DIN310 & DIN310E Earth Leakage Relay
User's Manual

A BRIEF OVERVIEW

1.

DESCRIPTION

The DIN310 and DIN310E are microprocessors based earth leakage relays designed for measure the 
low-level current flowing from the live part of the installation to the earth in the absent of the insulation 
fault.  A  zero  phase  current    transformer  is  connected  to  the  relay  and  function  as  the  sensor  for 
sensing the leakage current. All conductors of the circuit to be protected shall go through the ZCT.

For better fault preventive control of the system or equipment to be protected, DIN310E series comes 
with  a pre-fault  alarm contact and a positive safety  contact. The  pre-fault alarm contact   is  activated 
whenever the leakage current exceed 50% of the sensitivity setting. While the positive safety contact  
is activated if the relay  is  power  up and function correctly. The DIN310E series  also built-in a digital 
input port for remotely reset the relay after leakage fault trip, manual test trip or ZCT connection fault.

          

a  -  Trip status indicator

c      Alarm status indicator

d     Increment button

e     Decrement button

f      Reset button

g      Integral test button

h      DP2 indicator

i       DP1 indicator

a

c

d

e

f

g

i

j

k

Symbols

I       -  Sensitivity setting

   t    -  Time delay setting

Flt 1 -  Fault record #1 (Most recent)

n

 Flt 2 -  Fault record #2

Flt 3 -  Fault record #3 (Oldest)

b

b     Model

-

-

-

-

-

-

-

-

-

h

j       FUNC display

k      DATA display

-

Summary of Contents for DIN310

Page 1: ...es comes with a pre fault alarm contact and a positive safety contact The pre fault alarm contact is activated whenever the leakage current exceed 50 of the sensitivity setting While the positive safety contact is activated if the relay is power up and function correctly The DIN310E series also built in a digital input port for remotely reset the relay after leakage fault trip manual test trip or ...

Page 2: ... fault alarm condition then follow by 1 5s testing on the trip time delay End of time delay relay trip b Leakage Fault Trip Reset Manual Test Trip Reset Press the RESET button once or through digital input port c ZCT Connection Fault Reset Press the RESET button once or through digital input port Reset is inhabited if the fault is not rectify d Parameters Viewing When the relay is operate normal a...

Page 3: ...measured leakage current 50 of the I n and self reset when the measured leakage current 45 of the I n Activated and latch when the relay is tripped Table 3 Output contact description 6 RECORDS a Record the 3 latest tripped faults current or tSt for manual trip test b The records are stored in non volatile memory c To clear the entire record database Step 1 When the relay is healthy press RESET but...

Page 4: ...tandard 35mm DIN rail mounting Approximate weight 0 38kg excluding ZCT 9 CONNECTION DIAGRAMS 10 CASE DIMENSION Applicable to DIN310E series only TRIP CONTACT LOAD L1 L2 L3 N PE 6 2 3 4 5 7 1 8 9 10 11 12 13 14 L N AUX SHUNT TRIP MIKRO ZCT DIN310 TRIP CONTACT SAFETY CONTACT LOAD 6 2 3 4 5 7 1 8 9 10 11 12 13 14 L N AUX CONTACTOR MIKRO ZCT DIN310E REMOTE RESET Typical application diagram for DIN310 ...

Reviews: