Summary of Contents for FDMR

Page 1: ......

Page 2: ...ol min density 140 kg m 4 Fire protection mastic min thickness 1 mm 50 25 4 Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT Fire resistant...

Page 3: ...LTI CFS CT 4 HILTI CFS CT 5 HILTI CFS S ACR Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material...

Page 4: ...sity 140 kg m 4 Fire protection mastic min thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Duct Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 1...

Page 5: ...5 100 100 100 Position 1 Fire damper 2 Installation frame 3 Solid wall construction 100...

Page 6: ...ckness 1 mm 5 Duct Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for dampe...

Page 7: ...to EN 1366 1 2014 must be used Used materials example 4 DN 100 DN 800 System ISOVER_ULTIMATE PROTECT th 100 mm EIS 60 DN 100 DN 315 System ISOVER_ULTIMATE PROTECT th 120 mm 2x60 mm EIS 90 DN 350 DN 80...

Page 8: ...thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Stone wool with one side stitched wire fencing min density 105 kg m thickness 180 mm e g 3x60 mm 7 Stone wool with one si...

Page 9: ...40 50 5 Promastop P K Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material propertie...

Page 10: ...ystem for damper installation with equivalent material properties 40 40 50 40 100 Used materials example 4 HILTI CFS F FX EIS 60 PROMAFOAM C EIS 45 SOUDAL Soudafoam FR B1 EIS 30 DenBraven Fire protect...

Page 11: ...s 1 mm 6 Cement lime plate min th 15 mm min density 870 kg m 7 Duct Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 5 Promatect H Fire resi...

Page 12: ...een screws 200 mm Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm Installation opening has to be r...

Page 13: ...FS CT B 1S 140 50 4 Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties...

Page 14: ...ting th 1 mm 7 Duct D 60 to 800 max 2050 Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT 110 D 60 to 800 max 1650 Fire resistant insulation and fire resistant board can be replaced by...

Page 15: ...wool type depending on the type of construction 4 Mortar or gypsum 5 Stone wool with wired mat on one side density 66 kg m 6 Duct Installation opening has to be reinforced by profile UW CW Profil is...

Page 16: ...me plate min thickness 15 mm min density 870 kg m 7 Stone wool with one side stitched wire fencing min density 105 kg m thickness 180 mm e g 3x60 mm 8 Stone wool with one side stitched wire fencing mi...

Page 17: ...istant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties 25 50 Position 1 Fire damper 2 Solid ceil...

Page 18: ...Promatect H Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties Position 1 Fire dampe...

Page 19: ...d fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties Position 1 Fire damper 2 Solid ceiling construction 3 Stuffin...

Page 20: ...20 Position 1 Fire damper 2 Installation frame 3 Solid ceiling construction min 110 Concrete min 125 Aerated concrete...

Page 21: ...t Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation wi...

Page 22: ...nt material properties Depends on the distance of the flap from the construction when the maximum distance from the construct is not limited and according to EN 15882 2 must use the required number of...

Page 23: ...density 105 kg m thickness 60 mm 6 Duct min 110 Concrete min 125 Aerated concrete 100 400 variable 40 180 240 Stuffing box fire protection mastic cement lime plate and insulation materials can be repl...

Page 24: ...24 Position 1 Fire damper 2 Solid ceiling construction 3 Concrete B20 4 Rebar 5 Duct Around the perimeter min 110 Concrete min 125 Aerated concrete 30 100 50 100 100 750...

Page 25: ...20 D 300 50 50 130 130 110 400 Position 1 Damper casing 2 Mechanics 3 Damper blade 4 Inspection hole covering 5 Sensor sticker 6 Hole for camera 300 50 120 D 110 400 180 50 300 50 120 50 D 110 136 400...

Page 26: ...26 Position 1 Damper casing 2 Mechanics 3 Damper blade 4 Inspection hole covering 5 Sensor sticker 6 Hole for camera 400 110 180 D 120 400 D 110 136 39 120 400 130 130 110 D 120...

Page 27: ...ing mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical starting mechanism 6 Hole for camera X 53 mm BFL X 72 mm BFN X 78 mm BF 300 50 X 110 400 180 50 D 300 50 50 D 110 136 400...

Page 28: ...DN 355 DN 400 X 72 mm BFN X 78 mm BF Position 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical starting mechanism 6 Hole for camera 400 X 110 180...

Page 29: ...or 5 Mounting plate 6 Mechanics 7 Thermal fuse 1 Damper 2 Mounting plate 3 Actuating mechanism 4 Temperature sensor 5 Mounting plate 6 Mechanics 7 Thermal fuse 8 Sensor sticker 9 Hole for temperature...

Page 30: ...ween the adjacent dampers must be at least 200 mm The damper blade in its closed position must be inside of the fire separating structure The fire damper may also be installed outside the wall structu...

Page 31: ...damper control parts At least one inspection hole must be accessible The damper body must not get deformed during its installation process Once the damper is built installed its blade must not grind o...

Page 32: ...5 80 BAT Tf Tf LED 1 2 S3 S1 S2 S5 S4 S6 N L1 5 80 BAT Tf Tf LED AC 230V 5A IP 67 25 C 120 C 1 COM black wire 2 NC gray wire 4 NO blue wire This limit switch is possible to connect in following two ve...

Page 33: ...fuse from the fuse holder of initiation device check its correct functionality The mechanism is identified as M1 to M5 depending on the closing spring strongness The actuator design must be checked a...

Page 34: ...stos free fire resistant mineral fibre boards The damper control devices are made of galvanized materials alternatively of stainless steel without any additional surface finish The springs are galvani...

Page 35: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...