Electronic Bin Thermostat Control
The electronic bin thermostat control is used with ice machines on dispensers or ice machines with pure water
(reverse osmosis or de-ionized). Current production Ice Beverage (IB Model) machines also have the electronic bin
thermostat control replacing the mechanical bin thermostat control.The thermostat is intended to reduce overfill
and condensation issues. If an ice machine has an electronic bin thermostat control, a bin thermostat will be
mounted in the bin.
Bin Thermostat
ELECTRONIC BIN THERMOSTAT CONTROL
The temperature control opens the bin switch (or toggle
switch) circuit when ice contacts the sensor. When ice no
longer contacts the sensor, the circuit closes and the ice
machine starts.
Specifications
Setpoint Range: -30 to 212°F (-34 - 100°C)
CONTROL SETTINGS
Verify control is set properly before proceeding.
Positioning the Touchpad Jumpers
P5 Jumper
The P5 jumper position determines if the touchpad is
locked or unlocked. The control is factory locked; to unlock
move the jumper from one pin to two pins.
Inside of Bin Thermostat Control
P4 Jumper
The P4 jumper labeled Jump 1 is used to set the control for
heating or cooling mode. Jump 2 is used to establish Set-
point at either cut-in or cutout. The Cubers use Diagram A
settings and Nugget/Flake/Chiplet use Diagram B
settings.
Cubers
Nugget/Flake/Chiplet
Display
Function
Preset Settings
SP
Set Point
40
DIF
Differential
1
ASD
Anti-Short Cycle Delay
1
OFS
Temperature Offset
0
SF
Sensor Failure Mode
1 - Cubers
0 - Nugget/Flake/Chiplet
115V
240V COM
NC
NO
C
P5
P5
P4
P4
Jump 1
Jump 2
RED LEAD
SENSOR
PROBE
BLACK
LEAD
SENSOR
PROBE
MATCH
WIRING
TO ICE
MACHINE
VOLTAGE
BIN SWITCH
or TOGGLE
SWITCH
WIRE
BIN SWITCH
or TOGGLE
SWITCH
WIRE
KEYPAD
JUMPER
LOCATION
P4
Jump 1
Jump 2
Cooling Mode
Cut-In at Setpoint
Jumper on
Left Pins
Only
Diagram
A
P4
Jump 1
Jump 2
Cooling Mode
Cut-Out at Setpoint
Jumper on
Both Pins
Jumper on
Left Pin Only
Diagram
B
PSC003-04