Important Safety Instructions

The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards.  It is
the owner’s and installer’s responsibility to read and comply
with all safety information and instructions accompanying these
symbols.  Failure to heed safety information increases the risk
of personal injury, property damage, and/or product damage.

HIGH VOLTAGE!

 

Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.

WARNING

Only personnel that have been trained to install, 
adjust, service or repair (hereinafter, “service”) the 
equipment specified in this manual should service 
the equipment. The manufacturer will not be 
responsible for any injury or property damage arising 
from improper service or service procedures.  If you 
service this unit, you assume responsibility for any 
injury or property damage which may result.  In 
addition, in jurisdictions that require one or more 
licenses to service the equipment specified in this 
manual, only licensed personnel should service the 
equipment.  Improper installation, adjustment, 
servicing or repair of the equipment specified in this 
manual, or attempting to install, adjust, service or 
repair the equipment specified in this manual without 
proper training may result in product damage, 
property damage, personal injury or death.

Scroll equipped units should never be used to evacuate
the air conditioning system. Vacuums this low can cause
internal electrical arcing resulting in a damaged or failed
compressor.

CAUTION

CONDENSING UNIT

HEAT PUMP
INSTALLATION & SERVICE REFERENCE

© 2005-2013, 2016 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com -or- www.amana-hac.com
P/N: IOG-4002 Date:  August 2016

Shipping Inspection

Always keep the unit upright; laying the unit on its side or top
may cause equipment damage. Shipping damage, and subse-
quent investigation is the responsibility of the carrier.  Verify
the model number, specifications, electrical characteristics,
and accessories are correct prior to installation. The distribu-
tor or manufacturer will not accept claims from dealers for trans-
portation damage or installation of incorrectly shipped units.

Codes & Regulations

This product is designed and manufactured to comply with
national codes. Installation in accordance with such codes and/
or prevailing local codes/regulations is the responsibility of the
installer.  The manufacturer assumes no responsibility for equip-
ment installed in violation of any codes or regulations. Rated
performance is achieved after 72 hours of operation. Rated
performance is delivered at the specified airflow. See outdoor
unit specification sheet for split system models or product speci-
fication sheet for packaged and light commercial models. Speci-
fication sheets can be found at www.goodmanmfg.com for
Goodman

®

 brand products or www.amana-hac.com for Amana

®

brand products. Within either website, please select the resi-
dential or commercial products menu and then select the
submenu for the type of product to be installed, such as air
conditioners or heat pumps, to access a list of product pages
that each contain links to that model’s specification sheet.

The United States Environmental Protection Agency (EPA)
has issued various regulations regarding the introduc-
tion and disposal of refrigerants. Failure to follow these
regulations may harm the environment and can lead to
the imposition of substantial fines. 

Should you have any

questions please contact the local office of the EPA.

If replacing a condensing unit or air handler, the system must
be manufacturer approved and Air Conditioning, Heating and
Refrigeration Institute (AHRI) matched.  

NOTE: 

Installation of

unmatched systems is not allowed.

Outdoor units are approved for operation above 55°F in cooling
mode.  Operation below 55°F in cooling mode requires the use
of an approved low ambient kit.

Damage to the unit caused by operating the unit in a structure
that is not complete (either as part of new construction or reno-
vation) is not covered under the warranty.

 

 

is a registered trademark of Maytag Corporation or its related companies and is used under

license to Goodman Company, L.P., Houston, TX.  All rights reserved.

Summary of Contents for Amana VSZ14

Page 1: ...ecifications electrical characteristics and accessories are correct prior to installation The distribu tor or manufacturer will not accept claims from dealers for trans portation damage or installation of incorrectly shipped units Codes Regulations This product is designed and manufactured to comply with national codes Installation in accordance with such codes and or prevailing local codes regula...

Page 2: ...or springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration NOTE These units require special location consideration in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situate the unit...

Page 3: ...ed for line lengths of 79 feet or less to obtain optimum performance For alternate line sizing options or runs of more than 79 feet refer to Remote Cooling Service Manual or TP 107 Long Line Set Application R 410A or contact your distributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3...

Page 4: ...dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit Leak Testing Nitrogen or Nitrogen Traced To avoid the risk of fire or explosion never use oxygen high pressure air or flammable gases for l...

Page 5: ...tch located near the unit do not install the switch on the unit Refer to the installa tion instructions supplied with the indoor furnace air handler for specific wiring connections and indoor unit configuration Like wise consult the instructions packaged with the thermostat for mounting and location information Overcurrent Protection The following overcurrent protection devices are approved for us...

Page 6: ...If disabling this function is desired move the jumper from DLY to NORM on the defrost control Adequate refrigerant charge for the matching HSVTC evapora tor coil and 15 feet of lineset is supplied with the condensing unit If using evaporator coils other than HSVTC coil it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should ...

Page 7: ... Charge Adjustment The outdoor temperature must be 60 F or higher Set the room thermostat to COOL fan switch to AUTO and set the tem perature control well below room temperature Purge gauge lines Connect service gauge manifold to base valve service ports Run the system on low stage for two stage units for 10 minutes to allow pressures to stabilize then check subcooling and or superheat as detailed...

Page 8: ...URATED SUCTION TEMPERATURE ºF LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 90 285 127 92 295 130 95 305 133 97 325 137 101 355 144 108 375 148 112 405 155 118 415 157 119 425 n a 121 435 n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE...

Page 9: ...7 to 9 ºF and super heat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clockwise to increase and counter clockwise to de crease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check super heat c If subcooling and superheat are high adjust TXV valve...

Page 10: ...it with Voltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filte...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ... airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refrigerant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless yo...