltage and thus provides high system sta-
bility.
• Extends Fire Detection Control Panels
BC06-1 and BC06-2 by further 2
conventional detector zones
• Individual setting of detector zone
function
• Differentiation between the activation
of automatic detectors and manual
call points on the same detector line
• Lines monitored for wire breakage,
short circuit, and short to earth
Specifi cations
Current consumption at 24V
typ. 14mA (line termination 5.6k
Ω
, without detectors)
typ. 7mA (line termination 47µF, without detectors)
Line voltage
typ. 20V (line termination 5.6k
Ω
)
typ. 23V (line termination 47µF)
Line current
typ. 3.7mA (line termination 5.6k
Ω
)
typ. 0mA (line termination 47µF)
Line termination
5.6k
Ω
or 47µF
Line resistance
max. 50
Ω
per core
Ambient temperature
-5°C to +50°C
Dimensions L × W × H
103 × 58 × 15 (mm)
Weight
34g
Order number
210210
Order name
Zone Extension Board ZEB2-1