Summary of Contents for FDMA-PM

Page 1: ......

Page 2: ...mbly 32 6 Statement of installations 29 7 Installation frames 65 8 Thin shaft wall 80 9 Installation in Fire resistant foam 85 10 Installation outside of wall construction EIS60 87 11 Suspension syste...

Page 3: ...mechanism is started when the thermoelectrical starting mechanism BAT is activated when a reset button on BAT is pushed or when a power supply of the actuating mechanism is stopped The damper is seale...

Page 4: ...rbitrary position Dampers are suitable for systems without abrasive chemical and adhesive particles Dampers are designed for macroclimatic areas with mild climate according to EN 60 721 3 3 Temperatur...

Page 5: ...mit switch Design 01 with mechanical control can be complemented with a terminal switches signaling of the damper blade position CLOSED and OPEN Limit switches are connected via damper casing cables a...

Page 6: ...is moving connect wire 1 4 AC 230V 5A IP 67 25 C 120 C 1 Damper 2 Mounting plate 3 Sealing cover 4 Seal plates 5 Mounting plate cover 6 Thermal fuse 7 Mechanics 8 Actuator 9 Temperature sensor 10 Sen...

Page 7: ...from the position OPEN to the position CLOSED takes maximum 20 sec In case that the power supply is restored again the blade can be in any position the actuating mechanism starts to re displace the da...

Page 8: ...s 20 s Ambient temperature normal duty safety duty non operating temperature 30 C 55 C The safe position will be attained up to max 75 C 40 C 55 C Connecting motor auxiliary switch cable 1 m 2 x 0 75...

Page 9: ...complemented with smoke detector ORS 142 K The voltage can be AC 230 V or 24 V DC Design with voltage AC 230 V is equpped with Communication and supply device BKN 230 24 MOD and with actuating mechan...

Page 10: ...10 2 3 4 5 6 1 relay contact relay contact RS Bus communication 1 2 3 4 5 6 7 1 2 S2 S1 S3 S5 S4 S6 2 3 4 5 6 1 BAT Tf Tf LED 1 2 S2 S1 S3 S5 S4 S6 24 V DC 2 3 4 5 6 1 BAT Tf Tf LED...

Page 11: ...hand and on the other hand it transmits the signal informing about the flap valve position OPERATION and FAILURE through 2 conductor wiring to the central Control command SWITCHED ON SWITCHED OFF from...

Page 12: ...h spring return Protection Class II Degree of protection IP 40 Ambient temperature Non operating temperature 20 C 50 C 40 C 80 C Connection net motor terminal board cable 0 9 m with EURO plug type 26...

Page 13: ...0 24 MOD can be installed separately without a connection to a master control system in which case the connection bridge between the terminals 1 and 4 must be installed For more information see the Be...

Page 14: ...nformation in Belimo catalogue Design with the communication and supply device BKN 230 24LON and actuating mechanisms of fire dampers BF 24TL TN ST for cooperation with control units based on technolo...

Page 15: ...MP cable 1 m 4 x 0 75 mm halogen free Nominal voltage AC 230 V 50 60Hz Power consumption 11 W including actuator mechanism Dimensioning 13 VA including actuator mechanism Protection Class II Degree of...

Page 16: ...50 C 40 C 80 C Connection net actuator BF Top net LonWorks starting mechanism optional Top Line PC Tool via ZIP RS232 cable 1m with Euro plug 4 pole connector screw terminal 2 pole screw terminal 2 p...

Page 17: ...tacts are available Contacts showing operating and failure position of the damper are active when the damper is in the given position Function check can be done by pressing and holding the button RESE...

Page 18: ...tor wiring and issues control commands Proper damper operation is indicated by two light LED diodes Control ON position OPERATION Control OFF position FAILURE If the fire damper do not reach the given...

Page 19: ...19 Nominal voltage AC 24 V 50 60Hz Power consumption 3 5 W Dimensioning 5 5 VA Protection Class III Degree of protection IP 30 Ambient temperature 0 50 C Connection terminal 2 x 1 5 mm...

