Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA

Test

Link

Associate Transmitters to Fixture Control 

*

Before beginning this step, make sure that there are no other fixture controls being set up in the building which are currently in association 
mode. It is possible that wireless transmitters from other systems can be incorrectly associated to this module.

Important Note: 

To optimize RF performance of 

the product:  
–  Keep the lamp wiring as short as possible to 

reduce the radiation from the lamp wires.

–  Keep the lamp wiring as far as possible from 

the PowPak

R

 Wireless Fixture Control mounting 

location.

See the Troubleshooting section for more details.

PowPak

R

 Fixture Control Knockout

PowPak

R

 Fixture Control Wiring

Lamp Wiring

Maximize Distance

ce

Technical Assistance  |  1.800.523.9466  

USA, Canada, and the Caribbean

  |  +44.(0)20.7702.0657 

Europe

  |  +1.610.282.3800 

Others

  |  www.lutron.com

     

Part of the Energi TriPak

®

 Family

PowPak

®

 Fixture Controls

Installation

Required Components 

For each fixture, you will need:

PowPak

R

 Fixture Sensor 

(FC-SENSOR or  
FC-VSENSOR)

(1 maximum)

Pico

R

 Remote 

Control

(10 maximum)

6 mA maximum for the control lines. Switches up to 1 A total 
(or maximum 3 ballasts or drivers). May be pre-installed in fixture.

PowPak

R

 Wireless Fixture Control 

(FCJS-010 or FCJS-ECO)

Raise

Toggle

Lower

Load 
Status 
LED

Consult the fixture installation guide for fixture wiring. 

 Start Here

English

Important Notes: 

•  For installation by a qualified electrician in accordance with all local and 

national electrical codes.

•  Use copper conductors only.
•  Check to see that the device type and rating is suitable for the application.
• 

DO NOT

 install if product has any visible damage.

•  If moisture or condensation is evident, allow the product to dry completely 

before installation.

•  Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
•  0% to 90% humidity, non-condensing.
•  For indoor use only.

  120 – 277  V

~

  50 / 60 Hz  1 A switching

FCJS-010  

0–10 V

-

FCJS-ECO 
Lutron

®

   

EcoSystem

®

PowPak

®

 Wireless Fixture Control 

UL 2043 Plenum Rated

Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or 
driver to limit the sink/source current draw to 2.0 mA maximum).  

Provides IEC SELV / NEC

R

 

Class 2, 12 V

-

, 25 mA to a PowPak

fixture sensor  

(FC-SENSOR or FC-VSENSOR).

PIR Lens

Laser 
Detection

Daylight Lens

Radio Powr Savr

Occupancy/Vacancy 
Sensor

(10 maximum)

Radio Powr Savr

T

 

Daylight Sensor

(1 maximum)

Install Fixture Control and Optional Fixture Sensor

Suggested Installation Location: Close to the Fixture / Troffer.

 

The fixture control can be installed on a fixture/troffer, junction box or marshalling box using the 
conduit nut (provided) or with mounting screws (not provided). Please consult local and national 
electric codes for proper installation.

A

  Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using the 

adhesive strip (included). The two communication wires from the sensor attach to the fixture control 
stab-in connectors. The wires are interchangeable to eliminate miswiring. 

B

  Once installed, energize the control module. The fixture will turn on.

WARNING! Shock Hazard.

 

May result in serious injury or death. 

Turn off power at circuit breaker before installing the unit.

6 mA sink/source 

Notes:

 

1.  Fixture control can be used 

without a fixture sensor as long 
as at least one Radio Powr 
Savr

T

 sensor or Pico

R

 remote 

control is  used.

2.  Only one fixture control can be 

used per fixture sensor, and 
only one fixture sensor can be 
used per fixture control.

Pico

®

  

remote 
control

30 ft (9 m) 

maximum

PowPak

®

  

Fixture Control 

Install the fixture control directly to a fixture or 
on a junction box nearest to the fixture. Install 

the sensor on the ceiling near the fixture to 

optimize coverage in the desired area.

Fixture 
Control 

Sensor

For more information, see  
www.lutron.com/TechnicalDocumentLibrary/369866.pdf 

Notes:

1.  Control wires (Violet/Gray for FCJS-010 or Violet/Violet for FCJS-ECO) can be run 

as either Class 1 or Class 2.

2.  If hanging pendant fixtures the maximum wire length between fixture sensor and 

fixture control is 12 ft (3.7 m). Sensor should be mounted no more than 2 ft (0.6 m) 
from the fixture.

