Troubleshooting
*
www.lutron.com
Load does
not respond
to Wireless
Transmitter(s)
• Ensure breaker to the PowPak
®
Relay Module
is on.
• Ensure the load has been properly wired to the
PowPak
®
Relay Module.
• Ensure Wireless Transmitter is properly
associated to PowPak
®
Relay Module.
• Ensure Wireless Transmitter’s battery is installed
correctly.
Wireless
Transmitter(s)
cannot be
associated
to PowPak
®
Relay Module
• The maximum number of Wireless Transmitters
have been associated to the PowPak
®
Relay
Module. To remove a previously set up Wireless
Transmitter, tap the button used for association
on the Wireless Transmitter three times, on the
third tap hold for three seconds and then tap
three more times.
Unaffected Mode
Unaffected Mode allows a system with an Occupancy Sensor
associated to multiple Relay Modules to be set up such that only
selected loads turn on automatically. Other loads will require a
manual turn-on with a Pico
R
Remote Control. All loads will turn off
automatically when the room is vacated.
A
On a Relay Module, press and hold both the Relay Toggle and
Advanced Operations (“ADV”) buttons for 6 seconds until the
LED begins flashing quickly.
B
On the associated Occupancy Sensor, press and hold the
“Test” button* for 6 seconds until the lens flashes.
C
Unaffected mode will be exited automatically. This Relay
Module will now be unaffected by occupancy commands.
Repeat procedure for any additional devices.
* If no “Test” button, hold “Lights On” button.
Note:
The CCO cannot be made unaffected.
Reset Factory Defaults
Note:
In some instances it may be necessary to reset the
PowPak
®
Relay Module back to factory default settings.
A
Triple-tap the “CNTRL” button on the Relay Module and hold
until the LED begins to flash slowly.
B
Within 3 seconds of flashing, release and triple-tap the button
again and the LED will flash rapidly indicating that the unit has
been reset to factory defaults.
Note:
Any associations or programming previously set up with
the unit will be lost and will need to be re-programmed.
Test
Link
Test
Link
Cal.
CCO Information
•
Some PowPak
®
Relay Modules include a dry contact closure
output that provides occupancy status to 3rd-party equipment
such as building management systems, HVAC, and VAV
controllers.
•
CCO provides both normally open (NO) and normally closed (NC)
maintained-type outputs.
•
CCO rated to switch resistive loads at
voltages up to 24 V only. To properly
control inductive load types such as
relays, solenoids, or motors, refer to
Application Note #434.
Switching
Voltage
0-24 V
-
0-24 V
~
Resistive
Load
1.0 A
0.5 A
R
Test
Link
Cal.
Part of the Energi TriPak
®
Family
PowPak
®
| Installation
Relay Module
English
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
041504
Rev. A
09/2015
Need Help? www.lutron.com or call the Lutron Technical Support Center, at 1.800.523.9466
For each system ensure you have:
At least one PowPak
®
Relay Module.
At least one Wireless Transmitter.
Required Components
Start Here
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For
warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase.
This warranty does not cover the cost of installtion, removal or reinstallation, or damage resulting from misuse, abuse, or damage from
improper wiring or installation. This warranty does not cover incidental or consequential damages.
LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE
MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE
PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow
the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above
limitations may not apply to you.
Lutron, Energi TriPak, Pico, PowPak and Softswitch are registered trademarks and Radio Powr Savr and Vive are trademarks of Lutron
Electronics Co., Inc. ©2012-2015 Lutron Electronics Co., Inc.
1
When installing a PowPak
R
Relay Module,
use the supplied conduit nut and wire the module
as shown.
Install PowPak
R
Relay Module
Associate Wireless Transmitters to PowPak
R
20 A Relay Module
*
A
Hold the Relay Toggle
button on the PowPak
®
Relay Module for 6 seconds
to enter association mode.
Before beginning this step, make sure that there are no other PowPak
®
modules being set up within the same building. It is possible that Wireless Transmitters
from other systems can be incorrectly associated to this system.
2
3
Permanently Install
Wireless Transmitters
Note:
Please consult individual component
installation guides for information.
RMJS-16R-DV-B | URMJS-16R-DVB
With Softswitch
®
RMJS-16RCCO1DV-B | URMJS-16RCCO1DVB
With Softswitch
®
and Occupancy-Status CCO
120 / 277 V
~
50 / 60 Hz 16 A
1/2 HP at 120 V
~
1
1
⁄
2
HP at 277 V
~
UL 2043 Plenum Rated
RMJS-5R-DV-B
RMJS-5RCCO1-DV-B
With Occupancy-Status CCO
120 / 277 V
~
50 / 60 Hz 5 A
1/6 HP at 120 V
~
1/3 HP at 277 V
~
UL 2043 Plenum Rated
Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
WARNING
All Wireless Transmitters must be installed within
30 ft (9 m) of the PowPak
®
Relay Module.
Radio Powr Savr
TM
Occupancy
Sensor
30 ft (9 m)
Maximum
40 ft (12 m)
30 ft (9 m)
PowPak
®
Relay Module
Install in center of room to
maximize RF coverage.
Pico
®
Remote
Control
FCC / IC Information:
This device complies with part 15 of the FCC Rules and Industry Canada licence-exempt
RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause undesired
operation.
Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s
authority to operate this equipment.
NOTE:
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Radio Powr Savr
TM
Occupancy
Sensor (10 maximum)
PowPak
®
Relay Module
Load
Status
LED
Relay Toggle
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
(Occupancy-Status CCO Option Shown)
Relay Module
without
occupancy-status
CCO also
available.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakrelay
120/277 V
~
50/60 Hz
Conduit Nut
White
(Neutral)
Black
(Line/Hot)
Red
(Switched
Line/Hot)
Note:
When wiring a CCO model
to 3rd-party
systems, use 20 AWG to 16 AWG (0.5 mm
2
to
1.5 mm
2
) solid or stranded wire.
To 3rd Party Equipment
To Load
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
NC
(Normally Closed)
CCO operation affected only by
associated occupancy or vacancy sensors.
Room Occupied:
NO = Close NC = Open
Room Unoccupied:
NO = Open NC = Close
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
B
Hold the indicated button on a Wireless Transmitter for
6 seconds to associate the device.*
Repeat for any additional Wireless Transmitters.
C
Hold the Relay Toggle button on the PowPak
®
Relay Module for 6 seconds to save association(s).
* If no
g
button, hold “Lights Off” button.
Note:
The load will flash once after each
step to confirm successful completion.
Test
Link
Daylight Sensor setup
*
Calibration
A
Turn lights in room on using the Relay
Toggle button on the PowPak
®
Relay
Module or an associated Pico
®
.
B
Press & hold “Cal.” on the associated
Daylight Sensor for 6 seconds.
C
Exit room for 5 minutes to allow
calibration to be completed.
Note:
When calibration has completed, all
lights will flash and the system will begin
daylighting.
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
(using multiple Relay Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight Sensor
(LRF2-DCRB) installation instructions.
Use the Relay Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
Tuning (Optional)
4
Radio Powr Savr
TM
Daylight Sensor
(1 maximum)
Pico
®
Remote Control
(10 maximum)
Note for Replacement:
RMxS and URMxS - the "S" model can replace the non-"S" model
*
For set-up, programming, and troubleshooting with a Vive
TM
system, please refer to the installation instructions included
with the Vive
TM
hub or at www.lutron.com
Important Notes:
Please read before installing.
•
For installation by a qualified electrician in accordance with all local and
national electrical codes.
•
Note:
Use copper conductors only.
•
Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
•
If moisture or condensation is evident, allow the product to dry completely
before
installation.
•
Operate between 32 °F (0 °C) and 131 °F (55 °C).
•
0% to 90% humidity, non-condensing.
•
For indoor use only.
+