 GENERAL

The SPeX is a single-pole plug and receptacle for use 

in  explosive atmospheres and conforms to the relevant 

international and European standards, particularly the 

ATEx Directive 2014/34/UE.  SPeX can be used in 

zones 1 and 2 (gas) and 21 and 22 (dust).

In order to guarantee a connection and disconnection 

in complete safety, the SPeX receptacle is fitted with 

an electromechanical device ( ring) for electrical 

interlocking with a contactor (breaker) and an integral 

pilot control circuit.

Receptacle contacts are protected against standard 

test  finger  (IP2x/IPxxB)  according  to  IEC/EN  60529 

standard.

There are inherent dangers 

 

associated  with  electrical  pro-

ducts.  Failure  to  follow  safety  precautions can re-

sult in serious injury or death. These instructions  

must  be  followed  to  ensure  the  safe  and  proper  

installation, operation and maintenance of the 

MELTRIC devices. Before installation, disconnect all 

sources  of  power  to  the  circuit  to  eliminate  the  risk 

of electrical shock. This product must be installed 

with an electrical interlock that prevents connection or  

disconnection in a loaded condition.

 RATINGS

SPeX devices are provided with optional auxiliary 

contacts that make after and break before the phase 

contacts. The ratings for auxiliary contacts are shown 

in Table 1.

 INSTALLATION

SPeX must be installed by a qualified person in 

accordance with all applicable local and national  

electric codes.  Be sure power is off before starting.

The supply of the pilot circuit must be protected 

against transient over-voltages of 4 kV by means of an  

appropriate isolating device. Follow the requirements 

set forth by the ATEx classification. DO NOT ATTEMPT 

TO  TURN  THE  RING  TOWARDS  ‘‘1’’  WHEN  THE 

PLUG IS NOT ENGAGED.

Electrical interlocking with a contactor is mandatory.

Assembly

Insert cable through the cable gland and the handle or 

through the inclined sleeve.

Wiring of the pilot wires

Use  flexible  conductors  with  a  cross-sectional  area 

between 0.5 and 1 mm

(16 to 20 AWG).

NOTICE: 

 These conductors must be connected to the 

wires of the microswitch by means of the isolated crimping  

lugs supplied.  Use an appropriate crimping tool.

A typical pilot circuit wiring diagram is shown below.

Wiring of the main conductor

Wire the main conductors within the amperage 

and hazardous duty requirements of the ATEX 

(T5) classification.  The cross-section must be at least 

that defined in the certificate or the CE Declaration of 

Conformity, depending on the maximum current.

Strip  the  conductor  by  1.8”  (46  mm).    Crimp  the 

threaded  lug  or  the  ferrule  with  the  appropriate  die 

(NFC 20-130 or VDE 0220 or another).  Hexagonal 

crimping is recommended.

Tighten  the  threaded  lug  with  a  24  mm  wrench  or 

tighten the ferrule with a screw and a washer with a 

19 mm wrench.  Apply a torque ca. 95 ft-lbs (70 N.m).

While tightening the ferrule, prevent the contact from 

rotating or transmitting torque to the device with a 24 

mm wrench.

Assembly of the connector

Assemble the handles on the body of the products 

with the supplied gaskets and screws and tighten the 

cable gland with an appropriate tool.  To achieve  the 

IP65/IP66 of an interlocked connector, use a cable that  

incorporates the two pilot wires that are required for the  

interlock, or use an ATEX cable gland bushing that allows  

the passage of the main cable and the two pilot cables. 

The silicone ring must be assembled on the receptacle 

ring.

Assembly of the metal inclined sleeve.

Maintain air and creepage distances when assembling 

the appliance inlet or the receptacle onto the metal  

inclined sleeve, according to the operating voltage of 

the main and auxiliary circuit and the degree of  pollution.

The  metal  inclined  sleeve  must  be  grounded       

to Earth.

Assembly of the plug/inlet cap

Place the lug located at the tip of the wire under one 

of the mounting screws on the inlet side, or under the 

screw provided under the receptacle side.

Color-coded rings

In order to achieve watertightness, do not forget the 

color-coded ring at the rear of the inlet or receptacle.

The  color-coded  rings  allows  visual  identification  of 

the pole depending on the color code of each  country. 

Place  the  color  coded  gasket  between  the  inlet  or  

receptacle and its rear accessory or panel.

Isolating ring

When  assembling  the  SPeX  on  a  metallic  support 

(enclosure, panel, etc.), the isolating ring must be 

 positioned  as  above.  Be  sure  to  use  the  black  flat  

gasket, which guarantees the watertightness, between 

the isolating ring and the accessory.

Receptacles, plugs, connectors and inlets are protected  

against  dust  and  water  ingress  by  means  of  caps, 

which must be re-assembled after use.

To achieve IP65/IP66, the receptacle or connector cap 

must be assembled with its slot facing the socket-outlet 

protruding finger.

 OPERATION

To ensure safe and reliable operation, MELTRIC 

plugs and receptacles must be used in accordance  

with their assigned ratings.  

They  can  only  be  used  in  conjunction  with  mating 

receptacles  or  plugs  manufactured  by  MELTRIC  or 

another licensed producer of products bearing the 

TM

  technology trademark.

Color-coded ring

Color-coded ring

Flat gasket

Isolating ring

L1

L2

L3

N

L1

L2

L3

N

P1

P2

L1

L2

L3

N

L1

L2

L3

N

P1

P2

  

Max 

Min 

  SPeX  750 MCM 

2/0 

12-14 AWG

Table 2 - Wiring Terminal Capacity

  

Main Contacts  

Aux. Contacts 

Table 1 - Auxiliary Contact Ratings

  Device  120VAC 

240VAC  480VAC 600VAC

 

  SPeX 

– 

6A (220 max)* 

– 

* Rating is not UL or CSA listed.

SPeX

OPERATING INSTRUCTIONS

INSSPEX E

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

ENGLISH OPERATING INSTRUCTIONS

©2020 MELTRIC Corporation.  All rights reserved.  

Summary of Contents for SPeX

Page 1: ...he ferrule with a screw and a washer with a 19 mm wrench Apply a torque ca 95 ft lbs 70 N m While tightening the ferrule prevent the contact from rotating or transmitting torque to the device with a 24 mm wrench Assembly of the connector Assemble the handles on the body of the products with the supplied gaskets and screws and tighten the cable gland with an appropriate tool To achieve the IP65 IP6...

Page 2: ...MELTRIC designs and manufactures its products in accordance with Marechal key ing standards established to ensure intermatablility with similarly rated products manufactured by Marechal Electric Group INSSPEX E WARNING DANGER CAUTION NOTICE ADVERTENCIA DANGER CAUTION AVISO WARNING DANGER CAUTION NOTICE ADVERTENCIA DANGER CAUTION AVISO MARECHAL ELECTRIC S A S au capital de 5 341 400 SIRET 552 149 5...

Page 3: ... la bague empêchez le contact de tourner ou de transmettre le couple au dispositif avec une clé de 24 mm Assemblage du connecteur Assemblez les poignées sur le corps des produits avec les joints et les vis fournis et serrez la goupille de câble à l aide d un outil approprié Pour obtenir l indice de protection IP65 IP66 d un connecteur verrouillé utilisez un câble qui intègre les deux fils pilotes ...

Page 4: ...es des produits Meltric MELTRIC Corporation possède la certification ISO 9001 Ses produits sont conçus fabriqués et classés conformément aux normes UL CSA et IEC applicables MELTRIC conçoit et fabrique ses produits selon les normes de configurations des contacts de Marechal établies pour garantir la compatibilité de ses produits avec les produits de classes similaires fabriqués par Marechal Electr...

Page 5: ...riete el Ferrul con un tornillo y una rondana con una llave Allen de 19 mm Aplique un torque de 95 ft lbs 70 N m Mientras aprieta el Ferrul evite el contacto de la rotación o transmisión de torque de la llave Allen de 24 mm con el dispositivo Ensamble del conector Ensamble las manijas en el cuerpo de los dispositivos con los empaques y tornillos suministrados y apriete el conector tipo glándula co...

Page 6: ...da ISO 9001 Sus productos están diseñados manufacturados y con rangos de acuerdo a los estándares aplicables de las normas UL CSA y IEC MELTRIC manufactura sus productos de acuerdo con las posiciones de bloqueo estándar de Marechal para asegurar la interconexión con productos de rangos similares fabricados por Marechal Electric WARNING DANGER CAUTION NOTICE ADVERTENCIA DANGER CAUTION AVISO CAUTION...

Reviews: