Operating Instructions
Hazardous Location HLRS Series
MaxLite Hazardous Location HLRS Series
• To reduce the risk of death, personal injury or property damage from fire,
electric shock, falling parts, cuts/abrasions, and other hazards read all
warnings and instructions included with and on the fixture box and all
fixture labels.
• Before installing, servicing, or performing routine maintenance upon
this equipment, follow these general precautions.
• Commercial installation, service and maintenance of luminaires
should be performed by a qualified licensed electrician.
• DO NOT INSTALL DAMAGED PRODUCT!
• This fixture is intended to be connected to a properly installed and
grounded UL listed junction box.
• Make sure that the supply voltage is the same as the luminaire voltage.
• Do not install where the marked operating temperatures exceed the
ignition temperatures of the hazardous atmosphere.
• Do not operate in ambient temperatures above those indicated on the luminaire nameplate.
• All gasket seals must be clean and undamaged.
WARNING:
RISK OF ELECTRICALSHOCK
• Turn off electrical power at fuse or circuit breaker box before wiring fixture to the power supply.
• Turn off the power when you perform any maintenance.
• Verify that supply voltage is correct by comparing it with the luminaire label information.
• Make all electrical and grounded connections in accordance with the National Electrical
Code and any applicable local code requirements.
• All wiring connections should be capped with UL approved wire connectors.
• Luminaire must be supplied by a wiring system with an equipment grounding conductor.
CAUTION:
RISK OF INJURY
• Wear gloves and safety glasses at all times when removing luminaire from
carton, installing, servicing or performing maintenance.
• Avoid direct eye exposure to the light source while it is on.
• Account for small parts and destroy packing material, as these may be hazardous to children.
CAUTION:
RISK OF FIRE
• Keep combustible and other materials that can
burn away from luminaire and lamp/lens.
• MIN 90°C SUPPLY CONDUCTORS.
Models:
HLRS Series
Power (45=45W, 65=65W)
Voltage (U=120-277, H=347-480)
Lens Type ([BLANK]=Clear, 110°, D=Diffused,
L=Low Bay Lens, 130°)
Color Temperature ([BLANK]=5000K, 40=4000K, 30=3000K)
Mount Type ([BLANK]=3/4” NPT-Yoke Mount / U-Bracket /
Pendant, X=Ceiling, Wall 25°, Wall 90°, Stanchion 25°, Stanchion 90°)
Operating characteristic:
© Copyright 2019. MaxLite, Inc. All Rights Reserved.
12 York Ave, West Caldwell, NJ 07006 Tel: 800-555-5629 Fax: 973-244-7333 Email: info@maxlite.com
®
Picture is for illustration purposes only.
Your model may vary.
General Safety Information
This fixture is suitable for use in the following
hazardous (classified) areas as defined by the
National Electrical Code (NEC) and Canadian
Electrical Code (CEC):
Hazardous Locations
Class I, Division 2, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III, Division 1
Compliances
Environmental Ratings
UL 1598A
Suitable for hazardous
UL 1598
location.
UL 8750
UL844
Page: 1
REV: 12/19/19
Refer to the luminaire nameplate for specific classification
information, maximum ambient temperature suitability and
corresponding operating temperature (T-Code).
Rated Voltage
Power
Class I, Division 2
Class II, Division
1
100-240/277 Vac
347-480 Vac
45 W
65 W
40 W
60 W
-40°C (-40°F) ~ +55°C (131°F)
-40°C (-40°F) ~ +55°C (131°F)
-40°C (-40°F) ~ +52°C (126°F)
55°C (131°F)
52°C (126°F)