3.  To install unit inside a junction box, please see Application Note 423 on  

www.lutron.com

4.  The fixture control needs to be accessible for some programming steps. Record 

where it is mounted so that it can be easily located later.

5.  When using a Radio Powr Savr

T

 daylight sensor in conjunction with both a 

PowPak

R

 wireless fixture control and PowPak

R

 fixture sensor, the Radio Powr 

Savr

T

 daylight sensor will provide the daylighting input to the control module, and 

the PowPak

R

 fixture sensor daylighting input will be ignored.

6.  When using a Radio Powr Savr

T

 occupancy sensor in conjunction with both a 

PowPak

R

 wireless fixture control and PowPak

R

 fixture sensor, occupancy data 

from both sensors is used; either one detecting occupancy will turn the lights 
on, and the lights turn off only when both sensors have gone vacant (no longer 
detect occupancy).

7.  For more information on the PowPak

R

 fixture sensor, see: Document 369866 or 

048556 on www.lutron.com  
For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com 

Wireless sensors 
and controls must 
be located within 
60 ft (18 m) line of sight, 
or 30 ft (9 m), through walls, of 
the associated control module. 

Please read before installing.

+

One Fixture Control 

At least one of these transmitters (22 total allowed) 

FCJS-010:

 

At least one 0 – 10 V Fluorescent Ballast or LED Driver

FCJS-ECO:

 

At least one Lutron

®

 EcoSystem

®

 Ballast or LED Driver

+

1

2

  120 – 277  V

~

  50 / 60 Hz  1A switching

14 V

-

  6 mA

OR

Laser Detection

 

Green laser specifications: 

•  Wave output: constant
•  Wavelength: 532 nm
• Output power:  

5 mW maximum

Note:

 The fixture control 

will automatically exit 
association mode 10 
minutes after the last 
activity.

Wireless Controls: 

All lights

Default Functionality

Fixture Controls

Auto On level:

 

FC-SENSOR only

  

(not applicable for FC-VSENSOR)
Varies with ambient light level when occupancy is triggered 
(e.g., 100% for a dark room, 10% for a bright room).

Timeout period:

 15 minutes

On:

 100% ; 

Favorite

: 50%; 

Off

: 0% 

+

NEU

HOT

Class 2

MAINS

+

 Violet (both FCJS-010 and FCJS-ECO)

– 

Gray (FCJS-010) / Violet (FCJS-ECO)

Fixture Earth

Green/Yellow

Switched Line/Hot 
(Red)

Line/Hot 

(Black)

Neutral (White)

Neutral

Fixture/Troffer 
or Junction 
Box

1/2 in (21 mm) Knockout Opening

From back 
of sensor

Ballast / Driver

Conduit Nut

041507 
Rev. A
09/2015

B

   Hold the indicated button on each transmitter for 6 seconds. The fixture 

will flash to show that wireless transmitters have been associated. 
Alternatively, for Radio Powr Savr

T

 occupancy/vacancy and daylight 

sensors, the green laser pointer can be used. See Application Note 
#407 on www.lutron.com for more information. To associate another 
transmitter, repeat steps 

2A

 and 

2B

.

A

 

 Initiate association mode on the fixture control in one of two ways:

 

 1  Press and hold the 

Toggle

 button “ 

u

 ” for 6 seconds on the fixture control until the load attached to the fixture control starts flashing  

(every 2 seconds).

 

 2  Alternatively, shine a green laser pointer (available at hardware or office supply stores) at the laser detection hole on the sensor until the load 

attached to the fixture control starts flashing (every 2 seconds). 

 

 

Note:

 Multiple fixture controls can be placed into association mode by repeating one of the two above methods for the next fixture control prior to 

moving to Step 2B.

!

WARNING

  

 

!

DANGER

Eye injury and/or blindness hazard;

 avoid direct eye exposure to laser beam.

•  Use of laser pointer is NOT recommended for use with Lutron

®

 products located near reflective surfaces.

•  DO NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or through reflection by mirrors or other shiny surfaces. DO NOT 

view the laser beam through binoculars magnifying glass, or other optical devices.

•  DO NOT allow children to use laser pointers.  
• 

Read and follow the laser pointer manufacturer’s instructions on safe use.

 In the event of injury, get medical attention immediately.  

Note for Replacement:

FCJS - the "S" model can replace the non-"S" model

*

   For set-up, programming, and troubleshooting with a 

Vive

TM