18CE
P. 1 / 2
EM-1837 Rev.4
INSTRUCTION MANUAL
MODEL
18CE
CT CONVERTER
COMPONENT IDENTIFICATION
■
FRONT PANEL CONFIGURATION
INSTALLATION
Use Standard Rack (model: 18BX
❑
).
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the
connection diagram label behind the front cover.
Refer to the "FRONT PANEL CONFIUGRATION" for termi-
nal assignments.
Body
Specification Label
Front Cover
(Connection diagram
behind)
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■
PACKAGE INCLUDES:
Signal conditioner ................................................... (1)
■
MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.
POINTS OF CAUTION
■
POWER INPUT RATINGS
• Power input ratings are specified by the model number
suffix code. Check the power input voltage for the unit on the
specification label.
24V DC
±
10%, approx. 35mA
■
GENERAL
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■
ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55
°
C (23
to 131
°
F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■
WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■
AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
Span Adj.
Zero Adj.
5
8
7
6
1
2
4
3
+
–
OUTPUT 2
5
6
CONNECTOR
POWER
OUTPUT 1
OUTPUT 2
1
2
LOAD
SOURCE
k
l
CT
L
K