background image

                           

Installation Manual

 

 

 

 

Type

DR Family with Class II

Series

DR-15, DR-30, DR-60, DR-100

 

DR-15-5 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 5V 2.4A 

DR-15-12 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 12V 1.25A 

DR-15-15 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 15V 1A 

DR-15-24 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 24V 0.63A 

DR-30-5 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 5V 3A 

DR-30-12 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 12V 2A   

DR-30-15 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 15V 2A 

DR-30-24 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 24V 1.5A 

DR-60-5 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 5V 6.5A 

DR-60-12 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 12V 4.5A 

DR-60-15 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 15V 4A 

DR-60-24 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 24V 2.5A 

DR-100-12  INPUT: 100 -240VAC 3A 50/60Hz   

OUTPUT: 12V 7.5A 

DR-100-15  INPUT: 100 -240VAC 3A 50/60Hz   

OUTPUT: 15V 6.5A 

DR-100-24  INPUT: 100 -240VAC 3A 50/60Hz   

OUTPUT: 24V 4.2A 

 

 

Introduction 

DR with class II is a double insulated DIN rail power supply series, meaning it is ungrounded. Like other Mean Well’s 
DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source. 

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the  top  for  DR-15,  the  input  terminals  on  the  right  and  output  on  the  left  for  DR-30,  DR-60,  and  DR-100. 
Mounting  orientations  other  than  that,  such  as  upside  down,  horizontal,  or  table-top  mounting,  is  not 
allowed. 

 

 
 
 

 

3

Use stranded copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

Rated Current of 
Equipment (Amp) 

6A 

6-10A 

13-16A 

16-25A 

Cross-section of 
Lead(mm

2

 ) 

0.75 

1.00 

1.5 

2.5 

Note

Current each wire carries should be de-rated to 80% of the current suggested 

above when using 5 or more wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

1

DR15-100_1680-21407-0590-E-0418

Summary of Contents for DR-15-12

Page 1: ...nted on a TS35 Standard DIN rail Installation 1 Always allow good ventilation clearances 5mm left and right 40mm above and 20mm below around the unit in use to prevent it from overheating Also a 10 15 cm clearance must be kept when the adjacent device is a heat source 2 The appropriate mounting orientation for the unit is vertical the input terminals at the bottom and output on the top for DR 15 t...

Page 2: ...he locking action 10 For other information about the products please refer to www meanwell com for details Warning Caution 1 Risk of electrical shock and energy hazard All failure should be examined by a qualified technician Please do not remove the case of the power supply by yourself 2 Risk of electric arcs and electric shock danger to life Connecting both the primary and the secondary sides tog...

Page 3: ...gainst risk of fire replace only with same type and rating of fuse Pour ne pas compromettre la protection contre les risqué d incendie remplacer par un fusible de même type et de memes caractéristiques nominales Note 1 Pollution Degree 2 applies where there is only non conductive pollution that might temporarily become conductive due to occasional condensation Generally refer to dry well ventilate...

Page 4: ...B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hexavalent chromium Cr6 Polybrominated biphenyls PBB Polybrominated diphenyl ethers PBDE PCB and its components X O X O O O Metal structure parts X O O O O O Plastic structure parts O O O O O O Accessories O O O O O O C...

Page 5: ...e for you Addresses and Contacts Headquarter Switzerland Angst Pfister Sensors and Power AG Thurgauerstrasse 66 CH 8050 Zurich Phone 41 44 877 35 00 sensorsandpower angst pfister com Office Germany Angst Pfister Sensors and Power Deutschland GmbH Edisonstraße 16 D 85716 Unterschleißheim Phone 49 89 374 288 87 00 sensorsandpower de angst pfister com ...

Reviews: