background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-5656  Rev.21  P. 1 / 6

INSTRUCTION MANUAL

PC RECORDER

(thermocouple or DC input, 16 points)

MODEL

R1M-GH

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

This product is for use in general industrial environments, 
therefore may not be suitable for applications which require 
higher level of safety (e.g. safety or accident prevention sys-
tems) or of reliability (e.g. vehicle control or combustion con-
trol systems).

For safety, installation and maintenance of this product 
must be conducted by qualified personnel.

 

PACKAGE INCLUDES:

PC Recorder (body + CJC sensor) ......................................(1)
Cable (9-pin D-sub cable, straight type) ............................(1)
CD (software and users manual) ........................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.  Read also the Users Manual 
for the software included in the CD for maximum use of the 
PC Recorder.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and  

Installation Category II (transient voltage 2500V).  Re-
inforced insulation (input or RS-232-C/RS-485 to power: 
300V) and basic insulation (input to RS-232-C/RS-485: 
300V) are maintained.  Prior to installation, check that 
the insulation class of this unit satisfies the system re-
quirements.

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• Insert noise filters.  Okaya Electric Industries Model 

SUP-E1H or equivalent for the power source connected to 
the unit, and TDK Model ZCAT 3035-1330 or equivalent 
for the RS-232-C cable are recommended.

• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
    24V DC rating: 24V ±10%, approx. 7W

 

GENERAL PRECAUTIONS

• Before you remove the module, turn off the power supply 

and input signal for safety.

 

PC RECORDER SOFTWARE

• Use the latest version of PC Recorder Software included 

in the product package.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the air, 

install the module inside proper housing with sufficient 
ventilation.

• Do not install the module where it is subjected to continu-

ous vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +60°C     

(23 to 140°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tightly.
• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The module is designed to function as soon as power is 

supplied, however, a warm up for 10 minutes is required 
for satisfying complete performance described in the data 
sheet.

Summary of Contents for R1M-GH

Page 1: ...r equivalent for the RS 232 C cable are recommended The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this ...

Page 2: ... C port COM1 through COM5 supported LAN card LAN card by Windows 1 External e g SCSI devices may impair appropriate performance MSR128LS MSR128LV MSR128LS MSR128LV PC IBM PC AT or compatible Operating system Windows XP SP1 or SP2 For High Speed Mode Group 0 50 msec storing cycle use Windows XP SP1 SP2 Note Proper software functions may not be ensured under certain conditions CPU Pentium II 233 MHz...

Page 3: ...ok at the rear side on the DIN rail and push in the lower Push back the DIN rail adaptor WALL MOUNTING Set the body so that its DIN rail adaptor is at the bottom Pull down the DIN rail adaptor Refer to EXTERNAL DIMENSIONS TERMINAL CONNECTIONS Connect the unit as in the diagram below Attach the CJC sensor together with input wiring to the input screw terminals The sensor is calibrated for each part...

Page 4: ...ot designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Note 2 Be sure to maintain the same potential at all the common negative terminals for DC input 9 8 7 6 5 4 3 2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 29 30 31 32 33 35 34 36 TRIGGER INPUT T C INPUT DC INPUT INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT ...

Page 5: ...re size 0 75 to 1 25 mm2 AWG19 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6 max 24 3 12 max 3 2 13 dia mm inch EURO TYPE CONNECTOR TERMINAL Power input Modbus Applicable wire size 0 2 to 2 5 mm2 AWG24 to 12 Stripped length 7 mm COMMUNICATION CABLE CONNECTIONS R1M T1 T2 T3 T4 R1M T1 T2 T3 T4 T1 T2 T3 T4 R1M CONNECTOR RS 232 C RS 485 1 1 1 Internal terminating...

Page 6: ... 16 ON Voltage input above 0 8V SW301 SW308 ch 1 ch 8 SW401 SW408 ch 9 ch 16 Set to position 3 Attenuation ON SW311 ch 1 ch 8 SW411 ch 9 ch 16 ON Factory default setting CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input Check supply voltage 3 Input Check that the input is within 0 100 of full scale 4 DIP SW setting Check tha...

Reviews: