background image

LED Driver Installation

Best Practices Guide

Driver Mounting

Mount the driver flush against the fixture to provide the best heat transfer. Avoid mounting the driver close to a heat source such as a fixture cover plate or a 

light source. For use only within a suitable electrical enclosure or fixture.

Correct

Incorrect

Accommodates #6 screws for mounting. Tighten screws to a maximum of 8 in-lb (0.9 N•m).

Power Wiring

1

  Class 2 must be separated from Class 1 and line voltage wiring by the following: 0.25 in 

(6 mm) or physical barrier. Please refer to Application Note #142 for further information.

2

  EcoSystem digital link length is limited by the wire gauge used for E1 and E2 as shown below.

EcoSystem

Digital Link

(Class 1 or Class 2) 

1,2

Power Input

(Line Voltage)

Driver Wiring

For proper wiring, follow the wiring schematic on the driver being installed. Driver illustrations are for reference only.

Driver Enclosure

1.60 in (41 mm) W × 1.05 in (27 mm) H × 4.30 in (117 mm) L

Load Wiring

Wire Gauge

Maximum Lead Length

150 mA  – 700 mA 710 mA  – 1.05 A

18 AWG (0.75 mm

2

) 30 ft (9 m)

15 ft (4.5 m)

16 AWG (1.5 mm

2

) 35 ft (10.5 m)

25 ft (7.5 m)

14 AWG (2.5 mm

2

) 50 ft (15 m)

40 ft (12 m)

12 AWG (4.0 mm

2

) 100 ft (30 m)

60 ft (18 m)

Lutron Customer Assistance 

1.844.LUTRON1 

(1.844.588.7661)

)

Lutron, Lutron, and EcoSystem are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and 

other countries.
NEC is a registered trademark of the  National Fire Protection Association, Quincy, Massachusetts.
UL is a registered trademark of Underwriters Laboratories, Inc.

www.lutron.com/support

P/N 041660b

01/2019

See table below

–V (Black)

+V (Red)

LED Light 

Source

Black

White

Purple

Purple / White

L
N

E1
E2

EcoSystem Digital Link Wiring

Both wires of the EcoSystem link are included in maximum digital lead length.

Wire Gauge Digital Link Length (max)

18 AWG

550 ft

16 AWG

900 ft

14 AWG

1400 ft

12 AWG

2200 ft

Wire Size

Digital Link Length (max)

0.75 mm

2

155 m

1.0 mm

2

207 m

1.5 mm

2

310 m

2.5 mm

2

517 m

4.0 mm

2

828 m

To EcoSystem Digital Link compatible devices

3.94 in

(100 mm)

1.25 in

(32 mm)

Installing or Servicing LED Driver or Light Engine

Shock hazard.

 May result in serious injury or death.

Disconnect power before servicing or installing.

WARNING

Reviews: