Need Help?
Please visit the Hi-lume 1% page at www.lutron.com/europe or
call the Lutron Customer Assistance at
+44.(0)20.7680.4481
Hi-lume 1%
EcoSystem Constant-Voltage LED Driver
Installation
LDE1-96W24V-E / FXD196CEU
Output: 2 – 96 W 24 V
-
Input: 220 – 240 V
~
50 / 60 Hz, Max 110 W
Important Notes
: Please read before installing.
• For installation by a qualified electrician in accordance with all local and national electrical codes.
• Use copper conductors only.
• For indoor use only.
• Check to see that the driver type and rating are suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely before installation.
• Operate between 0 °C (32 °F) and 40 °C (104 °F) ambient.
• 0% to 90% humidity, non-condensing.
• Four 8-32 × 9.5 mm (3/8 in), serrated lid screws provided.
• For installation best practices, please refer to Application Note #591 at www.lutron.com
* Driver and control must be grounded in accordance with local and national electrical codes.
Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299
English
Mounting (mount as shown on the right)
1. Remove top cover to access multi-sided mounting key holes.
2. Mount driver either horizontally or vertically as shown.
Note
: Minimum of 75 mm (2.95 in) required between any two
LED drivers.
Note
: Install in accordance with all national and local electrical codes.
Note
: Driver should be mounted in an accessible location.
Note
: Any other mounting configuration will require additional
mechanical support. Improper installation may result in hazards
to personnel or property.
Note
: Recommended minimum mounting screw diameter is 4 mm (0.15 in).
Wiring (wire as shown below)
WARNING: Shock Hazard. May result in serious injury or
death.
Turn off power at circuit breaker before installing the unit.
1. Remove the top cover to access the terminal blocks and mounting hardware.
2. Choose single or multiple driver wiring. Open necessary knockouts.
3. Install input cord grip(s) in knockouts (
A
B
C
D
E
and
A
B
C
D
E
), pass wire/cord into the wiring compartment, and tighten.
4. Install output grommet (
A
B
C
D
E
) and output cord grips (
A
B
C
D
E
and
A
B
C
D
E
), install wire and tighten.
5. Connect the necessary wires according to the illustration below. For E1 / DA1 and E2 / DA2 wiring, please refer to Application Note #142.
Terminals accept 0.75 mm
2
to 2.5 mm
2
(18 AWG to 12 AWG).
6. Ensure compatible control and load are installed and restore power to the circuit. See reverse side for Compatible Controls.
041580 Rev. A
12/2016
Required Components
For each system, ensure that you have:
At least one compatible
LED Load (light engine)
3,4
1
See list of compatible controls on the reverse side.
2
Please refer to the control installation sheet for wiring instructions.
3
Refer to LED load manufacturer instructions for proper installation practices.
Load ratings must match driver output ratings.
4
For connection to voltage driven loads only. Not for use with LED modules/loads that
include active logic circuits.
At least one Hi-lume
1% LED Driver
At least one
compatible control
1,2
lutron.com
EcoSystem Wiring Diagram
Hi-lume
1% LED
Driver
E1 / DA1
E2 / DA2
Live (L)
Neutral (N)
Neutral
Live
LED
Light
Engine
Earth* (
D
)
Earth*
To EcoSystem or
DALI Digital Link
LED +
LED –
86 mm
(3.375 in)
2x wires
4x wires
Multiple Driver Wiring (Up to 30)
Ensure that earth leads are at
least 50 mm (2 in) longer than
other leads. Twist leads before
inserting in the terminal.
Feed from panel
or other driver
To next driver
LED- LED+ E1/
DA1
E2/
DA2
L
N
}
}
} }
}
}
Single Driver or End-of-Run Wiring
Feed from panel
or other driver
LED- LED+ E1/
DA1
E2/
DA2
L
N
}
}
}
}
}
}
Ensure that earth lead is at
least 50 mm (2 in) longer than
other leads.
A
B
C
D
E
A
B
C
D
E
A
B
C
D
E
A
B
C
D
E
A
B
C
D
E