background image

 

 

MELSECNET/H 

Network Module

 

 

 

User’s Manual

(Hardware)

 

QJ71NT11B

 

 

  Thank you for purchasing the Mitsubishi programmable controller 

MELSEC-Q Series. 

 

 

Prior to use, please read both this manual and detailed manual 
thoroughly and familiarize yourself with the product. 

 

   

 

MODEL

QJ71NT11B-U-HW 

MODEL

CODE 

13JY93 

IB(NA)-0800440-A(0810)MEE 

 

 

 

 

 

 

©

2008 MITSUBISHI ELECTRIC CORPORATION

 

Summary of Contents for 13JY93

Page 1: ...chasing the Mitsubishi programmable controller MELSEC Q Series Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL QJ71NT11B U HW MODEL CODE 13JY93 IB NA 0800440 A 0810 MEE 2008 MITSUBISHI ELECTRIC CORPORATION ...

Page 2: ...ctions of the programmable controller system please read the CPU module user s manual In this manual the safety instructions are ranked as DANGER and CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Note that t...

Page 3: ...cause a malfunction failure or drop When using the programmable controller in the environment of much vibration tighten the module with a screw Tighten the screw in the specified torque range Undertightening can cause a drop short circuit or malfunction Overtightening can cause a drop short circuit or malfunction due to damage to the screw or module z Completely turn off the externally supplied po...

Page 4: ...oreign substances such as sawdust or wiring debris inside the module Such debris could cause fires damage or erroneous operation z The module has an ingress prevention label on its top to prevent foreign matter such as wire offcuts from entering the module during wiring Do not peel this label during wiring Before starting system operation be sure to peel this label because of heat dissipation z Ma...

Page 5: ...tion This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2008 MITSUBISHI ELECTRIC CORPORATION ...

Page 6: ...8 5 1 2 Precautions for wiring twisted pair cable 9 5 2 Twisted Bus System When using Version 1 10 compatible CC Link dedicated cable 10 5 2 1 Specifications of Version 1 10 compatible CC Link dedicated cable 10 5 2 2 Precautions for wiring Version 1 10 compatible CC Link dedicated cable 11 5 3 Connecting Twisted Pair Cable and Bar Terminal for Version 1 10 Compatible CC Link Dedicated Cable 12 6 ...

Page 7: ...system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller EMC and Low Voltage Directives compliant into other machinery or equipment refer to Chapter 9 EMC AND LOW VOLTAGE DIRECTIVES of the QCPU User s Manual Hardware Design Maintenance and Inspection The CE mark indicating compliance with the EMC and Low Voltage Directives is p...

Page 8: ...dule The network module is used as a control normal station in the PLC to PLC network in the MELSECNET H system After unpacking the network module confirm that the following products are enclosed Model name Part name Quantity Model QJ71NT11B MELSECNET H network module Twisted bus type 1 QJ71NT11B Terminal resistor 110 1 2W brown brown brown 1 ...

Page 9: ...tion 31 Communication speed Twisted pair cable Version 1 10 compatible CC Link dedicated cable 156kbps 3 1200m 1200m 312kbps 600m 900m 625kbps 400m 600m 1 25Mbps 200m 400m 2 5Mbps 200m 5Mbps 150m 10Mbps Not applicable 100m Overall distance for one network Connection cable Twisted pair cable optional Version 1 10 compatible CC Link dedicated cable optional 4 Number of I O occupied points 32 points ...

Page 10: ...he module with the fixing hole as a supporting point Incorrect loading of the module can cause a malfunction failure or drop When using the programmable controller in the environment of much vibration tighten the module with a screw Tighten the screw in the specified torque range Undertightening can cause a drop short circuit or malfunction Overtightening of screws can cause damages to the screws ...

Page 11: ...l during wiring Before starting system operation be sure to peel this label because of heat dissipation 5 Before handling the module touch a grounded metal object to discharge the static electricity from the human body Not doing so may cause a failure or malfunction of the module 6 Tighten the screws such as module fixing screws within the following ranges Screw location Tightening torque range Mo...

Page 12: ...ormal station D LINK On In data link Off Not in data link RD On Receiving data Off Not receiving data QJ71NT11B 1 2 3 L ERR On Communication error Off No communication error 2 Station number Mode setting switches Used to set the station number and mode of the network module Factory default setting 1 Setting range 10 1 Indication 0 0 Setting error The ERR LED turns on 0 1 to 3 2 Station number 1 to...

Page 13: ...6 3 Spring clamp terminal block Used to connect a twisted pair cable or Version 1 10 compatible CC Link dedicated cable Refer to Section 5 1 2 2 b ...

Page 14: ... substances such as sawdust or wiring debris inside the module Such debris could cause fires damage or erroneous operation z The module has an ingress prevention label on its top to prevent foreign matter such as wire offcuts from entering the module during wiring Do not peel this label during wiring Before starting system operation be sure to peel this label because of heat dissipation z Make sur...

Page 15: ...y the following specifications can also be used even not introduced Item KNPEV SB 0 5SQ 1P 1 Cross section Cable Shielded twisted pair cable Core 2 core Conductor resistance 20 39 4 km or less Insulation resistance 20 10M km or more Dielectric withstand voltage V min 1000VAC 1 minute Capacitance 1KHz 70nF km or less on average Characteristic impedance 100KHz 110 10 1 Applicable only when the commu...

Page 16: ... or I O signal cables 3 Do not use any of shielded twisted pair cables e g One pair among three pairs for supplying power b Connecting terminating resistors For the network modules at both ends connect the DA and DB by a terminating resister 110 1 2W provided with the module c Connecting disconnecting a shielded twisted pair cable Shut off all phases of the external power supply for the system 2 C...

Page 17: ...g a bar terminal the cable can be inserted without pressing the button Insertion hole Open close button 2 Disconnecting the cable Keep pressing the open close button by a slotted screwdriver until the cable is completely pulled out 5 2 Twisted Bus System When using Version 1 10 compatible CC Link dedicated cable 5 2 1 Specifications of Version 1 10 compatible CC Link dedicated cable The following ...

Page 18: ...he SLD and FG are connected within the module d Connecting a terminating resistor For the network module at both ends connect the DA and DB by a terminating resister 110 1 2W provided with the module e Connecting disconnecting Version 1 10 compatible CC Link dedicated cable Shut off all phases of the external power supply for the system 2 Connection of cable a Connection method Connect a blue whit...

Page 19: ... Co Ltd representative Bar type solderless terminal TE0 5 10 0 3 to 0 5mm2 Tool for bar type solderless terminal NH 79 For inquiries and orders please contact your local NICHIFU TERMINAL MFG Co Ltd representative Bar type solderless terminal AI0 5 10WH 0 5mm2 CRIMPFOX UD6 CRIMPFOX UD6 4 1 CRIMPFOX UD6 6 1 Tool for bar type solderless terminal CRIMPFOX ZA3 For inquiries and orders please contact yo...

Page 20: ...of the bar terminal or crimping tool used In the example a crimping tool FA VTC125T9 manufactured by Mitsubishi Electric Corporation is used 1 Strip the cable jacket by 5 5mm to 6 5mm 2 Place the terminal in the correct place in the end of the locater 3 Insert the terminal until it reaches to the locater 4 Insert the stripped cable into the terminal and crimp it ...

Page 21: ...14 6 EXTERNAL DIMENSIONS QJ71NT11B 27 4 1 08 90 3 54 17 5 0 69 98 3 86 Unit mm in ...

Page 22: ...ant Cugat del Valles Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B V French Branch 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 Hong Kong Mitsubishi Electric Automation Hong Kong Ltd 10th Floor Manulife Tower 169 Electric Road North Point...

Reviews: