background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-8940  Rev.1  P. 1 / 4

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC voltage output module ..................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

HOT SWAPPABLE MODULES

• Replacing the module does not affect other modules on 

the same base.  Thus, the module can be replaced while 
the power is ON.  However, replacing multiple modules 
at once may greatly change live voltage levels.  We highly 
recommend to replace them one by one.

 

GENERAL PRECAUTIONS

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx). 

DC VOLTAGE OUTPUT MODULE

(4 points, isolated, tension clamp terminal block)

MODEL

R3S-YV4

Summary of Contents for R3S-YV4

Page 1: ...e highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous...

Page 2: ...put Range SW1 SW2 OUTPUT 1 SW1 OUTPUT 2 SW1 RANGE OUTPUT 3 SW2 OUTPUT 4 SW2 1 2 3 4 5 6 7 8 OFF OFF OFF OFF OFF OFF OFF OFF 10 10V DC ON OFF OFF OFF ON OFF OFF OFF 5 5V DC OFF ON OFF OFF OFF ON OFF OFF 1 1V DC ON ON OFF OFF ON ON OFF OFF 0 10V DC OFF OFF ON OFF OFF OFF ON OFF 0 5V DC ON OFF ON OFF ON OFF ON OFF 1 5V DC OFF ON ON OFF OFF ON ON OFF 0 1V DC Output Hold SW3 1 SW OUTPUT HOLD HOLD OFF S...

Page 3: ...NTERNAL BUS B 1 For dual redundant communication 2 To use shield line connect it to SLD terminal and ground the terminal 20 Note Do not connect wide span and narrow span simultaneously within the same channel Do not use void terminals 1 INTERNAL POWER WIDE SPAN NARROW SPAN OUTPUT 1 3 2 5 WIDE SPAN NARROW SPAN OUTPUT 2 7 6 11 WIDE SPAN NARROW SPAN OUTPUT 3 13 12 15 WIDE SPAN NARROW SPAN OUTPUT 4 17...

Page 4: ...Be sure wire insulation is not inside the terminal Screw Driver Power wire OUTPUT PIN ASSIGNMENT PIN No FUNCTION 1 VH1 2 COM1 3 VL1 4 SLD 5 VH2 6 COM2 7 VL2 8 SLD 9 NC 10 NC 11 VH3 12 COM3 13 VL3 14 SLD 15 VH4 16 COM4 17 VL4 18 SLD 19 SLD 20 SLD FUNCTIONS OUTPUT HOLD or OUTPUT OFF In normal conditions the module outputs the signal from the preferred bus A When an error is detected the output is sw...

Reviews: