Contact Configurations

This is in reference to different keying positions on the 

PXN12c.  If or when 2 contacts are not in use, 9 different 

contact/keying configurations can be achieved by plugging 

the contact holes not in use with the hole plugs supplied.

  OPERATION

 To ensure safe and reliable operation,  

MELTRIC 

plugs and 

receptacles must 

be used in 

accor-

dance 

with 

their 

as-

signed 

rat-

ings.  

MELTRIC 

plugs & receptacles can only be used in conjunction 

with mating receptacles or plugs manufactured  

by MELTRIC or another licensed producer of products  

bearing the 

 

 

technology trademark.  

WARNING:

 PXN12c/DXN25c/DXN37c plugs and 

receptacles must be operated in compliance with its 

hazardous area classifications. 

When not in use, the receptacle is shielded by a protective 

lid preventing the entry of dust and  moisture.

The maximum cross-section of the conductors is 

4934 CM (2.5 mm

2

) (solid or flexible). Conductors 

must be  stripped by .315 in (8 mm).

  1.   Contacts can be soldered or crimped.  If  

crimping, crimp the contact with a KNIPEX  

crimping tool part # 61-CA500 or a GREENLEE  

crimping tool part # 4CN30. Use the 4 mm

2

  

footprint whatever the conductor cross-section.   

Perform a double crimping with a 90° rotation, in  

compliance with IEN 60352-2. For 16AWG wires, 

the ferrule (MEC7177071) is required. Place the 

ferrule over the stripped conductor and insert it 

into the contact terminal. Crimp the contact with 

the conductor and ferrule using the appropriate 

crimping tool. 

  2.      Prior to soldering or crimping a heat shrink 

sleeve (supplied- part  # 9CP0250) must be  

slipped over each conductor or alternatively  

an insulating sleeve (supplied - part # 

9SES201007301) can be used but the insulating 

sleeve must be installed using sleeve tool  

61-CA400 (sold separately).

  3.   If soldering use tin solder and a 50 W soldering  

iron.  Insert the conductor in the terminal and  

heat the terminal for about 30 s.  During heating,  

insert the solder wire in the hole at the foot of the  

terminal and let the solder penetrate by capillary  

action.  Let the terminal cool without any tension  

on the conductor.

  4.   Slip the heat shrink or insulating sleeve over the  

whole visible part of the contact, down to the molding.

  5.   Slide the heat-shrink sleeve up to the shoulder of 

the contact.  With a heat gun, apply heat evenly  

370° around the sleeve until it shrinks around the  

terminal and wire.

NOTICE:

 For a proper clamping, the use of PVC 

cables is not recommended.

WARNING:

 This product must be electrically grounded  

to Earth. A grounding terminal is provided on all metal 

accessories.

Contact Assembly/Disassembly

Once wired, contacts must be inserted through the 

rear of the interior moulding  1.  Push each contact 

fully home.  Check its proper engagement by a light 

pull  2.  Contacts can be removed with the supplied 

tool: insert the tool through the front  3. and push fully 

home  4.  Tool part # 9-LD12-37.

  GENERAL

PXN12c/DXN25c/DXN37c plugs and receptacles 

comply with international and European safety  

standards in particularly with ATEX Directive 2014/34/EU.   

PXN12c/DXN25c/DXN37c products can be installed 

in zones 1, 2 (Gas), and 21, 22 (Dust). These devices 

may be used as intrinsic safety devices provided 

they are associated with certified intrinsically safe 

equipment only. Such combination must comply with 

the requirements in IEC/EN 60079-25. Live parts are 

protected against contact test finger (IP2X/IPXXB), 

according to IEC/EN 60529.

There are inherent dangers  

associated with electrical products.  

Failure to follow safety precautions can result in 

serious injury or death. These instructions must be 

followed to ensure the safe and proper installation, 

operation and maintenance of the MELTRIC devices. 

Before installation, disconnect all sources of power to 

the circuit to eliminate the risk of electrical shock. It is 

imperative that MELTRIC explosion-proof multicontact 

plugs and receptacles are connected or disconnected 

with the circuit in a de-energized state.

  INSTALLATION

 PXN12c/DXN25c/DXN37c plugs and  

receptacles must be used in conjunction with  

other appropriately rated hazardous duty  

products and must be installed by qualified  

electricians in accordance with all applicable  

local and national electrical codes.

Assembly

Optimum operating conditions are achieved by installing  

PXN12c/DXN25c/DXN37c plugs and receptacles with 

the latch at the top.

Wiring

 Before starting, verify that the power is off, that 

the product ratings are appropriate for the  

application, and the conductors meet code  

requirements and are within the capacities of  

 the terminals noted in Table 1.

Cable

Terminal

Heat Shrink Sleeve or

Insulating Sleeve

Solder

Molding

Cable

Terminal

Funda Termocontractil 

o Funda Aislante

Soldadura

Moldura

Câble

Contact

Manchon d’isolement

Soudure

Isolant

MULTI-CONTACTS

PXN12c / DXN25c / DXN37c

ENGLISH OPERATING INSTRUCTIONS

A COMPANY OF MARECHAL ELECTRIC

MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132

Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail

@

MELTRIC.com 

INSPXNDXNMULTI H

A manufacturer of products using Marechal technology

meltric

.com

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

Table 1 — Wiring Terminal Capacity* (in AWG)

 

  Contacts 

Device 

Min 

 

Max

 

DXN25c 

16   14

DXN37c 

16   14

PXN12c 

16   14

1

2

3

4

5

1

2

3

4

Contact

Tool

©2020 MELTRIC Corporation.  All rights reserved.  