background image

48V

P. 1 / 4

EM-9311  Rev.5

BEFORE USE ....

Thank you for choosing M-System.  Before use, check the 
contents of package you received as outlined below.
If you have any problems or questions on the product, please 
contact M-System’s Sales Office or representatives.

PACKAGE INCLUDES:

  Bargraph indicator ...................................................... (1)

MODEL NO.

Check that model No. described on the specification label is 
exactly what you ordered.

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation and connection.

POINTS OF CAUTION

POWER INPUT RATINGS

• Operational range & power consumption: Check the power 

rating for the unit on the specification label.
AC Ratings

  Rating 85 – 132V AC: 85 – 132V, 47 – 63 Hz
  Rating 170 – 264V AC: 170 – 264V, 47 – 63 Hz
  Approx. 3.5VA (48V-1) or 5.5VA (48V-2)

DC Rating

  Rating 24V DC: 24V ±15%, 
  approx. 2W (48V-1) or 4W (48V-2)

INSTALLATION

• A bezel is provided in the pocket inside the package.
Push the bezel in behind the front side of the unit as illus

-

trated below.

• When installing the meter into a panel, first remove the 

nameplates at the top and bottom of the front panel.  Turn the 
screws behind these nameplates clockwise until the retaining 
clips come up and are fixed.
Turning the screws counterclockwise loosen the retaining clips.

• The acrylic front cover and scaleplate can be removed when 

you remove the nameplates.

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing and ventilate it.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not apply physical impact to the unit.

• Environmental temperature must be within 0 to 50°C (32 to 
122°F) with relative humidity within 40 to 80% RH in order 

to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with cables, 

etc.  With the vertical mounting, leave at least 5 cm (2 in.) both 

at the top and bottom of the unit; with the horizontal mount

-

ing, leave at least 2.5 cm (1 in.) at the both sides of the unit.

WIRING

• Do not install cables (power supply, input and output) close 

to noise sources (relay drive cable, high frequency line, etc.).

• Do not bind these cables together with those in which noises 

are present.  Do not install them in the same duct.

AND ....

• The unit is designed to function as soon as power is supplied, 
however, a warm up for 10 minutes is required for satisfying 

complete performance described in the data sheet.

BARGRAPH INDICATOR

MODEL

48V

INSTRUCTION  MANUAL

Bezel

Nameplate

Retaining Clip

Reviews: