background image

CM20AN-E-NZ

VRF City Multi Product Catalogue

Summary of Contents for City Multi R2 Series

Page 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...

Page 2: ...ucts and services Since our foundation we have risen to the very pinnacle of the air conditioning industry and we continue to maintain that position The company is proud of its achievements in providing some of the most energy efficient systems on the market Unparalleled Mitsubishi Electric Air Conditioning Systems 2 ...

Page 3: ...n Air to Water Series P 214 Installation Information P 236 Maintenance Equipment P 246 Contents VRF Outdoor Heat Source Units P 6 BC Controllers P 101 Indoor Units P 112 Technologies and functions P 162 Ventilation Systems P 181 Remote Controller P 190 Hot Water Solution Air to Water Series P 214 Installation Information P 236 Maintenance Equipment P 246 Contents VRF 3 ...

Page 4: ... BC CONTROLLER CMB M P VENTILATION Air to Water Series Air cooled Water cooled WR2 Series Simultaneous Cooling and Heating BC CONTROLLER Standard High efficiency PQRY P R2 Series PURY P PUHY EP PUHY HP PURY EP Main BC controller Main BC controller with sub BC controller Sub BC controller LGH GUF Series PWFY Series P 91 P 68 P 11 P 69 P 12 P 101 P 182 Air Handling Unit Controller P 189 P 215 QAHV S...

Page 5: ...sed type Concealed type PEFY P Low noise type Compact depth type Low static pressure type Medium static pressure type High static pressure type Fresh air intake type PMFY P 1 way ariflow type Ceiling suspended type Wall mounted type Floor standing type PCFY P PKFY P Advanced Touch Controller ON OFF Remote Controller AHC adapter PI DIDO AI controller LONWORKS interface BACnet interface P 115 P 126 ...

Page 6: ...e range of products in order to meet air conditioning needs for both new constructions and existing buildings Mitsubishi Electric offers a wide range of products in order to meet air conditioning needs Outdoor Heat Source Units VRF 6 ...

Page 7: ...ior appearance of the building Heat recovery Y Series WY Series Simultaneous Cooling and Heating P 69 Simultaneous cooling and heating operation with a two pipe system available only from Mitsubishi Electric Greater energy efficiency made possible by using the waste heat from both the heat source units and indoor units Heat recovery Simultaneous Cooling and Heating P 12 Simultaneous cooling and he...

Page 8: ... 14 16 14 16 32HP P800 14 18 14 18 34HP P850 16 18 16 18 36HP P900 18 18 18 18 38HP P950 10 14 14 10 14 14 40HP P1000 10 14 16 10 14 16 42HP P1050 10 16 16 10 16 16 44HP P1100 14 14 16 14 14 16 46HP P1150 14 16 16 14 16 16 48HP P1200 16 16 16 16 16 16 50HP P1250 16 16 18 16 16 18 52HP P1300 16 18 18 16 18 18 54HP P1350 18 18 18 18 18 18 Indicates single modules and indicates combination modules Th...

Page 9: ...0 20 42HP P1050 20 22 20 22 44HP P1100 22 22 22 22 Indicates single modules and indicates combination modules The circled numbers in the table indicate the horse power and the combination of S L and XL modules Color of the external finish depends on the production location Please refer to the specification for details on the external finish 1 22HP P550 can be used only in combination with others F...

Page 10: ...0 12 12 14HP P350 14 14 16HP P400 16 8 8 16 8 8 18HP P450 18 8 10 18 8 10 20HP P500 20 10 10 20 10 10 22HP P550 22 10 12 22 10 12 24HP P600 24 12 12 24 12 12 28HP P700 14 14 14 14 30HP P750 14 16 14 16 32HP P800 16 16 16 16 34HP P850 16 18 16 18 36HP P900 18 18 18 18 Indicates single modules and indicates combination modules The circled numbers in the table indicate the horse power and the combina...

Page 11: ... length Maximum allowable length Furthest indoor from first branch Vertical differentials between units Indoor outdoor outdoor higher Indoor outdoor outdoor lower Indoor indoor Maximum meters Feet 1 000 3 280 165 190 equivalent 541 623 40 131 1 Maximum meters Feet 50 164 2 40 131 3 15 49 4 This image shows the standard type Cooling or Heating Heat pump Standard High efficiency Features P 14 P 16 S...

Page 12: ...m 164ft 2 3 Between indoor units top bottom differential 30m 98ft 5 Between indoor units top bottom differential 30m 98ft 5 BC controller BC controller Indoor unit Indoor unit The world s first two pipe system that simultaneously cools and heats The CITY MULTI R2 Series offers the ultimate in freedom and flexibility Cool one zone while heating another Our exclusive BC controller makes two pipe sim...

Page 13: ...igh pressure gas COP of the heat recovery system Compressor shuts down All indoor units stop for a few minutes There is no need to stop the compressor The refrigerant noise that is generated when the refrigerant flow is switched can be lowered When cooling heating mode switches When cooling heating mode switches Piping connections Piping connections Unique to Mitsubishi Electric our heat recovery ...

Page 14: ... P YNW A1 4 31 4 06 3 91 3 42 3 67 3 38 4 41 4 16 3 93 3 85 3 69 3 73 3 50 0 00 1 00 2 00 3 00 4 00 5 00 8HP 10HP 12HP 14HP 16HP 18HP 20HP Previous model PUHY EP YLM A1 New model PUHY EP YNW A1 4 36 4 10 4 09 3 59 3 80 3 48 4 67 4 49 4 27 3 92 3 83 3 73 4 20 0 00 1 00 2 00 3 00 4 00 5 00 8HP 10HP 12HP 14HP 16HP 18HP 20HP Previous model PUHY EP YLM A1 New model PUHY EP YNW A1 4 06 3 78 3 79 3 40 4 ...

Page 15: ...curs in the upstream and downstream of conventional propeller fans This helps reduce power consumption as well as minimises sound levels Furthermore the change of the orientation of the fan blade from the outer circumference direction to the inner circumference direction reduces air leakage from the outer circumference and sends more air to the upstream of the fan Visualization of air flow of fan ...

Page 16: ...between terminals is reduced and the insulation distance is shorter This improves the motor s operation performance and contributes to high efficiency operation of the compressor Improved high efficiency motor Fixed scroll Conventional mechanism Orbiting scroll F Slider Vortex pressing load F is high Centrifugal force canceling mechanism F F Vortex pressing load F F is low Centrifugal force cancel...

Page 17: ...pipe mm in 22 2 7 8 Brazed 22 2 7 8 Brazed 22 2 7 8 Brazed FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1 Air flow rate m3 min 170 185 240 L s 2 833 3 083 4 000 cfm 6 003 6 532 8 474 Control Driving mechanism Inverter control Direct driven by motor Inverter control Direct driven by motor Inverter control Direct driven by motor Motor output kW 0 92 x 1 0 92 x 1 0 92 x 1 6...

Page 18: ...azed FAN Type x Quantity Propeller fan x 2 Propeller fan x 2 Propeller fan x 2 Propeller fan x 2 Air flow rate m3 min 270 300 305 365 L s 4 500 5 000 5 083 6 083 cfm 9 534 10 593 10 770 12 888 Control Driving mechanism Inverter control Direct driven by motor Inverter control Direct driven by motor Inverter control Direct driven by motor Inverter control Direct driven by motor Motor output kW 0 46 ...

Page 19: ... x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure swit...

Page 20: ...wder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 wi...

Page 21: ...x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure swi...

Page 22: ...ing for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 wit...

Page 23: ...ternal dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 ...

Page 24: ...mension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 ...

Page 25: ...legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16...

Page 26: ...nsion HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 7...

Page 27: ...egs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 ...

Page 28: ... 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi Inverter circuit COMP FAN Over c...

Page 29: ...ts powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 ...

Page 30: ...r output kW 7 7 9 8 11 1 12 5 Case heater kW External finish Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type M...

Page 31: ...40 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch a...

Page 32: ...UNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3...

Page 33: ...858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4...

Page 34: ...r BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without l...

Page 35: ...l dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 ...

Page 36: ...ion HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16...

Page 37: ... 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without...

Page 38: ... mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 1...

Page 39: ... 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without...

Page 40: ...x 2 Propeller fan x 2 Air flow rate m3 min 305 305 305 L s 5 083 5 083 5 083 cfm 10 770 10 770 10 770 Control Driving mechanism Inverter control Direct driven by motor Inverter control Direct driven by motor Inverter control Direct driven by motor Motor output kW 0 46 x 2 0 46 x 2 0 46 x 2 6 External static press 0 Pa 0 mmH2O 0 Pa 0 mmH2O 0 Pa 0 mmH2O Compressor Type Inverter scroll hermetic compr...

Page 41: ...For 8 branches CMY Y1010 G For 10 branches Fin Guard PAC FG01S E For side surfaces of S and L modules a set of two pieces PAC FG02S E For side surfaces of XL modules a set of two pieces PAC FG01B E For rear surface of S module PAC FG02B E For rear surface of L module a set of two pieces PAC FG03B E For rear surface of XL module a set of two pieces 1 If there is a risk that the drain water will fre...

Page 42: ...d galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 ...

Page 43: ...lar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 wi...

Page 44: ...d steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73...

Page 45: ...x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4...

Page 46: ...ion HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure prote...

Page 47: ...out legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure protection High pressure sen...

Page 48: ...ed steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 2...

Page 49: ...ithout legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 750 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 Protection devices High pressure protection High pressur...

Page 50: ...steel sheets powder coating for BS type MUNSELL 3Y 7 8 1 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 750 x 740 1 858 1 798 without legs x 1 750 x 740 1 858 1 798 without legs x 1 750 x 740 1 858 1 798 without legs x 1 750 x 740 in 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 ...

Page 51: ...0 13 16 without legs x 68 15 16 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi Inverter circuit COMP FAN Over current protection Compressor Fan motor Refrigerant Type x original charge R410A x 10 8 kg 24 lbs R410A x 10 8 kg 24 lbs Net weight kg lbs 340 750 340 750 Heat exchanger ...

Page 52: ...r kW External finish Pre coated galvanized steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 w...

Page 53: ... type MUNSELL 5Y 8 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar Pre coated galvanized steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 74...

Page 54: ...eel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70...

Page 55: ...740 1 858 1 798 without legs x 920 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa ...

Page 56: ... mm 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 920 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 36 1 4 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure protection Hig...

Page 57: ... x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 Protection devices High pressure protection High pressure sensor High...

Page 58: ...teel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 7...

Page 59: ...egs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 240 x 740 1 858 1 798 without legs x 1 750 x 740 in 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 48 7 8 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 Protection devices High pressure protection High pressure sensor...

Page 60: ...steel sheets powder coating for BS type MUNSELL 5Y 8 1 or similar External dimension HxWxD mm 1 858 1 798 without legs x 1 750 x 740 1 858 1 798 without legs x 1 750 x 740 1 858 1 798 without legs x 1 750 x 740 1 858 1 798 without legs x 1 750 x 740 in 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29...

Page 61: ...68 15 16 x 29 3 16 73 3 16 70 13 16 without legs x 68 15 16 x 29 3 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi Inverter circuit COMP FAN Over current protection Over current protection Compressor Fan motor Refrigerant Type x original charge R410A x 10 8 kg 24 lbs R410A x 1...

Page 62: ...r CMB M108 1012 1016V JA1 When the outdoor unit capacity is P200 to P900 CMY R303S G For CMB M108 1012 1016V JA1 and for use with sub BC controller CMY R304S G For CMB P1016V KA1 When the outdoor unit capacity is P200 to P1000 CMY R305S G For CMB P1016V KA1 and for use with sub BC controller CMY R306S G For CMB M104 108V KB1 Branch pipe Header CMY R160 J1 Joint for connecting to two nozzles Fin Gu...

Page 63: ...vide full heating performance even at 15 C and continuous heating for up to 250 minutes in one continuous cycle ensuring phenomenal heating performance at low temperatures Heating or Cooling Installation image System Pipe Lengths 1 When the outdoor unit is installed below the indoor unit top bottom differential is 40m 131 ft Refrigerant Piping Lengths Total length Maximum allowable length Farthest...

Page 64: ...A Standard CITY MULTI PUHY P400 YSJM A Standard CITY MULTI PUHY P250 YJM A 50 0 25 0 kW 10 0 25 20 15 10 5 0 3 Outdoor temp C W B 20 25 10 0 10 20 20 C Outdoor temperature 25 C 15 5 C 15 5 C 15 5 C 15 5 C 15 5 C 15 5 C Expanded to 25 C Hyper Heating Inverter System Hyper Heating Inverter System Conventional CITY MULTI Conventional CITY MULTI PUHY P YJM PUHY P YJM Conventional CITY MULTI Convention...

Page 65: ...d Long Product Life Cycle Backup operation Alternate operation High Static Pressure Setting With our new ZUBADAN model high static pressure setting up to 60Pa is available by setting the dip switch 0Pa at factory setting making it an ideal and flexible solution for any type of application Shorter Warm up in About 20 Minutes With its new improved startup performance the ZUBADAN system achieves full...

Page 66: ...V 1 Indoor LEV Discharged pressure is maintained at high level Discharged Pressure Middle pressure Injection pressure Suction pressure J I A H B Pressure Enthalpy diagram showing HIC Heating efficiency improved by HIC D F Heating capacity is maintained by the Flash injection circuit Secures sufficient refrigerant by Flash injection circuit With its new highly effective defrost feature which preven...

Page 67: ...0 153 500 12 86 21 7 20 6 19 8 3 49 50 0 170 600 13 35 22 5 21 4 20 6 3 74 P15 P250 1 34 59 ø15 88 ø5 8 Brazed ø28 58 ø1 1 8 Brazed 56 0 191 100 18 16 30 6 29 1 28 0 3 08 63 0 215 000 18 04 30 4 28 9 27 8 3 49 P15 P250 1 43 60 ø15 88 ø5 8 Brazed ø28 58 ø1 1 8 Brazed 15 24 C 59 75 F 5 43 C 23 109 F 3 phase 4 wire 380 400 415V 50 60Hz 15 27 C 59 81 F 25 15 5 C 13 60 F 50 130 of outdoor unit capacity...

Page 68: ...fter that point Refrigerant piping lengths Total length Maximum allowable length Furthest indoor unit from first branch Vertical differentials between units Indoor heat source heat source higher Indoor heat source heat source lower Indoor indoor Maximum meters Feet 300 500 984 1640 165 190 equivalent 541 623 40 131 2 Maximum meters Feet 50 164 40 131 15 49 Cooling or Heating Heat pump Features P 7...

Page 69: ... 20m 98ft 65ft 5 1 When the heat source unit is installed below the indoor unit top bottom differential is 40m 131ft 2 Details refer to the DATA BOOK 3 Farthest Indoor from BC controller can exceed 40m 131ft till 60m 197ft if no Indoor sized P200 P250 connected Details refer to the DATA BOOK 4 Distance of Indoor sized P200 P250 from BC must be less than 10m 32 ft if any 5 Distance of Indoor sized ...

Page 70: ...etween 10 C 45 C can be used Benefits of the WY WR2 Series Installation image It is possible now to combine the features of VRF with a water circuit using CITY MULTI WR2 WY In this case the heat is discharged to a water source rather than to the outside air The advantages of a water cooled system are that the water can be delivered at optimized temperatures and volumes which allows even greater fl...

Page 71: ...Heat recovery First Heat recovery First Cooling tower Expansion tank Pump Water piping Heating Heating Heating Cooling Heating Heating Heating Cooling Cooling Cooling Cooling Heating Cooling Cooling Cooling BC controller Heat source unit Heat exchanger GL Pump Thermal storage tank Heating The water circuit is closed Heat taken from water Heat radiated to water Auxiliary heat source WR2 system diag...

Page 72: ... Height 1 100 43 5 16 Width 880 34 11 16 Depth 550 21 11 16 Height 1 100 43 5 16 Width 880 34 11 16 mm in To indoor unit liquid twinning pipe optional part To indoor unit gas twinning pipe optional part Piping is necessary between the heat source units Depth 550 21 11 16 Height 1 450 57 1 8 Width 880 34 11 16 To indoor unit liquid To indoor unit gas S module Depth 550 21 11 16 Height 1 100 43 5 16...

Page 73: ...ote controller ON The valve closes and stops the water flow during standby and Thermo OFF to reduce the energy consumption of the pump Heat source unit operation status Valve opening Water flow rate Time min 0 Time Stopped Standby Thermo ON Thermo ON Remote controller ON Thermo OFF Thermo OFF Power save function Water flow rate control High EER and COP compared to conventional models Comparison of...

Page 74: ...r Starting method Inverter Inverter Inverter Motor output kW 4 8 6 2 7 7 Case heater kW External finish Galvanized steel sheets Galvanized steel sheets Galvanized steel sheets External dimension HxWxD mm 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 in 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 Protection devices High pressure protection High ...

Page 75: ...l sheets Galvanized steel sheets External dimension HxWxD mm 1 450 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High p...

Page 76: ...Motor output kW 13 0 15 0 16 1 Case heater kW 0 045 240 V 0 045 240 V External finish Galvanized steel sheets Galvanized steel sheets Galvanized steel sheets External dimension HxWxD mm 1 450 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High ...

Page 77: ...50 1 100 x 880 x 550 1 100 x 880 x 550 in 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi High press...

Page 78: ...teel sheets External dimension HxWxD mm 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High p...

Page 79: ...x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi Inverter circuit COMP Over heat protection Over current protection Over heat protection Over current ...

Page 80: ...vanized steel sheets External dimension HxWxD mm 1 450 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi ...

Page 81: ...Y302S G2 651 or above Total capacity of indoor unit Branch pipe Header CMY Y104 G For 4 branches CMY Y108 G For 8 branches CMY Y1010 G For 10 branches Twinning kit CMY Y100VBK3 For PQHY P400 P600YSLM A1 CMY Y200VBK2 For PQHY P700 P900YSLM A1 81 SPECIFICATIONS VRF Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Series VRF Indoor Units Ventilation Systems Technologie...

Page 82: ...method Inverter Inverter Inverter Motor output kW 4 8 6 2 7 7 Case heater kW External finish Galvanized steel sheets Galvanized steel sheets Galvanized steel sheets External dimension HxWxD mm 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 in 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure se...

Page 83: ...ish Galvanized steel sheets Galvanized steel sheets Galvanized steel sheets External dimension HxWxD mm 1 450 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4...

Page 84: ...ic compressor Inverter scroll hermetic compressor Starting method Inverter Inverter Inverter Motor output kW 13 0 15 0 16 1 Case heater kW 0 045 240 V 0 045 240 V External finish Galvanized steel sheets Galvanized steel sheets Galvanized steel sheets External dimension HxWxD mm 1 450 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8...

Page 85: ...880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 in 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pre...

Page 86: ...5 9 5 Case heater kW External finish Galvanized steel sheets Galvanized steel sheets Galvanized steel sheets External dimension HxWxD mm 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 1 100 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 43 5 16 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 ...

Page 87: ...0 x 880 x 550 1 450 x 880 x 550 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi devices Inverter circuit COMP Over heat protection Over current protect...

Page 88: ...0 1 450 x 880 x 550 in 57 1 8 x 34 11 16 x 21 11 16 57 1 8 x 34 11 16 x 21 11 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi Inverter circuit COMP Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over he...

Page 89: ...essure protection High pressure sensor High pressure switch at 4 15 MPa 601 psi High pressure sensor High pressure switch at 4 15 MPa 601 psi Inverter circuit COMP Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Refrigerant Type x original charge R410A x 6 0 kg 14 lbs R410A x 6 0 kg 14 lbs Net weight kg ...

Page 90: ... capacity of indoor unit CMY R203S G 601 650 Total capacity of indoor unit CMY R204S G 651 1000 Total capacity of indoor unit CMY R205S G 1001 or above Total capacity of indoor unit Reducer CMY R301S G For CMB M104 106 108 1012 1016V J1 When the heat source unit capacity is P200 to P300 CMY R302S G For CMB M108 1012 1016V JA1 When the heat source unit capacity is P200 to P900 CMY R303S G For CMB M...

Page 91: ...ing Lengths Total length Furthest indoor from outdoor Furthest indoor from first branch Vertical differentials between units Indoor outdoor outdoor higher Indoor outdoor outdoor lower Indoor indoor Maximum meters Feet 150 492 80 90 equivalent 262 295 30 98 Maximum meters Feet 50 164 40 131 15 49 P200YKMD A 1 When the outdoor unit is installed below the indoor unit top bottom differential is 30m 98...

Page 92: ... P200 Nominal cooling heating capacity kW 330 13 981 38 5 8 1050 41 11 32 1 fan type 2 fan type 1 fan type 2 fan type 1338 52 11 16 330 13 1050 41 11 32 VKMD model Single phase type YKMD model Three phase type PUMY P112 125 140VKM5 YKM4 BS PUMY P200YKMD A BS EER COP EER COP VKM YKM Series Refer to the installation manual for installation restrictions and requirements A compact single fan unit is a...

Page 93: ... type Operable in temperatures up to 52 C The PUMY Series has an expanded guaranteed cooling operation range of up to 52 C so it can be used reliably even if the outdoor air temperature rises abnormally during the hot summer daytime Inverter technology allows units to operate at outdoor air temperatures as high as 52 C Performs well even in narrow spaces and in multiple installations where heated ...

Page 94: ...ayout for easier connection Back Right Bottom Front 1 fan type 2 fan type Optional parts For the PUMY Series Description Model Remarks Branch box PAC MK34BC For PUMY SP VKMD A YKMD A PUMY P VKM5 YKM4 YKMD A PAC MK54BC For PUMY SP VKMD A YKMD A PUMY P VKM5 YKM4 YKMD A Branch 2 Branch CMY Y62 G E For PUMY SP VKMD A YKMD A PUMY P VKM5 YKM4 YKMD A Header CMY Y64 G E For PUMY SP VKMD A YKMD A PUMY P VK...

Page 95: ...W Operating Current A Dimensions H x W x D mm Weight kg Branch Indoor Side mm Piping diameter mm mm Liquid Gas mm Connection Method to Indoor Unit to Outdoor Unit Model Source Outdoor V Phase Hz Main Outdoor Side Gas Liquid Wiring Features of the Branch Box Connecting a branch box makes it possible to connect to Mitsubishi Electric indoor units room air conditioners Mr SLIM that do not normally su...

Page 96: ...door Total branch pipe length Farthest branch pipe length Total main pipe length Farthest main pipe length Branch box Indoor Branch box Branch box Refrigerant Piping Length Vertical Differentials Between Units Refrigerant Piping Length Vertical Differentials Between Units Refrigerant Piping Length Vertical Differentials Between Units Refrigerant Piping Length Vertical Differentials Between Units R...

Page 97: ...Starting method Inverter Inverter Inverter Inverter Motor output kW 2 1 3 1 3 5 3 7 External finish Galvanized Steel Sheet Munsell No 3Y 7 8 1 1 Galvanized Steel Sheet Munsell No 3Y 7 8 1 1 Galvanized Steel Sheet Munsell No 3Y 7 8 1 1 Galvanized Steel Sheet Munsell No 3Y 7 8 1 1 External dimension H W D mm 981 1 050 330 25 981 1 050 330 25 981 1 050 330 25 981 1 050 330 25 inch 38 5 8 41 3 8 13 1 ...

Page 98: ...ranch box 2 units CITY MULTI P10 P100 3 2 P10 P140 3 2 P10 P140 3 2 P10 P140 3 2 Branch box P22 P100 3 4 P22 P100 5 6 P22 P100 6 7 P22 P100 7 8 Sound pressure level measured in anechoic room dB A 51 54 52 54 53 56 54 56 Refrigerant piping diameter Liquid pipe mm inch 9 52 3 8 Flare 9 52 3 8 Flare 9 52 3 8 Flare 9 52 3 8 Flare Gas pipe mm inch 15 88 5 8 Flare 15 88 5 8 Flare 15 88 5 8 Flare 15 88 5...

Page 99: ...P100 5 P15 P100 5 Branch box 2 units 8 CITY MULTI P15 P140 3 or 2 7 P15 P140 3 P15 P140 3 Branch box P15 P100 7 or 8 7 P15 P100 8 P15 P100 8 Sound pressure level 5 measured in anechoic room dB A 49 51 50 52 51 53 Sound power level 5 measured in anechoic room dB A 69 71 70 72 71 73 Refrigerant piping Liquid pipe mm in 9 52 3 8 9 52 3 8 9 52 3 8 diameter Gas pipe mm in 15 88 5 8 15 88 5 8 15 88 5 8 ...

Page 100: ...P100 5 Branch box 2 units 8 CITY MULTI P15 P140 3 or 2 7 P15 P140 3 P15 P140 3 P15 P200 3 Branch box P15 P100 7 or 8 7 P15 P100 8 P15 P100 8 P22 P100 8 Sound pressure level 5 measured in anechoic room dB A 49 51 50 52 51 53 57 61 Sound power level 5 measured in anechoic room dB A 69 71 70 72 71 73 Refrigerant piping Liquid pipe mm in 9 52 3 8 9 52 3 8 9 52 3 8 9 52 3 8 diameter Gas pipe mm in 15 8...

Page 101: ...BC Controllers 101 ...

Page 102: ...e unit to deliver a mixture 2 phase of hot gas for heating and liquid for cooling all through the same pipe The three pipe system allocates a pipe to each of these phases When this mixture arrives at the BC controller it is separated and the correct phase is delivered to each indoor unit according to the individual requirement for either heating or cooling The refrigerant flow is adjusted accordin...

Page 103: ... CMB M V JA1 CMB P V KA1 CMB M V KB1 When mixing the use of a conventional J JA KA KB type and latest J1 JA1 KA1 KB1 type BC controller please refer to the DATABOOK for details Outdoor unit Heat source unit Main BC controller J1 type Main BC controller J1 type Model 4 6 8 E P200 to E P350 12 CMB M104V J1 CMB M106V J1 CMB M108V J1 CMB M1012V J1 CMB M1016V J1 16 Number of branches Connectable outdoo...

Page 104: ... M V J1 V JA1 V KB1 CMB P V KA1 Easier maintenance with inbuilt detachable drain pan Conventional model Latest model Piping CMB P V JA V KA V KB CMB M V JA1 V KB1 CMB P V KA1 Drain pan inbuilt detachable Sub BC connection Drain pan externally attached Low pressure piping Low pressure piping connected to a sub BC make installation easier Outdoor unit Heat source unit Main BC controller JA1 or KA1 t...

Page 105: ...for connecting to two nozzles VRF Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Series VRF Indoor Units Ventilation Systems Technologies and Functions Remote Controller Hot Water Solution VRF BC Controllers VRF S Series 105 BC CONTROLLER ...

Page 106: ...2 3 8 Brazed Indoor unit Model 50 or smaller 12 7 1 2 Brazed bigger than 50 15 88 5 8 Brazed 19 05 3 4 22 2 7 8 with optional joint pipe used Field drain pipe size mm in O D 32 1 1 4 O D 32 1 1 4 O D 32 1 1 4 Net weight kg lbs 26 58 29 64 33 73 Sound power level measured in anechoic room Rated operation dB A 59 59 59 Defrost dB A 71 71 71 Sound pressure level measured in anechoic room 15 Rated ope...

Page 107: ...15 Rated operation dB A 40 40 Defrost dB A 53 53 Accessories Drain Connection pipe Washer Tie band 1 Installation foundation work electrical connection work insulation work power source switch and other items shall be referred to the Installation Manual 2 The equipment is for R410A refrigerant 3 Install this product in a location where noise refrigerant noise emitted by the unit will not disturb t...

Page 108: ... 3 4 Brazed 12 7 1 2 Brazed 28 58 1 1 8 Brazed 19 05 3 4 Brazed 12 7 1 2 Brazed 28 58 1 1 8 Brazed P351 to P400 mm in O D 22 2 7 8 Brazed 12 7 1 2 Brazed 28 58 1 1 8 Brazed 22 2 7 8 Brazed 12 7 1 2 Brazed 28 58 1 1 8 Brazed P401 to P600 mm in O D 22 2 7 8 Brazed 15 88 5 8 Brazed 28 58 1 1 8 Brazed 22 2 7 8 Brazed 15 88 5 8 Brazed 28 58 1 1 8 Brazed P601 to P650 mm in O D 28 58 1 1 8 Brazed 15 88 5...

Page 109: ... 28 1 5 8 Brazed P1001 or above mm in O D 34 93 1 3 8 Brazed 19 05 3 4 Brazed 41 28 1 5 8 Brazed Field drain pipe size mm in O D 32 1 1 4 Net weight kg lbs 68 150 Sound power level measured in anechoic room Rated operation dB A 68 Defrost dB A 74 Sound pressure level measured in anechoic room 15 Rated operation dB A 50 Defrost dB A 56 Accessories Drain Connection pipe Washer Tie band 1 Installatio...

Page 110: ... Galvanized steel plate Lower part drain pan Pre coated galvanized sheets powder coating Connectable outdoor heat source unit capacity P200 to P1100 Indoor unit capacity connectable to 1 branch 13 Model P80 or smaller Use optional joint pipe combining 2 branches when the total unit capacity exceeds P81 External dimension HxWxD mm 250 x 1 135 x 622 in 9 7 8 x 44 11 16 x 24 1 2 Refrigerant piping di...

Page 111: ... 58 1 1 8 Brazed 19 05 3 4 Brazed 34 93 1 3 8 Brazed 28 58 1 1 8 Brazed 19 05 3 4 Brazed 34 93 1 3 8 Brazed P801 to P1000 mm in O D 28 58 1 1 8 Brazed 19 05 3 4 Brazed 41 28 1 5 8 Brazed 28 58 1 1 8 Brazed 19 05 3 4 Brazed 41 28 1 5 8 Brazed P1001 or above mm in O D 34 93 1 3 8 Brazed 19 05 3 4 Brazed 41 28 1 5 8 Brazed 34 93 1 3 8 Brazed 19 05 3 4 Brazed 41 28 1 5 8 Brazed Field drain pipe size m...

Page 112: ...Indoor Units VRF 112 ...

Page 113: ...h air intake type Model PEFY P VMS1 L E PEFY P VMA L E PEFY P VMHS E PEFY P VMHS E F PEFY P VMH E F Line Up P15 P20 P25 P32 P40 P50 P63 P71 P80 P100 P125 P140 P200 P250 Reference page P 134 P 136 P 139 P 143 P 143 Type Ceiling suspended type Wall mounted type Floor standing type Model PCFY P VKM E PKFY P VLM E PKFY P VKM E PFFY P VKM E2 PFFY P VLEM E PFFY P VLRM E PFFY P VLRMM E Line Up P10 P15 P2...

Page 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...

Page 115: ...t is uniformly comfortable air conditioning The airflow direction of each vane can be set using the wired remote controller or wireless remote controller PAR SL100A E Units are equipped with high and low ceiling operation modes that make it possible to switch the airflow volume to match the height of the room Being able to choose the optimum airflow volume helps optimize the breezy sensation felt ...

Page 116: ...on Installation is possible without removing the screws for the corner panel and the control box they simply need to be loosened This lowers the risk of losing screws After reviewing the power supply terminal position in the electrical box the structure has been redesigned to improve connectivity This makes complex wiring work easier The top and bottom positions of the liquid and gas pipes have be...

Page 117: ...nput A 0 25 0 25 0 25 0 29 0 43 0 60 0 99 External finish Galvanized steel sheet External dimension H x W x D mm 258 x 840 x 840 258 x 840 x 840 258 x 840 x 840 258 x 840 x 840 258 x 840 x 840 298 x 840 x 840 298 x 840 x 840 in 10 3 16 x 33 3 32 x 33 3 32 10 3 16 x 33 3 32 x 33 3 32 10 3 16 x 33 3 32 x 33 3 32 10 3 16 x 33 3 32 x 33 3 32 10 3 16 x 33 3 32 x 33 3 32 11 3 4 x 33 3 32 x 33 3 32 11 3 ...

Page 118: ...ency filter element PAC SH59KF E P20 P25 P32 P40 P50 P63 P80 P100 P125 Space panel PAC SJ65AS E P20 P25 P32 P40 P50 P63 P80 P100 P125 Duct flange for fresh air intake PAC SH65OF E P20 P25 P32 P40 P50 P63 P80 P100 P125 Panel Corner panel With signal Receiver With 3D i see Sensor With New Wireless Remote Controller With Auto Elevation Panel PLP 6EA PLP 6EAL PLP 6EAE PLP 6EALE PLP 6EAJ PLP 6EAJE PLP ...

Page 119: ...pe Compact 119 VRF Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Series VRF Indoor Units Ventilation Systems Technologies and Functions Remote Controller Hot Water Solution VRF BC Controllers VRF S Series ...

Page 120: ...lly fed into the room to reduce the cold draft feeling This airflow is ideal for offices and restaurants The panel weighs 3 kg and the main unit weighs 14 kg P15 P20 and P25 models or 15 kg P32 P40 and P50 models These weights are 5 kg lighter than the PLFY VEM E model allowing easy suspension Above ceiling height of 245 mm The square design matches 2 2 600 mm 600 mm ceiling construction specifica...

Page 121: ...te m3 min 6 5 7 5 8 0 6 5 7 5 8 5 6 5 8 0 9 0 7 0 8 0 9 5 7 5 9 0 11 0 9 0 11 0 13 0 Lo Mid Hi L s 108 125 133 108 125 142 108 133 150 117 133 158 125 150 183 150 183 217 cfm 230 265 282 230 265 300 230 282 318 247 282 335 265 318 388 318 388 459 External static press Pa 0 Motor Type DC motor Output kW 0 05 Air filter PP Honeycomb fabric long life type Refrigerant pipe diameter Gas Flare mm in ø12...

Page 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...

Page 123: ...rflow 290 mm 11 7 16 in Simple panel design Drain pump as a standard feature Vane control The drain can be positioned anywhere up to 583 mm 22 15 16 in from the ceiling surface providing greater flexibility with long cross piping and allowing more versatility with piping layouts The unobtrusive slim line profile of the cassette is designed to work in harmony with ceilings and light fittings especi...

Page 124: ...5 0 38 0 43 0 46 0 66 0 69 0 69 0 83 1 33 1 33 External finish Unit Galvanized steel plate Munsell No Panel Pure white 6 4Y 8 9 0 4 Dimension Unit mm in 290 x 946 x 634 11 7 16 x 37 1 4 x 25 290 x 1446 x 634 11 7 16 x 56 15 16 x 25 290 x 1708 x 606 11 7 16 x 67 1 4 x 23 7 8 H x W x D Panel mm in 20 x 1250 x 710 13 16 x 49 1 4 x 28 20 x 1750 x 710 13 16 x 68 15 16 x 28 20 x 2010 x 710 13 16 x 79 3 ...

Page 125: ...w Type 125 VRF Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Series VRF Indoor Units Ventilation Systems Technologies and Functions Remote Controller Hot Water Solution VRF BC Controllers VRF S Series ...

Page 126: ...e main unit and 3 kg for the panel making this unit one of the lightest in the industry The drain can be positioned anywhere up to 600 mm 23 5 8 in from the ceiling surface mm in 198 7 13 16 PMFY VBM 230 9 11 16 max 402 15 7 8 max 600 23 5 8 No access door is required Installing a 1 way airflow type unit in a room creates a more spacious feel that enhances room comfort This overhead format is also...

Page 127: ... 283 304 328 272 307 343 378 External static press Pa 0 Motor Type 1 phase induction motor Output kW 0 028 Air filter PP Honeycomb fabric Refrigerant Gas Flare mm in ø12 7 ø1 2 pipe diameter Liquid Flare mm in ø6 35 ø1 4 Field drain pipe diameter mm in O D 26 1 Sound pressure level dB A 27 30 33 35 32 34 36 37 33 35 37 39 Lo Mid2 Mid1 Hi 2 3 1 Cooling Heating capacity indicates the maximum value a...

Page 128: ...Ceiling Concealed Type 128 ...

Page 129: ...ight 200 mm Duct flange and filter are excluded 3 inlet type Air flow rate 3 levels Drain pump standard Maximum lifting height 700 mm For PEFY P VMA E Air flow rate 3 levels Medium static pressure type PEFY P VMA L E Thin design with a body height of 250 mm all HP models enables installation in a ceiling with small cavity space The position of the inlet can be selected to be at the bottom or rear ...

Page 130: ... rear of the main unit Interlocking using a card key The air conditioner can be switched ON OFF by inserting or removing a card key to prevent forgetting to turn off the air conditioner and save wasteful operation Optional accessory is needed Models are available with the refrigerant drain piping and control box on either the right or left side to flexibly fit rooms that are symmetrically arranged...

Page 131: ...l finish Galvanized Dimension Rear inlet mm in 292 x 640 x 580 11 1 2 x 25 1 4 x 22 7 8 H x W x D Bottom inlet mm in 300 x 640 x 570 11 7 8 x 25 1 4 x 22 1 2 Net weight kg lbs 18 40 Heat exchanger Cross fin Aluminum fin and copper tube FAN Type x Quantity Sirocco fan x 1 Airflow rate m3 min 4 8 5 8 7 9 4 8 5 8 9 3 Lo Mid Hi L s 80 97 132 80 97 155 cfm 170 205 279 170 205 328 External static pressu...

Page 132: ...ear Inlet Bottom Inlet 450 mm 1 677 mm 1 677 mm 1 450 mm 1 200 mm 698 948 1148 mm 1 Duct flange and filter are excluded Wall Ceiling Wall Ceiling Wall Ceiling Top Outlet Bottom Inlet P15 P20 P25 P32 P40 P50 P63 948 698 1148 200 450 1 Height Width Depth mm mm mm P15 Height mm PEFY P VMX L E 1 The thin body allows installation in tight spaces such as above a closet Compact design Three air inlet pos...

Page 133: ...200 2 Power input kW 0 038 0 038 0 054 0 060 0 105 0 121 0 120 2 Current input A 0 42 0 42 0 53 0 70 1 21 1 31 1 42 Heating capacity 3 kW 1 9 2 5 3 2 4 0 5 0 6 3 8 0 Nominal 3 BTU h 6 500 8 500 10 900 13 600 17 100 21 500 27 300 2 Power input kW 0 038 0 038 0 054 0 060 0 105 0 121 0 120 2 Current input A 0 42 0 42 0 53 0 70 1 21 1 31 1 42 External finish Galvanized Galvanized Galvanized Galvanized...

Page 134: ...ws installation in a ceiling with small cavity space Compact design with a height of no more than 200 mm all models and widths of 790 mm P15 P32 External static pressure can be selected from 5 15 35 and 50 Pa set to 15 Pa at the time of factory shipment Demonstrates a maximum external static pressure of 50 Pa despite its compact design Owing to a centrifugal fan and coil low noise operation is rea...

Page 135: ... 150 100 133 167 133 158 183 158 183 217 200 233 275 cfm 176 212 247 194 229 282 194 247 317 212 282 353 282 335 388 335 388 459 424 494 583 External static press Pa 5 15 35 50 Motor Type DC motor Output kW 0 096 Air filter PP Honeycomb fabric washable Refrigerant Gas mm in ø12 7 ø1 2 Brazed ø15 88 ø5 8 Brazed pipe diameter Liquid mm in ø6 35 ø1 4 Brazed ø9 52 ø3 8 Brazed Field drain pipe diameter...

Page 136: ...t design with a height of no more than 250 mm all models Thin body design with a height of no more than 250 mm all models enables the installation in a ceiling with small cavity Height 250 mm all models Built in drain pump PEFY P VMA E Drain pump ensures a lifting height of up to 700 mm Units with an L at the end of the model name are not equipped with a drain pump No drain pump PEFY P VMAL E Unit...

Page 137: ... 94 2 10 External finish Galvanized steel plate Dimension H x W x D mm 250 x 1 100 x 732 250 x 1 100 x 732 250 x 1 100 x 732 250 x 1 400 x 732 250 x 1 400 x 732 250 x 1 600 x 732 in 9 7 8 x 43 5 16 x 28 7 8 9 7 8 x 43 5 16 x 28 7 8 9 7 8 x 43 5 16 x 28 7 8 9 7 8 x 55 1 8 x 28 7 8 9 7 8 x 55 1 8 x 28 7 8 9 7 8 x 63 x 28 7 8 Net weight kg lbs 32 71 31 69 32 71 31 69 32 71 31 69 42 93 41 91 42 93 41 ...

Page 138: ...parts For PEFY P VMA L E Description Model Applicable capacity VMA L Filter box PAC KE91TB E P20 P25 P32 PAC KE92TB E P40 P50 PAC KE93TB E P63 P71 P80 PAC KE94TB E P100 P125 PAC KE95TB E P140 138 SPECIFICATIONS ...

Page 139: ...izontal piping requirements The factory setting of external static pressure is shown without brackets Refer to Fan characteristics curves according to external static pressure in the DATA BOOK for the usable range of airflow rate Drain pump option lifts drain water up to 550 mm 700 mm 550 mm for P40 P140 VMHS 700 mm for P200 P250VMHS models Ceiling concealed type High static pressure type A wide r...

Page 140: ...ght has been reduced offering easier installation The use of a high efficiency DC motor for the drain pump motor in the latest models reduces power consumption by 90 in comparison to conventional models The pump head height of 550 mm provides for greater piping design flexibility The use of a DC motor In the past the only models featuring a DC motor were the P200 8 HP and P250 10 HP Now the P140 6...

Page 141: ...Mid Hi m3 min 10 0 12 0 14 0 10 0 12 0 14 0 13 5 16 0 19 0 15 5 18 0 22 0 18 0 21 5 25 0 L s 167 200 233 167 200 233 225 267 317 258 300 367 300 358 417 cfm 353 424 494 353 424 494 477 565 671 547 636 777 636 759 883 Sound pressure level measured Low Mid High in anechoic room 2 dB A 20 23 27 20 23 27 24 27 32 24 26 30 25 27 30 Air filter Option Synthetic fiber unwoven cloth filter long life filter...

Page 142: ... 32 0 38 0 26 5 32 0 38 0 28 0 34 0 40 0 50 0 61 0 72 0 58 0 71 0 84 0 L s 442 533 633 442 533 633 467 567 667 833 1 017 1 200 967 1 183 1 400 cfm 936 1 130 1 342 936 1 130 1 342 989 1 201 1 412 1 766 2 154 2 542 2 048 2 507 2 966 Sound pressure level measured Low Mid High in anechoic room 2 dB A 27 31 34 27 31 34 27 32 36 36 39 43 39 42 46 Air filter Option Synthetic fiber unwoven cloth filter lo...

Page 143: ...o the room It is not for controlling internal thermal load Ceiling concealed type Fresh air intake type Air conditioner with fresh air intake structure enables intake of outside air Pre treating the intake air contributes to ensure optimized room comfort PEFY P VMHS E F PEFY P VMH E F Technologies and functions P 167 PEFY P200 250VMHS E F Air conditioner with fresh air intake structure enables int...

Page 144: ...e maximum value at operation under the following condition Cooling Indoor 33 CDB 28 CWB Outdoor 33 CDB The set temperature of the remote controller is 18 C 2 The value are measured at the factory setting of airflow mode and external static pressure 3 Heating capacity indicates the maximum value at operation under the following condition Heating Indoor 0 CDB 2 9 CWB Outdoor 0 CDB 2 9 CWB The set te...

Page 145: ...alues are measured at the factory setting of external static pressure The figure of Electrical characteristic indicates at 240V 50Hz 230V 60Hz PEFY P80 140VMH E F type at 50Hz 60Hz PEFY P200 250VMH E F type 3 The factory setting of external static pressure is shown without Refer to Fan characteristics curves according to the external static pressure in DATA BOOK for the usable range of air flow ra...

Page 146: ...MH E F Long life filter PAC KE88LAF P80 PAC KE89LAF P125 P140 PAC KE85LAF P200 P250 P200 P250 Filter box PAC KE80TB F P80 PAC KE140TB F P125 P140 PAC KE250TB F P200 P250 P200 P250 Drain pump PAC KE04DM F P80 P140 P200 P250 PAC DRP10DP E2 P125 PAC KE06DM F P200 P250 146 SPECIFICATIONS ...

Page 147: ...7 VRF Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Series VRF Indoor Units Ventilation Systems Technologies and Functions Remote Controller Hot Water Solution VRF BC Controllers VRF S Series ...

Page 148: ...omatically adjusts the air speed to conditions that match the room environment At the start of heating cool ing operation the airflow is set to high speed to quickly heat cool the room When the room temperature reaches the desired setting the airflow speed is decreased automatically for stable and comfortable heating cooling operation A height of 230 mm for harmony with the interior design Auto va...

Page 149: ...fan x 3 Sirocco fan x 4 Airflow rate 2 m3 min 10 11 12 13 14 15 16 18 21 24 26 28 21 24 27 31 Lo Mid2 Mid1 Hi L s 167 183 200 217 233 250 267 300 350 400 433 467 350 400 450 517 cfm 353 388 424 459 494 530 565 636 742 847 918 989 742 847 953 1 095 External static pressure Pa 0 Motor Type DC motor Output kW 0 090 0 095 0 160 Air filter PP Honeycomb long life Refrigerant pipe diameter Gas Flare mm i...

Page 150: ...Wall Mounted Type 150 ...

Page 151: ...ht lines of the walls floor and ceiling The white body color has been adopted to enhance the beauty and comfort of a room without disturbing its atmosphere Fan speed vane control Airflow control has been improved to achieve horizontal airflow This reduces the cold draft feeling even with a wall mounted model while ensuring optimal air conditioning The VLM model provides 4 fan speeds and an auto mo...

Page 152: ... 2 4 4 4 7 4 0 4 4 4 9 5 4 4 0 4 6 5 4 6 7 4 3 5 4 6 9 8 4 6 3 7 4 8 6 10 0 6 8 8 3 10 2 12 4 Lo Mid2 Mid1 Hi L s 55 58 63 70 67 70 73 78 67 73 82 90 67 77 90 112 72 90 115 140 105 123 143 167 113 138 170 207 cfm 117 124 134 148 141 148 155 166 141 155 173 191 141 162 191 237 152 191 244 297 222 261 304 353 240 293 360 438 External static pressure Pa 0 Motor Type DC motor Output kW 0 030 Air filte...

Page 153: ...4 Compatible Liquid Flare mm in ø9 52 ø3 8 Field drain pipe diameter mm in I D 16 5 8 Sound pressure level dB A 39 45 41 49 Lo Hi 2 3 1 Cooling heating capacity indicates the maximum value at operation under the following condition Cooling Indoor 27 C 81 F DB 19 C 66 F WB Outdoor 35 C 95 F DB Heating Indoor 20 C 68 F DB Outdoor 7 C 45 F DB 6 C 43 F WB 2 Airflow rate Sound pressure level are in low...

Page 154: ...Floor Standing Type 154 ...

Page 155: ...ratures are accomplished through optimum powerful and efficient air distribution through upper and lower air outlets The upper vane angle is remote controllable with 5 air flow direction levels Swing and Auto modes and 4 wind power levels Auto mode By setting the vane angle almost vertical bothersome direct wind can be avoided for increased comfort Sophisticated design This innovative new floor st...

Page 156: ... 2 Airflow rate Lo Mid Hi SHi m3 min 5 9 6 8 7 6 8 7 6 1 7 0 8 0 9 1 6 1 7 0 8 0 9 1 8 0 9 0 9 5 10 7 External static pressure Pa 0 Motor Type DC motor Output kW 0 03 x 2 Air filter PP honeycomb fabric Catechin Filter Refrigerant Gas Flare mm in ø12 7 ø1 2 pipe diameter Liquid Flare mm in ø6 35 ø1 4 Field drain pipe diameter I D 16 5 8 Sound pressure level dB A 27 31 34 37 28 32 35 38 28 32 35 38 ...

Page 157: ...er cooling Dehumidifying Mode to manage moisture build up Compact unit for perimeter air conditioning Floor standing type Exposed type PFFY P VLEM E Technologies and functions P 167 This floor standing type allows efficient air conditioning around the perimeter of a room It adopts a low height design that does not block the daylight from the windows 157 VRF Y Series VRF Lineup VRF R2 Series VRF Zu...

Page 158: ...e FAN Type x Quantity Sirocco fan x 1 Sirocco fan x 2 Airflow rate 2 m3 min 5 5 6 5 7 0 9 0 9 0 11 0 12 0 14 0 12 0 15 5 Lo Hi L s 92 108 117 150 150 183 200 233 200 258 cfm 194 230 247 318 318 388 424 494 424 547 External static pressure Pa 0 Motor Type 1 phase induction motor Output kW 0 015 0 018 0 030 0 035 0 050 Air filter PP Honeycomb fabric washable Refrigerant pipe diameter Gas Flare mm in...

Page 159: ...tronic dry function dehumidify refreshingly Concealed design ensures harmony with any interior The embedded type design makes it possible to install the unit while keeping its beautiful appearance and architectural design Installation image Air outlet Air inlet 220 mm Floor standing type Concealed type Fits neatly and easily installed in perimeter zone PFFY P VLRM E PFFY P VLRMM E Technologies and...

Page 160: ...ger Cross fin Aluminum plate fin and copper tube FAN Type x Quantity Sirocco fan x 1 Sirocco fan x 2 Airflow rate 2 m3 min 5 5 6 5 7 0 9 0 9 0 11 0 12 0 14 0 12 0 15 5 Lo Hi L s 92 108 117 150 150 183 200 233 200 258 cfm 194 230 247 318 318 388 424 494 424 547 External static pressure Pa 0 Motor Type 1 phase induction motor Output kW 0 015 0 018 0 030 0 035 0 050 Air filter PP Honeycomb fabric was...

Page 161: ...0 40 60 Motor Type DC motor Output kW 0 096 Air filter PP Honeycomb fabric washable Refrigerant Gas mm in ø12 7 ø1 2 Brazed ø15 88 ø5 8 Brazed pipe diameter Liquid mm in ø6 35 ø1 4 Brazed ø9 52 ø3 8 Brazed Field drain pipe diameter mm in I D 26 1 Accessory hose O D 27 1 3 32 top end 20 13 16 Sound pressure 20Pa dB A 31 36 40 27 32 37 30 36 40 32 37 41 35 40 44 level Lo Mid Hi 40Pa dB A 34 39 42 30...

Page 162: ... CITY MULTI compressors are inverter driven to precisely match the cooling and heating demands of each building Compressor 100 15 Linear Capacity Control Image Compressor Frequency High Low Heating Cooling Capacity Values vary depending on actual conditions such as ambient temperature Power modules manufactured by Mitsubishi Electric are installed in the compressor which is the core component as w...

Page 163: ...and accelerates the rotation speed of the compressor from 60 rps to 140 rps The number of compressor rotations differs depending on the usage condition Output current is increased For low loads Requires a high output current For high loads The ability to adjust the pulse range and output current to suit a given load increases the operating range of the unit The flat tube heat exchanger delivers hi...

Page 164: ... liquid refrigerant that passes through the outdoor heat source unit heat exchanger flows directly into the indoor unit and the rest passes through linear expansion valve LEV C to lower both the temperature and pressure The heat is exchanged between the low temperature low pressure liquid refrigerant that passes through LEV C and the moderate temperature liquid refrigerant from the outdoor heat so...

Page 165: ...s improved In addition the drop in heat exchanger capacity for per path prevents the refrigerant stagnation and improves the condensing performance of the heat exchanger during cooling During heating a parallel flow path flow refrigerant simultaneously through all heat exchangers split into three is used By flowing the refrigerant to all paths at the heat exchanger inlets by increasing the number ...

Page 166: ...mp Auto mode Dual set point 1 Energy efficiency control Evaporating temperature control Fixed temperature control 6 C 9 C 14 C 6 C 9 C 14 C 6 C 9 C 14 C 6 C 9 C 14 C 4 C 9 C 14 C 6 C 9 C 14 C Evaporating temperature control Automatic control shifting 4 patterns 4 patterns 4 patterns 4 patterns 4 patterns 4 patterns High sensible heat operation during cooling Demand control 2 12 steps 12 steps 8 step...

Page 167: ... 550 700 Filter cleaning sign 8 1 Requires a panel with the 3D i see Sensor sold separately An MA remote controller PAR 40MAA is required to set the 3D i see Sensor Some settings can be made using the PAR SL100A E 2 To set the fan speed to Auto using the wireless remote controller certain controller settings need to be made beforehand Refer to the installation manual of the wireless remote control...

Page 168: ...PKFY P VLM E PKFY LM PKFY P VKM E PKFY KM PFFY P VKM E2 PFFY KM PFFY P VLEM E PFFY LEM PFFY P VLRM M E PFFY LRM LEM VLRM VLRMM 3 levels 3 levels 3 1 level 4 levels 4 levels 2 levels 4 levels 2 levels VLRM 2 levels VLRMM 3 levels 5 levels Auto 5 levels Auto 4 levels Auto 4 levels Auto P20 P140 4 levels P200 P250 5 levels 4 levels P80 P140 3 levels P200 P250 2 levels VLRM VLRMM 3 levels P40 P140 550...

Page 169: ... frequency and the number of rotations of the outdoor fan for the air cooled outdoor unit The user can select a preferred level Cooling heating capacity drops during low noise mode operation 10 20 30 40 50 60 70 80 90 63 125 250 500 1k 2k 4k 8k NC 40 NC 30 NC 20 NC 60 NC 50 NC 70 Octave band central frequency Hz Octave band sound level dB Approximate minimum audible limit on continuous noise Stand...

Page 170: ...ntial between the room temperature and the set temperature the operation of all indoor units in the system is switched from heating to cooling It is possible to automatically switch between cooling and heating without setting the dip switches on outdoor units Users can select from the two types of switching patterns shown below 1 Averaging Operation mode cooling or heating is determined and switch...

Page 171: ... operate in the comfortable temperature band defined by two temperature points where the thermostat is off This cuts down on unnecessary operation of the air conditioning system This function is supported only when all the indoor units remote controllers and system controllers that are connected to a given group are compatible with the function Room temperature stays within the comfortable tempera...

Page 172: ...porating temperature as follows The evaporating temperature is controlled to be constant regardless of the ΔT It is set to a value that is higher than the normal evaporating temperature The evaporating temperature is controlled in accordance with the ΔT It can be selected from 4 control patterns The availability of and varies depending on the model Refer to the function table Changing the evaporat...

Page 173: ...Humidity sensor locally procured Humidity information is sent to the control board The control board judges the humidity information and sends a HIGH LOW signal to the outdoor unit through CN3S The outdoor unit shifts the evaporating temperature depending on the information from the control board 1 2 In high sensible heat operation mode air conditioners consume less energy thereby realizing cost s...

Page 174: ... the outdoor unit is divided into two parts Even when defrosting is necessary one part of the heat exchanger continues the heating operation Image of continuous heating operation combination With the combination model units perform defrosting and heating alternately While one unit is performing defrosting the other continues heating Conventional heating operation Continuous heating operation Conti...

Page 175: ... 80 Pa local setting Example of flow analysis R2 Series EP R2 Series P Y Series EP Y Series P R2 Series EP R2 Series P Y Series EP Y Series P These images show the High efficiency R2 type Models for use in outside temperatures of up to 52 C If the passage of air is blocked in a built up area the high temperature air discharged from the outdoor units may linger around the units When the outdoor uni...

Page 176: ...to USB2 0 can be used Operation data was retrieved from conventional models using the maintenance tool On the latest model the data can be retrieved quickly via USB 1 It is unnecessary to carry the personal computer in which the maintenance tool has been installed reducing field operation time and improving convenience Software can be rewritten via USB Maintenance data retrieval via USB Pump down ...

Page 177: ...ng a comfortable effective temperature by automatically switching between ventilation and cooling When the pre set temperature is reached the air conditioner switches to swing fan operation to maintain the effective temperature This clever function contributes to keeping a comfortable coolness When heating The air conditioner automatically switches between circulation and heating Wasted heat that ...

Page 178: ...Standby or Defrost is displayed When the room temperature is higher than the set temperature during the heating mode Immediately after heating operation during standby for switching the operation mode 1 On PAR FL32MA Up and down Fan speed Remote controller display Auto Low 4 levels 3 levels 2 levels Middle The unit operates at high speed at startup to rapidly heat or cool the space then automatica...

Page 179: ... FM PEFY MHS PEFY MA PEFY MS PEFY MX PEFY MR PLFY EM PKFY KM PFFY CM PFFY LRM PFFY LEM PFFY KM PKFY LM PCFY KM PMFY BM PLFY LMD PLFY FM PEFY MHS PEFY MA PEFY MS PEFY MX PEFY MR PLFY EM High efficiency filter The high efficiency filter has a much finer mesh compared to standard filters and is capable of capturing minute particulates floating in the air that were not previously caught External stati...

Page 180: ...et with the DipSW on the indoor unit Contact your local distributor for details Built in drain pump optional for some models efficiently pumps out water Filter sign on the controller display Filter sign 1 VMX only 2 Optional for PEFY P VMS1L E and PEFY W VMS A 3 VMA only PKFY KM PFFY CM PFFY LRM PFFY LEM PFFY KM PKFY LM PCFY KM PMFY BM PLFY LMD PLFY FM PEFY MH F PEFY MHS F PEFY MHS PEFY MA PEFY MS...

Page 181: ...Ventilation Systems 181 ...

Page 182: ...ustment Language selection Initializing Filter cleaning sign Lossnay core cleaning sign Error indication Error history PZ 61DR E LGH RVX RVXT 4 fan speeds Energy recovery Bypass Auto Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 8 languages Yes Yes Yes Yes Yes 120 120 19 Unit mm Lossnay lineup Remote controller LGH RVX Series A commercially oriented system that can be used to deliver high perfor...

Page 183: ... intake OA Return air RA Supply air SA Lossnay is a total heat exchange ventilation system that uses paper characteristics to perform temperature sensible heat and humidity latent heat exchange EA OA SA RA The concept of sensible heat and latent heat exchange using a Lossnay core Indoor Air Quality Inside a Building is Optimized Through Temperature and Humidity Exchange by Lossnay What can be Impr...

Page 184: ...ning when the load is heavy t Comparison between latest and conventional power consumption Latest model Fan speed 4 at 230V 50Hz Conventional model Extra high at 220V 50Hz Fan speed 1 Fan speed 2 Fan speed 3 Fan speed 4 Airflow Static pressure Offers a wide range of airflow variations from small to large volumes 25 50 75 100 Height 808mm Height 500mm OA outdoor air Fresh outdoor air is drawn in by...

