background image

Nexus 110 AC Sounder & Sounder-Beacon

Installation Instructions

Tone

Tone Type

Tone Description / Application

Dip Switch

3rd Stage

Peak Sound

(S1/S2)

Tone

Level (dBA@1m)

1.

970Hz (BS5839-1:2002)

O-O-O-O-O-O

18

110

2.

800Hz/970Hz @ 2Hz (BS5839-1:2002)

O-O-O-O-O-I

1

110

3.

800Hz – 970Hz @ 1Hz (BS5839-1:2002)

O-O-O-O-I-O

1

110

4.

970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)

O-O-O-O-I-I

1

110

5.

970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)

O-O-O-I-O-O

1

110

6.

554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )

O-O-O-I-O-I

1

107

7.

500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) Dutch Slow Whoop

O-O-O-I-I-O

1

110

8.

420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)

O - O - O - I - I - I

1

105

9.

500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)

O-O-I-O-O-O

1

110

10.

550Hz/440Hz @ 0.5Hz

O-O-I-O-O-I

19

107

11.

970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)

O-O-I-O-I-O

1

110

12.

2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)

O - O - I - O - I - I

1

112

13.

1200Hz – 500Hz @ 1Hz (DIN 33 404)

O-O-I-I-O-O

1

110

14.

400Hz

O - O - I - I - O - I

18

105

15.

550Hz, 0.7s/1000Hz, 0.33s

O - O - I - I - I - O

1

111

16.

1500Hz – 2700Hz @ 3Hz (Vandal Alarm)

O - O - I - I - I - I

1

116

17.

Simulated Bell

O-I-O-O-O-O

1

112

18.

2130Hz

O-I-O-O-O-I

1

113

19.

660Hz

O-I-O-O-I-O

10

109

20.

660Hz 1.8s ON/1.8s OFF

O - I - O - O - I - I

19

108

21.

660Hz 0.15s ON/0.15s OFF

O-I-O-I-O-O

19

107

22.

510Hz, 0.25s/ 610Hz, 0.25s

O - I - O - I - O - I

1

107

23.

800/1000Hz 0.5s each (1Hz)

O - I - O - I - I - O

1

111

24.

250Hz – 1200Hz @ 12Hz

O - I - O - I - I - I

1

105

25.

500Hz – 1200Hz @ 0.33Hz.

O-I-I-O-O-O

1

110

26.

2400Hz – 2900Hz @ 9Hz

O - I - I - O - O - I

1

116

27.

2400Hz – 2900Hz @ 3Hz

O - I - I - O - I - O

1

116

28.

800Hz – 970Hz @ 100Hz

O - I - I - O - I - I

1

110

29.

800Hz – 970Hz @ 9Hz

O - I - I - I - O - O

1

110

30.

800Hz – 970Hz @ 3Hz

O - I - I - I - O - I

1

110

31.

800Hz, 0.25s ON/1s OFF

O - I - I - I - I - O

1

108

32.

500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)

O - I - I - I - I - I

1

110

33.

340Hz

I-O-O-O-O-O

1

106

34.

1000Hz

I-O-O-O-O-I

18

111

35.

1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)

I-O-O-O-I-O

1

110

36.

660Hz 6.5s ON/13s OFF

I - O - O - O - I - I

19

108

37.

1000Hz/2000Hz, 1s each

I-O-O-I-O-O

1

113

38.

720Hz, 0.7s ON/0.3s OFF

I - O - O - I - O - I

1

106

39.

970Hz, 0.25s ON/OFF

I - O - O - I - I - O

1

110

40.

2800Hz, 1s ON/OFF

I - O - O - I - I - I

1

113

41.

2800Hz 0.25s ON/OFF

I-O-I-O-O-O

1

113

42.

2400/2900 @ 2Hz

I - O - I - O - O - I

1

115

43.

Chime, 554Hz/440Hz Single shot ‘ding dong’

I - O - I - O - I - O

1

104

44.

Chime, 554Hz/440Hz Repeating ‘ding dong’

I - O - I - O - I - I

1

107

45.

Chime, 970Hz/800Hz Single shot ‘ding dong’

I- O - I - I - O - O

1

106

46.

Chime, 970Hz/800Hz Repeating ‘ding dong’

I - O - I - I - O - I

1

106

47.

Hooter, Repeating

I - O - I - I - I - O

1

107

48.

Gentle alarm - Tone 2, rises slowly to full volume over 30s

I - O - I - I - I - I

1

109

49.

Time-Out Alarm – As Tone 2, cuts off after 10 mins

I-I-O-O-O-O

1

109

50.

Time-Out Alarm – As Tone 2, cuts off after 2 mins

I - I - O - O - O - I

1

109

51.

750Hz 0.33s ON/0.51s OFF

I - I - O - O - I - O

1

106

52.

750Hz 0.51s ON/0.33s OFF

I - I - O - O - I - I

1

107

53.

550Hz, 0.33s/1000Hz, 0.7s

I - I - O - I - O - O

1

111

54.

600Hz – 900Hz/ 0.9s

I - I - O - I - O - I

1

109

55.

660Hz – 680Hz/ 0.9s

I - I - O - I - I - O

1

105

56.

670Hz – 725Hz/ 0.9s

I - I - O - I - I - I

1

107

57.

920Hz – 750Hz/ 0.9s

I - I - I - O - O - O

1

110

58.

700Hz - 900Hz, 0.3s/0.6s OFF

I - I - I - O - O - I

1

109

59.

900Hz - 760Hz, 0.6s/0.3s OFF

I - I - I - O - I - O

1

110

60.

750Hz

I - I - I - O - I - I

18

107

61.

Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - O

43

62.

Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - I

43

63.

Power Only – Use with Stage 3 control for manual/intermittent horn triggering

I - I - I - I - I - O

47

64.

Reserved for future use

I - I - I - I - I - I

FR

NL

EN

DE

ES

PT

IT

PL

SE

DK

Issue 5.0 (August 2010) 18-186459-5

Copyright © Texecom Ltd

sales@klaxonsignals.com www.klaxonsignals.com

Texecom Ltd (Incorporating Klaxon Signals)

St Crispin Way, Haslingden, BB4 4PW, UK

+44 1706 233879

+44 1706 223450

Summary of Contents for WHR 100EA

Page 1: ...I I O 1 108 32 500Hz 1200Hz 3 75s 0 25s OFF AS2220 O I I I I I 1 110 33 340Hz I O O O O O 1 106 34 1000Hz I O O O O I 18 111 35 1400Hz 1600Hz 1s 1600Hz 1400Hz 0 5s NF 48 265 I O O O I O 1 110 36 660Hz 6 5s ON 13s OFF I O O O I I 19 108 37 1000Hz 2000Hz 1s each I O O I O O 1 113 38 720Hz 0 7s ON 0 3s OFF I O O I O I 1 106 39 970Hz 0 25s ON OFF I O O I I O 1 110 40 2800Hz 1s ON OFF I O O I I I 1 113...

Page 2: ...d 70mA Peak Sound Level 103 115 dBA at 1m Number of Tones 64 Frequency Range 340 2900 Hz Volume Control 20 dBA typical Remote Tone Switching Provision for 3 volt free contact activated alarm stages Operating Temperature 25 C to 55 C Casing High Impact Polycarbonate ABS IP Rating IP66 with suitable cable glands Synchronisation Automatic with Klaxon Nexus and Sonos Sounders depends on selected tone ...

Page 3: ...ationsanweisung DE Das Ziel der EG Richtlinie über Elektro und Elektronik Altgeräte ist Umwelt und Gesundheitsschäden durch Elektro und Elektronik Altgeräte so gering wie möglich zu halten Um diese Richtlinie einzuhalten dürfen Elektrogeräte die mit diesem Symbol gekennzeichnet sind nicht in den öffentlichen europäischen Entsorgungssystemen entsorgt werden Europäische Benutzer von Elektrogeräten m...

Page 4: ...araat openen om afstellingen aan de toon of het volume uit te voeren WAARSCHUWING er bevinden zich geen onderdelen in het apparaat die door de gebruiker onderhouden kunnen worden c De sounder wordt geïnstalleerd door eerst de basiseenheid te monteren en dan de externe bedradingaansluitingen aan de basis te maken De hoofdeenheid sluit dan automatisch aan wanneer het aan de basis wordt bevestigd d D...

Page 5: ...parsi della manutenzione di alcun pezzo dell unità c L apparecchio acustico si installa in primo luogo montando l unità di base e collegando quindi i cavi esterni alla base L unità principale quindi si collega automaticamente quando viene montata sulla base d La testa dell apparecchio acustico si separa dalla base sbloccando le quattro chiusure girevoli sugli angoli dell apparecchio acustico cacci...

Page 6: ...dstawy w odpowiednim miejscu i podłączenia jej do instalacji zewnętrznej Po osadzeniu głowicy sygnalizatora w podstawie następuje automatyczne podłączenie głowicy do instalacji d Aby odłączyć głowicę sygnalizatora od podstawy nale y odkręcić cztery łączniki znajdujące się w naro nikach sygnalizatora Zaleca się u ycie śrubokręta marki Philips nr 2 długość min 100mm e Uwaga głowicę mo na zamocować n...

Page 7: ...ste og andet trin indstilles uafhængigt ved hjælp af 6 vejs DIP kontakter henholdsvis S1 og S2 Den krævede indstilling vises i tabellen på næste side Alarmtonen for tredje trin er forudindstillet til at supplere den tone der vælges til første trin som vist i tabellen b Lydstyrkeregulering Enhedens lydsignal kan mindskes med op til 20 dBA ved at justere potentiometeret Teknisk specifikation Strømfo...

Reviews: