CGSW AL29-4C Stainless Steel - Pressure Rated Venting System
CGVSW 444 Stainless Steel - Pressure Rated Venting System
IMPORTANT:
DO NOT INSTALL WITHOUT FIRST READING THESE
INSTRUCTIONS VERY CAREFULLY.
Corr/Guard, manufactured by Metal-Fab, Inc. is a special stainless steel
venting system for gas-fired appliances listed as Cat. II, III & IV or in Canada,
Type BH Gas Venting Systems per ULC-636, with rated operating temperature
of 550
°
F (287
°
C), and rated for positive pressure of 15” w.c. Metal-Fab, Inc.
recommends the system be inspected once a year by a qualified service
technician.
Examine all components for possible shipping damage before installation.
Proper joint assembly is essential for a safe installation. Follow these
instructions exactly as written. Check severe stress of joints upon
completion of assembly. This venting system must be free to expand and
contract. Check for unrestricted movement through walls, ceilings and
roof penetrations. Different manufacturers have different joint systems
and adhesives. Do not mix pipe, fittings or joining methods from different
manufacturers.
Venting system design may be limited by appliance performance. Consult
appliance installation instructions to determine proper sizing and limitations
such as maximum horizontal length and height, maximum number of elbows or
offsets, connecting two or more appliances to a common venting system, and
other limitations that may affect design and installation.
It is the responsibility
of the installer to contact local building and fire officials concerning any
installation restrictions and/or inspection requirements that may apply.
Permits may be required before starting an installation. Installation is to be in
accordance with local building code requirements and National Codes: USA –
NFPA 54 ANSI-Z223.1 or NFPA 211. In Canada – CAN/CGA-B149.1 or CAN/
CGA-B149.2 Propane Installation Code as applicable.
GENERAL
Corr/Guard is to be installed in accordance with these installation instructions
and those of the appliance manufacturer. For conditions and applicable
restrictions not specifically mentioned herein, contact building or fire officials
having jurisdiction in your area. The following is a guide to assist a professional
installer.
•
Proper operation of the venting system and appliance is dependant on the
use of all parts specified by Metal-Fab for use in the particular installation.
System performance may be affected if the proper assembly of all required
parts is not accomplished.
•
Refer to appliance’s instructions to determine proper sizing and connection
of the venting system to the appliance.
•
Tee sections should only be used in conjunction with a drain on appliances
tested for use with a drain, or if allowed by the appliance manufacturer for
multiple appliance connections.
•
If required by the appliance manufacturer, a drain fitting must be located
as close as possible to the appliance flue outlet. Unless a drain fitting is
supplied with the appliance, install only a Corr/Guard Drain Fitting.
•
More than one Category II, III or IV appliance may not be connected into the same
vent system, unless the appliance manufacturer specifically approved such a system
and the appliances are designed for multiple venting. Cat. II, III or IV appliances MAY
NOT share any part of their vent system with a natural draft appliance.
•
Check the joints and seams for gas tightness when using the venting system
with a Cat. III or Cat. IV appliance.
•
Except for installation in one and two family dwellings, a venting system that
extends though any zone above that on which the connected appliance is
located shall be provided with an enclosure having a fire resistance rating
equal to or greater than that of the floor or roof assemblies through which it
passes.
For 5” diameter Corr/Guard (CGSW or CGVSW) HORIZONTAL
installation, any enclosures must be NON-COMBUSTIBLE MATERIALS!
•
Corr/Guard shall not be routed into, through, or within any other vent, such
as an existing masonry or factory-built chimney flue that is connected to
another appliance.
•
WARNING! Do not place or install insulation in any required clearance
spaces surrounding the venting system.
•
Enclosure of exterior mounted venting systems below the roofline is
recommended to limit condensation and protect from mechanical damage.
VENT LENGTH
For installations that require non-standard vent lengths, CGSW or CGVSW
Variable Length vent sections may be used. The vent section consists of a
telescoping assembly that is adjusted from 5” to 20” additional finished length
to the venting system. Once proper length is set, secure the vent section by
tightening the integral compression band.
WARNING: Variable Length vent
sections are not to be subjected to vertical force loads. Use appropriate
supports.
JOINT CONNECTIONS
Each Corr/Guard vent component contains
a seal gasket on the female end of the vent
joint and locking tabs. Mechanical fastening
of the joint is automatic and requires no
tools. Visually check the gasket for proper
location within the pipe bead during assembly
or flue gases could leak, resulting in carbon
monoxide poisoning. Assembly of joints is
shown on
FIG. 1
:
NOTE:
When assembling Corr/Guard single
wall vent, always install the female flue end
elevated above the male flue end. The “UP” arrow will point to the elevated
female flue end. Change of directions are made by using a male to male or
female to female adapter depending on the flow of the condensate.
1. Insert the male end of the vent pipe into the adjoining female vent section
until the bead of the male joint stops at the edge of the female joint.
2. When properly inserted to the fullest extent, the integral locking tabs will
snap into place, securing the joint.
Before Proceeding, verify that all
locking tabs are engaged for each joint assembly.
APPLIANCE CONNECTION
If an appliance does not supply a condensate drain and one is required per the
appliance manufacturer’s instructions or local codes, install a drain fitting in the
horizontal portion of the vent, as close as possible to appliance outlet. If the
appliance flue collar is not designed to accept the Corr/Guard joint profile, an
adapter may be available from Metal-Fab. (See
FIG. 2
)
CORR/GUARD
SINGLE WALL
INSTALLATION INSTRUCTIONS
7' MAX.
APPLIANCE
TERMINATION
APPLIANCE ADAPTER
SEAL AT APPLIANCE WITH
HIGH TEMPERATURE RTV
ELBOW
HORIZONTAL DRAIN TEE
OR DRAIN FITTING
HANGER
STRAP
WALL
THIMBLE
TO DRAIN DISPOSE OF
CONDENSATE ACCORDING
TO LOCAL CODE
7' MAX.
APPLIANCE
TERMINATION
APPLIANCE ADAPTER
SEAL AT APPLIANCE WITH
HIGH TEMPERATURE RTV
ELBOW
HORIZONTAL DRAIN TEE
OR DRAIN FITTING
HANGER
STRAP
WALL
THIMBLE
TO DRAIN DISPOSE OF
CONDENSATE ACCORDING
TO LOCAL CODE
Side Wall
Installation
FIG. 2
INSERT MALE END UNTIL THE
END OF THE FEMALE PROFILE
MAKES CONTACT WITH THE
MALE PROFILE BEAD.
VERIFY THAT TABS “SNAP”
INTO LOCKING POSITION.
FIG. 1
CONDENSATE DRAINS
Corr/Guard drain fittings contain a 1/2” (13 mm) dia. steel tube that should
be located at the bottom of the vent when properly installed. A plastic drain
hose must be attached to the tube and a trap loop formed into the drain hose
(trap loop should be 4 times the appliance maximum pressure – in. w.c.). Vents
using a drain hose must be inspected periodically to assure that water is in
the trap loop.
If trap loop is not maintained, exhaust from the connected
appliances may accumulate inside the building area.
HORIZONTAL VENTING AND WALL PENETRATION
A venting system that exits through a side wall shall:
•
Terminate not less than 12 inches (305 mm) above the ground.
•
Be located above the snow line in geographical areas where snow
accumulates.
•
Not be located in traffic areas such as walkways unless the venting system
is at least 7 feet (2.1 m) above the ground.
When an appliance incorporates a combustion air inlet system, the venting
system shall terminate:
•
6 feet (1.8m) or more from the combustion air intake of any appliance.
•
More than 3 feet (0.9m) from any other building opening, gas utility meter, or
service regulator.
•
Less distance is permitted if specified in the appliance’s installation
instructions.
For horizontal venting:
•
Means shall be provided for draining condensate. Due to ice build up and
blockage, it is required that proper sloping be employed when the vent is
installed horizontally. A male to male or female to female adapter can be
used to allow condensate to drain properly.
•
Any portion of a horizontally installed vent shall have a slope (upwards for
Cat. II, III or IV appliances or downwards for Cat. III or IV appliances) not
less than 1/4 inch (6.4 mm) every 12 inches (305 mm) to prevent collection
of condensate at any location in the assembly.
•
Use non-combustible hanger straps a minimum of every 7 feet (1.8 m)
to support the vent system from ceiling joints or other solid structures.
WARNING! Do not puncture vent system!
•
Vent must not sag or dip providing areas for condensate to collect.
Install venting system maintaining clearances as indicated in these
instructions and the labeled product.