QUICK START GUIDE

SMS Alarm/Status Communicator

Single/Dual Pump Interface - FPC-30120

V2.1

Introduction

MATelec Australia’s SMS Alarm/Status Communicator features the newly designed ME-Link Module, which is a cellular CAT-M1 remote 

monitoring and control device utilising the 700Mhz frequency for ‘best in class’ signal strength. The Single/Dual Pump Interface Version 

of the Communicator reports status information and alarms from the BMS/remote output on MATelec Australia Standard Single and 

Dual Pump Controllers. The ME-Link Module can also be utilised to control external devices with the two onboard relay outputs, and 

uses easy to set up SMS commands to configure the operation and alarms without the need for any additional software. 

Safety

This SMS alarm sender panel has been designed and built for applications that are Commercial and/or Industrial in nature, operation, 

function and location. If the control panel is to be used in Domestic/Residential applications, where specific Wiring Rules in respect 

of ‘electrical supply’ protection may apply, it is the responsibility of the installing electrician to ensure compliance with relevant 

standards.

• 

Prior to installation, ensure power supply is isolated.

• 

Electrical connection to the panel must be carried out in accordance with the following pages.

• 

Additions or modifications to the control panel are not permitted and will void warranty.

• 

The controller is not intended for use by children or infirm persons without supervision.

• 

Repairs to the controller must only be carried out by a suitably qualified electrician.

This quick start guide makes use of the following symbols to indicate warnings that must be paid specific attention to:

Damage to equipment or personal harm may occur if this instruction is not followed

 

 

 

 

Electrical risk (electrocution hazard) may occur if this instruction is not followed

 

 

 

 

Summary of Contents for FPC-30120

Page 1: ...een designed and built for applications that are Commercial and or Industrial in nature operation function and location If the control panel is to be used in Domestic Residential applications where specific Wiring Rules in respect of electrical supply protection may apply it is the responsibility of the installing electrician to ensure compliance with relevant standards Prior to installation ensur...

Page 2: ... cables conduits entering the panel have mechanical protection and that the penetrations are sealed and do not compromise the weatherproof rating of the enclosure Warning All electrical connections must be carried out by a suitably qualified and registered electrician Front View Side View Bottom Mounting Frame Wall Back View Top Mounting Holes 20mm from each edge Step 2 Connections Max cable lengt...

Page 3: ... is enabled Disable the SIM pin before retrying connection 3 1 SIM Card Installation The SMS alarm sender takes a Micro SIM card which must be from a network operator who offers the CAT M1 700Mhz frequency At the time of printing all SIM cards that use the Telstra network will be compatible Other network providers will be compatible when they support CAT M1 modules 1 Ensure power to the panel is O...

Page 4: ...ff Use this command to request alarm messages for all inputs in OFF state Example response Input on messages 1 Power Off Failure 2 High Level Fault Cleared 3 Pump 1 Fault Cleared 4 Pump 2 Fault Cleared 5 6 7 ME Link Mains Power Restored 8 ME Link Battery Voltage Low title new title 4 2 Set the numbers to receive alarm messages Use this command to delete a phone number Example SMS command num del 3...

Page 5: ...Not Accepted Yet or Accepted Step 4 SMS Programming Continued msg input on message msg input off message reset Use this command to reset all settings back to defaults including the PIN Example SMS Command Response SMS Command Response reset Are you sure you want to factory reset Enter reset again within 1 minute to confirm reset Device has been reset back to factory defaults Use this command to se...

Page 6: ...t 1 On Power On Restored Input 1 Off Power Off Failure Input 2 On High Level Fault Input 2 Off High Level Fault Cleared Input 3 On Pump 1 Fault Input 3 Off Pump 1 Fault Cleared Input 4 On Pump 2 Fault Input 4 Off Pump 2 Fault Cleared Input 5 On Unused Input 5 Off Unused Input 6 On Unused Input 6 Off Unused Input 7 On ME Link Mains Power Failure Input 7 Off ME Link Mains Power Restored Input 8 On M...