Page 20: ...le covering 5 Sensor sticker 6 Hole for camera 35 A 10 B 10 275 123 110 35 80 20 65 A B 30 30 375 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical...

Page 21: ...Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical starting mechanism 6 Hole for camera 1 Damper casing 2 Mechanics 3 Damper blade 4 Inspection hole covering 5 Sensor...

Page 22: ...0 0376 BFL M1 33 278 23 0 26 0 0 1451 BFN M2 73 12 0 13 5 0 0411 BFL M1 53 298 23 5 26 5 0 1541 BFN M3 80 5 12 5 14 0 0 0438 BFL M1 78 323 25 0 28 0 0 1654 BFN M3 100 5 13 0 15 0 0 0508 BFL M1 13 11...

Page 23: ...07 BFN M2 73 17 5 19 5 0 0999 BFL M1 203 21 5 24 5 0 1436 BFN M2 80 5 18 0 20 0 0 1063 BFL M1 223 22 5 25 5 0 1639 BFN M2 100 5 19 5 21 0 0 1233 BFL M1 238 23 0 26 0 0 1697 BFN M2 123 20 5 22 5 0 1424...

Page 24: ...7 0 40 0 0 3859 BF M3 223 33 0 36 0 0 3237 BF M2 13 16 5 18 5 0 0615 BFL M1 238 34 0 37 0 0 3418 BF M2 23 17 0 18 5 0 0722 BFL M1 3 248 34 5 37 5 0 3539 BF M2 36 17 5 19 5 0 0856 BFL M1 28 273 36 5 39...

Page 25: ...25 5 28 5 0 1987 BFN M2 23 25 0 26 5 0 1181 BFL M1 123 27 5 30 5 0 2295 BFN M2 36 26 5 28 0 0 1400 BFL M2 148 29 5 32 5 0 2637 BFN M2 48 28 0 29 5 0 1619 BFL M2 173 31 5 34 5 0 2980 BFN M2 63 29 5 31...

Page 26: ...0 0 8044 BF M4 198 46 0 49 0 0 5214 BF M3 28 273 65 5 68 5 0 8731 BF M4 203 46 5 49 5 0 5321 BF M3 33 278 66 0 69 0 0 8869 BF M4 223 49 0 52 0 0 5751 BF M3 53 298 68 5 71 5 0 9419 BF M4 238 50 0 53 0...

Page 27: ...0 3461 BF M4 34 5 276 5 35 6 38 6 0 4464 BF M4 84 5 326 5 53 0 56 0 0 5727 BF M4 134 5 376 5 70 9 73 9 0 7147 BF M4 16 5 6 7 8 3 0 0137 BFL M1 26 5 7 7 9 3 0 0182 BFL M1 39 0 8 2 9 8 0 0248 BFL M1 51...

Page 28: ...Fig 34 35 Dimensions of damper connecting flanges are in accordance with EN 12 220 In case of damper installation into SPIRO duct round dampers are supplied without the flanges so as it is possible to...

Page 29: ...ust be situated at least 350 mm from the control parts of the damper Inspection hole must be accessible Damper blade has to be inside of construction labelled with BUILD IN EDGE on the damper body aft...

Page 30: ...opening dimensions The recommended dimension of the installation opening is from 25 mm to 50 mm on the both sides it means from A 50 to A 100 or B 50 to B 100 Built in edge Built in edge 375 260 375 2...

Page 31: ...struction with fire classification EI120 or EI 90 The fire damper can also be integrated outside the wall construction Duct and the damper part between the wall construction and the damper blade label...

Page 32: ...90 60 100 Installation next to wall mortar or gypsum and mineral wool EIS 90 55 100 Installation next to wall Installation frame R1 R2 R5 and mineral wool EIS 90 56 57 100 Movable ceiling Installatio...

Page 33: ...33 POSITION 1 Fire damper FDMA PM 2 Solid wall construction 3 Mortar or gypsum 4 Duct 50 100 40 100 Around the perimeter...

Page 34: ...pers with flanges Gap between damper and construction is filled by mortar or gypsum Fire damper FDMA PM C distance between dampers 60 mm Fire damper FDMA PM K distance between dampers 70 mm Flange to...

Page 35: ...100 D 20 D 20 D 20 D 100 100 100 20 100 100 50 Gap between damper and construction is filled by mortar or gypsum and mineral wool Wool is fixed to damper body and construction by fire protection masti...

Page 36: ...n must be filled by glue PROMAT K84 Wool is fixed to installation frame and construction by fire protection mastic Installation is valid for ceiling construction Dimensions Number X1 Number Y Number Z...

Page 37: ...aded rods or steel bracket 3 100 100 50 5 0 10 20 10 10 20 Dimensions Number X Number Y D 400 4 8 400 D 800 8 16 800 D 1000 12 24 It is possible to use corresponding number of holes and screws Fitting...

Page 38: ...in thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Duct Used materials example 3 Promapyr Rockwool Steprock HD 4 Promastop P K 5 Promatect H Fire resistant insulation and...

Page 39: ...39 100 100 100 100 POSITION 1 Fire damper FDMA PM 2 Installation frame 3 Solid wall construction 100 100 Installation details see chapter 7...

Page 40: ...4 Hilti CFS CT POSITION 1 Fire damper FDMA PM 2 Solid wall construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Duct Fire resistant insulation and fire resistant board can be repla...

Page 41: ...is possible to use corresponding number of holes and screws Fire damper FDMA PM C installation opening dimensions a x b 2x A 85 mm 20 mm x B 85 mm or a x b A 85 mm x 2x B 85 mm 20 mm Fire damper FDMA...

Page 42: ...ruct is not limited and according to EN 15882 2 must use the required number of hinges according to EN 13366 1 2014 Installation of profile U25x40x25 see Fig 73 Screws has to be fixed in wall ceiling...

Page 43: ...43 POSITION 1 Fire damper FDMA PM 2 Installation frame 3 Solid wall construction 4 Cement lime plate 5 Duct 100 100 50 50 Around the perimeter Installation details see chapter 7...

Page 44: ...44 POSITION 1 Fire damper FDMA PM 2 Solid ceiling construction 3 Mortar or gypsum 4 Duct 150 50 150 40 Around the perimeter min 110 Concrete min 125 Aerated concrete...

Page 45: ...s D 80 mm D 160 mm for dampers with flanges Gap between damper and construction is filled by mortar or gypsum Fire damper FDMA PM C distance between dampers 60 mm Fire damper FDMA PM K distance betwee...

Page 46: ...yr Rockwool Steprock HD 4 Promastop P K 5 Promatect H 3 3 50 50 150 40 50 150 Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper inst...

Page 47: ...47 150 150 150 150 150 150 POSITION 1 Fire damper FDMA PM 2 Installation frame 3 Solid ceiling construction Installation details see chapter 7 min 110 Concrete min 125 Aerated concrete...

Page 48: ...ard 4 Fire stop coating thickness 1 mm 5 Duct 150 150 Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent...

Page 49: ...g construction 3 Stuffing box mineral stone wool min density 140 kg m 4 Flange connection Fire damper FDMA PM C installation opening dimensions a x b 2x A 85 mm 20 mm x B 85 mm or a x b A 85 mm x 2x B...

Page 50: ...mm e g 3x60 mm 6 Stone wool with one side stitched wire fencing min density 105 kg m thickness 60 mm 7 Profil U25x40x25 8 Duct 3 3 Installation details of wool layers see chapter 8 Around the perimet...

Page 51: ...5 Rebar 6 Duct 100 100 150 150 POSITION 1 Fire damper FDMA PM 2 Solid ceiling construction 3 Concrete B20 4 Rebar 5 Duct 750 30 100 50 30 100 50 750 100 100 150 150 Around the perimeter min 110 Concr...

Page 52: ...1 Fire damper FDMA PM 2 Installation frame 3 Solid ceiling construction 4 Cement lime plate 5 Duct 150 50 50 150 Around the perimeter min 110 Concrete min 125 Aerated concrete Installation details se...

Page 53: ...50 40 100 Around the perimeter 100 Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corresponding length Distance between screws 200 mm Installation ope...

Page 54: ...or a x b D 97 mm x D 97 mm 20 mm Gap between damper and construction is filled by mortar or gypsum Fire damper FDMA PM C distance between dampers 60 mm Fire damper FDMA PM K distance between dampers...

Page 55: ...mper body and construction by fire protection mastic Mineral wool thickness construction thickness 20 mm or 50 mm Installation is valid for ceiling construction Installation opening has to be reinforc...

Page 56: ...ol is fixed to installation frame and construction by fire protection mastic Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corresponding length Dista...

Page 57: ...SITION 1 Fire damper FDMA PM with installation frame R5 2 Fitting with threaded rods 10 20 10 Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with correspon...

Page 58: ...resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties Screw min 4x50 Around the perimeter 300 25 25 300 300 25 25 300 Scr...

Page 59: ...istance between screws 200 mm Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corresponding length Distance between screws 200 mm Installation opening...

Page 60: ...an be replaced by another approved fire sealing system for damper installation with equivalent material properties B 60 to 800 max 2050 A 60 to 800 max 1650 D 60 to 800 max 2050 D 60 to 800 max 1650 I...

Page 61: ...er body and frame and construction must be filled by glue PROMAT K84 Fire damper FDMA PM C distance between dampers 104 mm Fire damper FDMA PM K distance between dampers 160 mm Flange to flange connec...

Page 62: ...iable 400 Screw min 4x50 Screw min 4x50 Installation details of wool layers see chapter 8 Around the perimeter 40 50 50 50 300 25 25 300 300 300 25 25 The screws must be firmly anchored in the profile...

Page 63: ...63 150 150 150 150 POSITION 1 Fire damper FDMA PM 2 Installation frame 3 Solid ceiling construction 4 Wall with possibility of ceiling movement Installation details see chapter 7...

Page 64: ...t profile into groove 3 Fix profile 4 Fix second layer of insulation 27 Screw 4 2x50 max 350 75 NOTICE For dampers with A 800 and damper placement outside wall construction is necessary to use reinfor...

Page 65: ...65 E1 Cement lime 100 150 100 E2 Galvanized plate 100 150 E3 Cement lime 100 E4 Cement lime 100 150 Solid ceiling construction 150 100 150 E5 Cement lime 100 E6 Cement lime 100 150 Rectangular dampers...

Page 66: ...dampers R1 Cement lime 100 150 100 R2 Cement lime 150 150 100 R3 Cement lime 100 150 100 R4 Cement lime 150 150 100 R5 Cement lime Solid ceiling construction 150 100 R6 Cement lime 100 150 R7 Cement...

Page 67: ...67...

Page 68: ...68...

Page 69: ...tion Gypsum wall construction Solid ceiling construction On the inside and outside is installation frame equipped by intumescent sealing It enlarges its capacity and air proofs the gap between damper...

Page 70: ...he gap between damper body and steel cartridge Gypsum wall construction has to be installed according manufacture requirements Installation frame cement lime plates and galvanized plate Fasteners galv...

Page 71: ...5 mm with corresponding length Distance between screws 200 mm Installation frame E3 is suitable for Gypsum wall construction Damper is on the body equipped by intumescent sealing It enlarges its capa...

Page 72: ...tallation frame equipped by intumescent sealing It enlarges its capacity and air proofs the gap between installation frame and damper body Gypsum wall construction has to be installed according manufa...

Page 73: ...and installation frame and between installation frame and wall construction Damper position Directly on the ceiling In distance from ceiling max 80 mm Installation frame cement lime plates Fasteners...

Page 74: ...on outside solid wall ceiling construction with cement lime plates On the inside is installation frame equipped by intumescent sealing It enlarges its capacity and air proofs the gap between installat...

Page 75: ...responding length Distance between screws 200 mm Installation frames R1 R2 are suitable for Solid wall construction Gypsum wall construction Solid ceiling construction On the inside and outside is ins...

Page 76: ...with corresponding length Distance between screws 200 mm Installation frame R3 R4 are suitable for Solid wall construction Gypsum wall construction Solid ceiling construction On the inside and outside...

Page 77: ...solid ceiling constructions with concrete On the inside is installation frame equipped by intumescent sealing It enlarges its capacity and air proofs the gap between installation frame and damper body...

Page 78: ...et Installation frame R6 is suitable for Installation outside solid wall ceiling construction with cement lime plates On the inside is installation frame equipped by intumescent sealing It enlarges it...

Page 79: ...er body and installation frame and between installation frame and wall construction Damper position Directly on the ceiling In distance from ceiling max 80 mm Installation frame cement lime plates Fas...

Page 80: ...200mm to the support structure The boards are mounted to tight butt joints without need of cementing The second sheathing layer is screwed to the first sheathing layer using screws Rodurit in square n...

Page 81: ...00 mm 100 250 50 250 50 50 20 20 110 50 POSITION 1 Fire damper FDMA PM S 2 Mortar or gypsum 3 Fire resistant board 4 Profile 50 UW or 50 CW 5 Screw 6 Additional fire resistant board Used materials exa...

Page 82: ...ard 5 Screw 6 Additional fire resistant board Used materials example 4 Glasroc F Ridurit tl 20 mm 5 Screw Ridurit 6 Glasroc F Ridurit tl 20 mm It is possible to use corresponding number of holes and s...

Page 83: ...00 mm 100 250 50 250 50 50 20 20 110 50 POSITION 1 Fire damper FDMA PM R 2 Mortar or gypsum 3 Fire resistant board 4 Profile 50 UW or 50 CW 5 Screw 6 Additional fire resistant board Used materials exa...

Page 84: ...istant board 5 Screw 6 Additional fire resistant board Used materials example 4 Glasroc F Ridurit tl 20 mm 5 Screw Ridurit 6 Glasroc F Ridurit tl 20 mm It is possible to use corresponding number of ho...

Page 85: ...damper FDMA PM 2 Solid wall 3 Fire resistant foam 4 Stucco plaster 5 Duct 100 50 40 100 Used materials example 3 HILTI CFS F FX EIS 60 PROMAFOAM C EIS 45 SOUDAL Soudafoam FR B1 EIS 30 DenBraven Fire r...

Page 86: ...Mineral wool type depending on the type of construction 4 Fire resistant foam 5 Stucco plaster 100 100 Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with...

Page 87: ...Isover Ultimate Protect Wired MAT 4 0 th 75 mm ALU1 25 100 3 Around the perimeter 3 Installation details of wool layers see chapter 11 80 75 Stuffing box fire protection mastic cement lime plate and i...

Page 88: ...3 Promapyr Rockwool Steprock HD 4 Promastop P K 5 Isover Ultimate Protect SLAB 4 0 th 80 mm ALU1 6 Isover Ultimate Protect Wired MAT 4 0 th 75 mm ALU1 Installation details of wool layers see chapter...

Page 89: ...tect SLAB 4 0 th 80 mm ALU1 6 Isover Ultimate Protect Wired MAT 4 0 th 75 mm ALU1 25 100 3 Installation details of wool layers see chapter 11 Around the perimeter 3 80 75 Stuffing box fire protection...

Page 90: ...r Rockwool Steprock HD 5 Promastop P K 6 Isover Ultimate Protect SLAB 4 0 th 80 mm ALU1 7 Isover Ultimate Protect Wired MAT 4 0 th 75 mm ALU1 25 100 3 3 3 Around the perimeter 50 50 Installation detai...

Page 91: ...e damper body is absolutely excluded Back to back air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded Threaded r...

Page 92: ...must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded Back to back air conditioning piping must be hung or supported so as all load tra...

Page 93: ...of using materials Position 1 Fire damper 2 Damping pad 3 Extension piece 4 Threaded rod 5 Mounting rail 6 Nut 7 U Washer 8 Washer 9 Screw connection 10 Mounting profile 11 Mounting bracket 12 Fire r...

Page 94: ...ly excluded Threaded rods longer than 1 5 m require fire resistant insulation If the threaded rod is located inside the duct insulation distance between threaded rod and duct is max 30 mm If the tread...

Page 95: ...construction see fig 100 Fire dampers can be suspended by using threaded rods and a mounting profiles Load the suspension system depend on weight of the fire damper Damper can be suspended from the ce...

Page 96: ...with extension piece by screws or rivets Expamples of using materials Position 1 Fire damper 2 Damping pad 3 Extension piece 4 Threaded rod 5 Mounting rail 6 Nut 7 Washer 8 Screw connection 9 Mounting...

Page 97: ...ns to the damper body is absolutely excluded Back to back air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded Th...

Page 98: ...p Pa presure loss w m s air flow speed in nominal damper section kg m air density coefficient of local pressure loss for the nominal damper section see Tab 13 1 1 a Tab 13 2 1 Determination of pressu...

Page 99: ...0 263 0 252 0 239 0 231 0 223 0 216 0 213 0 209 0 335 0 311 0 301 0 289 0 274 0 257 0 244 0 233 0 223 0 215 0 209 0 205 0 203 1 261 1 246 1 234 1 225 1 219 1 208 1 197 1 177 1 162 1 148 1 136 1 124 1...

Page 100: ...1 0 099 0 090 0 083 15 5 18 7 20 9 22 6 24 0 25 2 26 3 27 2 28 0 31 2 33 4 35 1 36 5 38 8 40 5 44 2 45 9 26 1 29 2 31 5 33 2 34 6 35 8 36 9 37 8 38 6 41 7 44 0 45 7 47 1 49 4 51 1 54 7 56 5 33 6 36 7...

Page 101: ...1 5 63 3 66 4 68 6 70 4 71 8 73 0 48 1 53 5 56 6 58 9 62 0 64 3 66 0 69 1 71 4 73 1 74 5 75 7 50 6 56 0 59 1 61 4 645 667 685 71 6 73 9 75 6 77 0 78 2 52 8 58 2 61 4 63 6 668 69 707 73 9 76 1 77 9 79...

Page 102: ...4 Mechanical components entering the interior of damper body lower sheet of mechanics lock holder 1 lock lever 2 lock spring 8 dia stopper pin mechanics pin 5 Inspection hole cover including the clip...

Page 103: ...out any aggressive vapours gases or dust Indoor temperature must be in the range from 30 C to 40 C and maximum relative humidity 95 avoid condensation on the damper body Dampers must be protected agai...

Page 104: ...ion of interior of fire damper micro camera device can be used On each fire damper is ispection hole In the case of inspection by camera take out the black rubber cap insert the camera inside the damp...

Page 105: ...from ELECTRICAL FIRE SIGNALISATION Check of blade displacement back into the OPEN position can be done after restoration of power supply e g By releasing the RESET button or restoration of supply from...

Page 106: ...TN ST BFL BFN 24 T ST and with smoke detector ORS 142 K 61 With communication and supply device BKN 230 24MP and actuating mechanism BF 24TL TN ST Top Line for connection to MP Bus 62 With communicat...

Page 107: ...s placed on the damper body Certificate WEIGHT kg Dob sk 550 267 24 Hostomice MAND K a s Czech Republic FIRE DAMPER FDMA PM DESIGN SERIAL NUMBER SIZE 1391 1391 CPR 2016 0158 14 EN 15650 2010 CLASSIFIC...

Page 108: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...