INSTRUCTION MANUAL

ONE-SHOT PULSE OUTPUT MODULE

(triac output, 16 points)

MODEL

R3-PD16B

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

One-shot pulse output module ...........................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

HOT INSERTION/REMOVAL OF MODULES

• 

Removing or replacing modules does not affect other mod-
ules on the same backplane.  It is possible to replace them 
without removing the power supply.  However, replacing 
multiple modules at once may greatly change line voltage 
levels.  We recommend that you replace them one by one.

• 

In order to prevent the erroneous output at the hot inser-
tion/removal when ON/OFF control output is in one-shot 
output mode, the first data received after the hot inser-
tion/removal is used as initial value.  For the combina-
tion with non-cyclic Modbus communication modules (R3-
NM1, R3-NE1, etc.) write the output data immediately 
before the hot insertion/removal.

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -10 to +55°C 
(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

AND ....

• 

The triacs for output may be damaged, if output load is 
shorted when using.  Install a fuse for each output ter-
minals.

INSTALLATION

Use the Installation Base (model: R3-BSx).

Summary of Contents for R3-PD16B

Page 1: ...ine voltage levels We recommend that you replace them one by one In order to prevent the erroneous output at the hot inser tion removal when ON OFF control output is in one shot output mode the first data received after the hot inser tion removal is used as initial value For the combina tion with non cyclic Modbus communication modules R3 NM1 R3 NE1 etc write the output data immediately before the...

Page 2: ...W Factory setting Output Hold Function SW3 1 Effective only in continuance output mode SW OUTPUT HOLD FUNCTION HOLD OFF SW3 1 OFF ON Output Mode Setting SW3 2 3 3 SW OUTPUT MODE SW3 2 SW3 3 OFF OFF One Shot Output Mode ON OFF ON OFF Control Output Mode OFF ON Continuance Output Mode Output Data Length SW3 4 Effective only in ON OFF control output mode SW OUTPUT DATA LENGTH 16 bit 8 bit SW3 4 OFF O...

Page 3: ...ugh 8 correspond to each binary digit 1st through 8th digit For every setting ON time will be as indicated below SW OUTPUT ON TIME sec 0 1 0 2 0 3 0 4 0 5 25 5 25 6 SW1 1 OFF ON OFF ON OFF OFF ON SW1 2 OFF OFF ON ON OFF ON ON SW1 3 OFF OFF OFF OFF ON ON ON SW1 4 OFF OFF OFF OFF OFF ON ON SW1 5 OFF OFF OFF OFF OFF ON ON SW1 6 OFF OFF OFF OFF OFF ON ON SW1 7 OFF OFF OFF OFF OFF ON ON SW1 8 OFF OFF O...

Page 4: ... 3 Ch1 One Shot Output Completion 4 5 7 8 9 2 One Shot Output ON OFF CONTROL OUTPUT MODE Data Length 16 bits Example that ON OFF control outputs sequentially Ch1 to Ch2 to Ch2 is shown below Example of when I O Mode is in Output Operation SW2 7 OFF and ON OFF Control channel is Not Swapped SW2 8 OFF 1 Output data Do 1 changes from 0 to 1 2 After Do 1 s rising edge Ch1 s one shot output turns ON fo...

Page 5: ...mpletion Di 2 Ch2 output completed status changes from 0 to 1 4 When Do 1 changes from 1 to 0 Di 2 changes from 1 to 0 5 After Do 1 s sinking edge Ch1 s one shot output turns ON for a fixed period of time SW1 s time set 6 After one shot output completion Di 1 Ch1 output completed status changes from 0 to 1 Do 1 Ch2 Ch1 1 4 3 Ch2 One Shot Output Completion 6 Ch1 One Shot Output Completion Note Duri...

Page 6: ...ompletion Status 0 Ch5 Output Completion Reset Do 6 1 Ch6 Output Di 6 Ch6 Output Completion Status 0 Ch6 Output Completion Reset Do 7 1 Ch7 Output Di 7 Ch7 Output Completion Status 0 Ch7 Output Completion Reset Do 8 1 Ch8 Output Di 8 Ch8 Output Completion Status 0 Ch8 Output Completion Reset Do 9 1 Ch9 Output Di 9 Ch9 Output Completion Status 0 Ch9 Output Completion Reset Do 10 1 Ch10 Output Di 10...

Page 7: ...7 Output Completion Status 0 1 Ch8 Output Di 8 Ch8 Output Completion Status 1 1 Output Data Reset Do 9 Do 10 0 0 Not Operating 1 0 Ch9 Output Di 9 Ch9 Output Completion Status 0 1 Ch10 Output Di 10 Ch10 Output Completion Status 1 1 Output Data Reset Do 11 Do 12 0 0 Not Operating 1 0 Ch11 Output Di 11 Ch11 Output Completion Status 0 1 Ch12 Output Di 12 Ch12 Output Completion Status 1 1 Output Data ...

Page 8: ...F control output is swapped with its pair when SW2 8 is ON The following is an example of Do1 Do WRITE ONE SHOT OUTPUT RESET Di OUTPUT COMPLETION STATUS Do 1 0 Ch2 Output Di 2 Ch2 Output Completion Status 1 Ch1 Output Di 1 Ch1 Output Completion Status CONTINUANCE OUTPUT MODE Do 1 through 16 are assigned to and Ch1 through 16 When data Do is 1 output is ON and when it is 0 output is OFF The operati...

Page 9: ... 8510 E mail info m system co jp EM 8390 Rev 2 P 9 10 DATA ASSIGNMENT Do 0 15 Do 1 Do 2 Do 3 Do 16 Note For 8 bit length ON OFF control mode Do 9 through Do 16 are unavailable Di 0 15 Di 1 Di 2 Di 3 Di 16 Note Di data is not practical discrete input data It is output completion status internal data ...

Page 10: ...CREEN TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL unit mm inch Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Applicable wire size 0 3 0 5 mm2 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max FUNCTIONS OUTPUT ...

Reviews: