INSTRUCTION MANUAL

RTD INPUT MODULE, 4 points

(CC-Link V.1.10)

MODEL

R7C-RS4

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

RTD input module ...............................................................(1)
Terminating resistor (110 Ω, 0.5 W) ...................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.  Choose a surge protector with its 
maximum surge voltage 40V or less between lines.  Rec-
ommended M-System model: MDP-D24.

 

POWER INPUT RATING & OPERATIONAL RANG

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    24V DC rating: 24V ±10%, approx. 90mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Summary of Contents for R7C-RS4

Page 1: ...orm ity Install lightning surge protectors for those wires connect ed to remote locations Choose a surge protector with its maximum surge voltage 40V or less between lines Rec ommended M System model...

Page 2: ...selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF...

Page 3: ...due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address se...

Page 4: ...5 5 22 DIN RAIL 35 mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for CC Link POWER 18 M3 SCREW TERMINALS for INPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2 5 1 0V 24V DC FG SLD DG...

Page 5: ...e Master Unit can be located other than at the extreme ends of communication line DATA ALLOCATION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused R...

Page 6: ...t range error Input 2 Burnout input range error Unused Input 3 Burnout input range error Input 0 ADC error Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Burnout input range error 15 115...

Page 7: ...ng the R7C Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 9: ...Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from th...

Page 10: ...m is not effective Points of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of...

Reviews: