INDICATORS

Pre-fault alarm ...........................................................… Red indicator
Leakage trip delay time .............................................… Red indicator
Leakage trip ..............................................................… 7-segment display and red indicators
Manual test trip .................................................……......….. 7-segment display and red indicators
ZCT connection fault ................................................…….... 7-segment display and red indicators
Trip records .................................................................. 7-segment display
Real-time leakage current ............................................ 7-segment display

ZERO-PHASE CURRENT TRANSFORMERS

To operate with Mikro's ZCT series of current transformers

NX300A & NX300EA Earth Leakage Relay
User’s Manual

A BRIEF OVERVIEW

MECHANICAL

Mounting....................................................................… Standard DIN 96x96mm panel mount
Approximate weight....................................................... 0.58kg (excluding ZCT)

9.

CONNECTION DIAGRAMS

AUX

L1 L2 L3 N

PE

N

L

MIKRO
ZCT

The EARTH wire

NX300A

must not pass

1

2

3

4

5

6

7

8

through the ZCT

SHUNT

TRIP

CONTACT

TRIP

NC

NO

C

9

10

11

12

13

14

15

16

LOAD

AUX

REMOTE

L1 L2 L3 N

PE

N

L

RESET

MIKRO
ZCT

NX300EA

The EARTH wire
must not pass

1

2

3

4

5

6

7

8

through the ZCT

CONTACTOR

TRIP

ALARM

POSITIVE SAFETY

CONTACT

CONTACT

CONTACT

NC

NO

C

NO

C

NC

NO

C

9

10

11

12

13

14

15

16

LOAD

a - DATA display

b - Trip status indicator

c - Alarm status indicator
d - DP2 indicator
e - Decrement button

f - Increment button

g - RESET button

h - TEST button

i - Model

j - DP1 indicator

k - FUNC display

1.

DESCRIPTION

Symbols

I

n

- Sensitivity setting

t

- Time delay setting

Flt 1 - Fault record #1 (Most recent)

Flt 2 - Fault record #2

Flt 3 - Fault record #3 (Oldest)

The NX300A and NX300EA are microprocessors based earth leakage relays designed for measure
the low-level current flowing from the live part of the installation to the earth in the absent of the

insulation fault. A zero phase current transformer is connected to the relay and function as the sensor
for sensing the leakage current. All conductors of the circuit to be protected shall go through the ZCT.

For better fault preventive control of the system or equipment to be protected, NX300EA series comes

with a pre -fault alarm contact and a positive safety contact. The pre-fault alarm contact is activated
whenever the leakage current exceed 50% of the sensitivity setting. While the positive safety contact
is activated if the relay is power up and function correctly. The NX300EA series also built-in a digital

input port for remotely reset the relay after leakage fault trip, manual test trip or ZCT connection fault.

10. CASE DIMENSION

* Applicable to NX300EA  series only

90mm
70mm

96mm

96mm

SIDE

FRONT

  PANEL
CUTOUT

91±0.5mm

91±0.5mm

EARTH LEAKAGE RELAY

NX 300A

TEST

RESET

TRIP

ALARM

a

b

c

d

e

f

g

h

k

j

i