EMERGENCY LIGHTING TESTING

Months 1 to 11 inclusive – Function Test, interrupt the permanent/UnSwitched supply and check the luminaire operates in Emergency 

mode at reduced output

Month 12 (Annual) – As months 1 to 11 but for a full 3hr duration

Luminaire Ref / Location:

  ........................................

In Case of difficulty, contact the Installation Engineers:- 

Tel: .........................................................

LHBCx11Exx/LHBCx22EXX

Duration 3hr

Lamp Type - LED

INITIAL USE AND ROUTINE TESTING

From initial install the downlight will require up to 24hr for the batteries to be fully charged and provide the rated 3hr duration  
in Emergency mode. Then following subsequent Emergency use, from full discharge will take approx. 14hr to fully recharge batteries.

It is important that the luminaire is routinely tested to ensure the batteries are conditioned and also to fully comply with BS5266. 
A function test should be conducted every month with an annual test of the full 3hr duration. Records can be kept on the adjacent table.

It is recommended that batteries are replaced every 4 years to ensure the optimum charging cycle is maintained.  

Month

Test

1

Function

2

Function

3

Function

4

Function

5

Function

6

Function

7

Function

8

Function

9

Function

10

Function

11

Function

Annual

Full Test

Signed

Date

Fifth Year

Signed

Date

Fourth Year

Signed

Date

Third Year

Signed

Date

Second Year

Signed

Date

First Year

 

Page 1

Tech Help Line

UK -

 0330 0249 279

Non UK -

 +44 (0)1952 238 100

Supplied by LUCECO

Stafford Park 1, Telford,  

Shropshire, England, TF3 3BD

Visit our website at

www.luceco.com

LHB.JH.04.2017

Tech Help Line

UK -

 0330 0249 279

Non UK -

 +44 (0)1952 238 100

Supplied by LUCECO

Stafford Park 1, Telford,  

Shropshire, England, TF3 3BD

Visit our website at

www.luceco.com

LHB.JH.04.2017

SUGGESTED METHOD OF INSTALLATION

1.  Identify a suitable location for installation. 

2.  Trunking:– This can be mounted using the central 20mm hole  

(a)  

 

For surface installation:– Use suitable fixing through fixing  

points 

(b) 

 

 

 

 

3.  The main housing is assembled to the bracket as shown.  

Larger bolt and washers are used for main fixings.  

Smaller bolt and washers are used for tilt adjustment slot 

Installation & Operating Instructions

LED INDUSTRIAL

CERES HIGHBAY

IP65

RATED

  1

WARRANTY

year 

on site

  5

WARRANTY

year 

extended

NOTE – To comply with regulations, installation must be carried out by suitably 

qualified competent person and in accordance with the current IEE Wiring 

Regulations (BS7671) and Building Regulations. A copy of the instructions must 

be left for the user/maintenance engineer for future reference.

For non-UK, please refer/consult local requirements
ENSURE ELECTRICAL SUPPLY IS DISCONNECTED/

ISOLATED BEFORE COMMENCING INSTALLATION

CRI

   80

>

ASSEMBLY AND INSTALLATION

•  Suitable for use with mains voltage 110-240V AC  

 

•  This product is pre-wired, with no user serviceable components.  

Opening the luminaire may void the IP65 rating and warranty

Installation & Operating Instructions

UK ONLY

70,000

HOURS

100,000

HOURS

50,000

HOURS

STANDARD EXTRA

ULTRA

a

b

2

3

Reviews: