1. DESCRIPTION

NX232A Earth-fault Relay User's Guide

start/

start/

8

CASE DIMENSIONS

 

 

    

7. CONNECTION DIAGRAMS

 a) Earth Fault Relay

  

Indicators

    

Mechanical

    

  

 

 

Outputs

  

    

Figure 7: Case Dimensions

 

 Setting Ranges

    Low-set setting I>.....................0.10 - 5.00 A (2%-100%)

    Time multiplier kt> ...................0.01 - 1.00

    High-set setting I>> .................0.10 - 50.0 A (2%-1000%)

    High-set definite time t>>.........0.00 - 100 s

    Low-set definite time t > ..........0.00 - 100 s

6. TECHNICAL DATA

    

    Ratings

    Rated current 

I

n

 ......................5 A

    Frequency ...............................50 Hz or 60 Hz

    Burden ....................................< 0.3 VA at 

I

n

   

    Auxiliary Supply

    

    NX232A-240A ........................198~265 VAC

    Supply frequency ....................50 Hz or 60 Hz

    VA rating .................................3 VA typical

    NX232A-110A..........................94~127 VAC

   

  NX232A

R1

R2

  NX233A

R1

R2

96 mm

96 mm

Front

110mm
100mm

90mm

90mm

L1

L2

L3

N

  NX232A

R1

R2

       Auxiliary supply .....................Green LED indicator

       Pick up ..................................Red LED indicator

       Trip ........................................7 segment LED and 

Red LED indicators

    NX232A-240AD ......................85~265 VAC/110~370 VDC

The NX232A is a microprocessor based 

numerical earth-fault relay. It uses 

fundamental frequency current 

measurement for excellent harmonic 

current rejection. The relay consists of 

independent low-set and high-set 

elements. The high-set element can be 

disabled by the user. The time current 

characteristics of the low-set elements 

are definite time or five selectable IDMT 

curves. The high-set element is a 

definite time or instantaneous relay. The 

4-digit panel display on the NX232A 

allows the display of the present load 

current; recorded fault current for last 

tripping; and all settings of the relay.

   

 2. LIGHT INDICATORS

      
  The indicators display the status of the system as follow:

   

Table 1: System Status

   

      1 = ON          0    = OFF      X= don’t care, not blinking   
      B = blinking   DT = DATA    FUNC = FUNCTION 

     

            Indicator 
  Aux   l>   l>>  FUNC  DT                     Status
     0    0     0       0        0    No Auxiliary power supply.
     1    0     0       X       X    Normal condition, no tripping.
     1    1     0       X       X    Low-set overcurrent triggered,
                                           time delay countdown started.
     1    0     1       X       X    High-set overcurrent triggered,
                                           time delay countdown started.
     1    B     0       B       B    Low-set tripped, 
                                           DT LEDs show tripped value.

     1    0     B       B       B    High-set tripped,
                                           DT LEDs show tripped value.

     1     X     X      1       B    Programming mode.

b) Overcurrent Relay and Earth fault relay (3 phase 4 wire system)

Thermal withstand.....................4 x In continuous

       Rated voltage ..........................250 VAC

       Continuous carry .....................5A (cos

      

= 1.0)

       Expected electrical life ............10

5

 operations

       Expected mechanical life ........5 x10

6

 operations

Environmental conditions

Temperature .......................... -10ºC to 55ºC

Humidity ................................ 5% to 95% non-condensing

Mounting................................ Panel mounting

Dimension (mm) .................... 96(w) x 96(h) x 110(d)

Enclosure protection.............. IP54 at the panel

Approximate weight............... 0.7 kg

   

Accuracy

       Protection thresholds ...............± 5%

       Time delay.................................± 5% with a

                                                          mimimum of 50ms

Rev M0 (04/19)

    (0.00 - 1.00, step 0.01; 1.00-10.0, step 0.10;

     10.0-100, step 0.5)