Page 185: ...2 0 SP2 0 51 75 500 139 43 24 0 SP1 0 19 23 250 69 11 18 0 SP4 2 50 420 1000 278 170 80 0 72 5 71 0 37 0 SP3 1 20 200 750 208 96 83 0 74 0 73 0 31 0 SP2 0 50 75 500 139 43 86 5 78 0 77 0 23 0 SP1 0 17 21 250 69 11 89 5 87 0 85 5 18 0 54 LGH 250RVXT E 220 240V 50Hz 220V 60Hz Heat recovery mode Bypass mode SP4 6 90 1298 2500 694 175 100 44 0 SP3 3 10 587 1875 521 98 56 38 5 SP2 1 30 212 1250 347 44 ...

Page 186: ...150 250 200 400 350 300 60 70 80 90 0 50 100 150 300 350 200 250 0 500 1500 1000 SP1 SP2 SP3 SP4 250mm dia straight pipe length Exchange efficiency Static pressure Pa Airflow m3 h L s 20 30 40 50 Temperature exchange efficiency Enthalpy exchange efficiency Heating Enthalpy exchange efficiency Cooling 0 100 200 300 400 500 600 700 800 60 70 80 90 0 50 100 150 300 350 200 250 0 1000 500 1500 2000 30...

Page 187: ...LGH 200RVXT E LGH 250RVXT E 4 The classification in EN779 2002 is G3 Filter Lossnay Filter material Classification Model name Included piece set Applicable model Required filter pieces ISO 16890 EN779 2012 Synthetic fiber ePM10 75 M6 PZ 15RFM E 1 LGH 15RVX E 1 PZ 25RFM E 2 LGH 25RVX E 2 PZ 35RFM E 2 LGH 35RVX E 2 PZ 50RFM E 2 LGH 50RVX E GUF 50RD4 2 PZ 65RFM E 2 LGH 65RVX E 2 PZ 80RFM E 2 LGH 80RV...

Page 188: ... 25RFP2 E 2 LGH 25RVX E 2 PZ 35RFP2 E 2 LGH 35RVX E 2 PZ 50RFP2 E 2 LGH 50RVX E GUF 50RD4 2 PZ 65RFP2 E 2 LGH 65RVX E 2 PZ 80RFP2 E 2 LGH 80RVX E 2 LGH 150RVX E 4 PZ 100RFP2 E 2 LGH 100RVX E GUF 100RD4 2 LGH 200RVX E 4 Filter Lossnay Filter material Classification Model name Included piece set Applicable model Required filter pieces ISO 16890 EN779 2012 Non woven fabrics ePM10 75 M6 PZ M6RTFM E 3 ...

Page 189: ... 0 11 2 11 2 14 0 14 0 16 0 16 0 22 4 22 4 28 0 36 0 45 0 45 0 56 0 ALLOWED HEAT EXCHANGER VOLUME CM3 1500 2850 1900 3550 2150 4050 3000 5700 3750 7100 6000 11400 7500 14200 REFERENCE AIR FLOW RATE M3 H 3 2000 2500 3000 4000 5000 8000 10000 STANDARD EVAPORATOR PATH NUMBER 1 4 5 4 5 5 6 6 10 8 10 16 20 16 20 DIMENSIONS MM INC MOUNTINGS WIDTH DEPTH HEIGHT 328 104 122 378 420 328 104 122 378 420 328 ...

Page 190: ...Remote Controllers 190 ...

Page 191: ...conditioning system is not properly controlled it will not run as efficiently as it should For every degree that the system deviates from the required temperature energy costs can rise by up to 5 Specify one of the many control options from Mitsubishi Electric to ensure air conditioning works as intended while giving the optimum amount of control The Simpler The Better With the array of comprehens...

Page 192: ...he efficiency and quality of air conditioning contributing to energy savings and reduction in running cost A wide variety of MELANS products are available to meet all requirements from the smallest and simplest to the largest and most complex Mitsubishi Electric offers a wide lineup of individual remote controllers various centralized controllers and centralized integrated software as well as BMS ...

Page 193: ... N 1 24 x 7 24 N N N 2 2 2 2 2 N 2 4 N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N 3 N N N N N N N N N 10 9 Each group Batched Each group Block for CITY MULTI Indoor unit not for all Mr SLIM AE 200E AE 50E EW 50E license registration possible Block N Not Available Not Used Batched only Batched handling for maintenance PAR 40MAA 1 16 4 1 N N N 5 N 8 x 7 1 N N N N N N N N N N N N N N...

Page 194: ...aying only ON OFF set temp fan speed Hotel setting A logo image can be displayed on the initial screen For PAR CT01MAA SB and PAR CT01MAA PB models only Logo image customization 180 color patterns can be selected for the display s control parameters or background Multiple color patterns Visible big size icons on the full color touch panel display Full color touch panel backlit display English Fren...

Page 195: ...fter a certain period of operation Operation time can be set to a value from 30 to 240 minutes in 10 minute increments Description Operations Display Switches between louver ON OFF Changes airflow direction Available airflow directions vary depending on the model Temperature range restriction The room temperature range for each operation mode can be restricted Operation lock The following operatio...

Page 196: ...off the unit after a certain period of operation Operation time can be set to a value from 30 to 240 minutes in 10 minute increments Description Operations Display Switches between louver ON OFF Changes airflow direction Available airflow directions vary depending on the model Temperature range restriction Daylight saving time The room temperature range for each operation mode can be restricted Op...

Page 197: ...fter a certain period of operation Operation time can be set to a value from 30 to 240 in 10 minute increments Allows disallows local operation The following operation can be prohibited by applying certain settings on the centralized controller ON OFF operation mode setting temperature setting fan speed air direction and filter sign reset While an operation is prohibited the operation icon lights ...

Page 198: ... W x 4 3 4 H x 19 32 D in Item Operation mode switching Temperature setting ON OFF Fan speed setting Select from COOL DRY FAN AUTO and HEAT AUTO mode is settable only when those functions are available on the indoor unit Ventilation equipment When the CITY MULTI indoor unit is connected interlocked setting of the CITY MULTI Lossnay unit is possible When the Mr SLIM indoor unit A control is connect...

Page 199: ...32 H x 7 8 D in Compatibility table VRF PMFY P VBM PLFY P VLMD PEFY P VMR E VMH S PFFY P VLEM VKM VLRM VLRMM PEFY P VMS1 L PEFY P VMA 3 L PAR FL32MA Receiver Transmitter PAR FA32MA PCFY P VKM PKFY P VKM PKFY P VLM PLFY P VEM PLFY P VFM E1 PAR FL32MA PAR SL100A E Receiver Transmitter PAR FA32MA PAR SL94B E PAR SE9FA E PAR SF9FA E Built in Built in Functions PAR SE9FA E 4 way cassette signal receive...

Page 200: ...e set Depending on the room temperature the indoor unit will automatically operate in either the Cool or Heat mode and keep the room temperature within the preset range Contact your Mitsubishi Electric sales office for details Preset temp COOL Preset temp HEAT Room temperature HEAT HEAT COOL COOL The room temperature changes in accordance with changes in the outside temperature Dual Set Point Dual...

Page 201: ...controller prohibit permit One input can be selected from those above An external input output adapter PAC YT51HAA sold separately is required Relays and DC power supply or other devices must be prepared at the site External output Error output operation output ON OFF and error normal are output with the level signal An external input output adapter PAC YT51HAA sold separately is required Relays a...

Page 202: ...med by comparing power consumption with the previous year and with the electrical power target Floor layout is displayed on the 10 4 inch LCD touch panel for easy management of air conditioning equip ment An optimal system can be easily and flexibly estab lished according to the size of the facility Up to 50 indoor units can be managed Centralized control of up to 200 indoor units can be performed...

Page 203: ... of the interlocked indoor unit starts External input output By using optional external input output adapter PAC YG10HA E you can set and monitor the following Input By level signal Batch ON OFF Batch emergency stop By pulse signal Batch ON OFF Enable disable local remote controller Output ON OFF Error Normal Energy Management 1 Bar Graph Indoor unit Electric Energy FAN operation time Thermo ON ti...

Page 204: ...LC in the U S and other countries Edge is a trademark or registered trademark of Microsoft Corporation in the U S and other countries Windows is a trademark or registered trademark of Microsoft Corporation in the U S and other countries Safari is a trademark or registered trademark of Apple Inc in the U S Company names and product names in this brochure may be trademarks or registered trademarks o...

Page 205: ... YG10HA sold separately Web browser Monitor operation failure filter sign monitoring schedule setting interlocked control setting option energy saving control setting option energy saving peak cut setting option set temperature range restrictions other Connectable location Centralized system transmission line Connectable Recommended Indoor and outdoor transmission line Connectable External input t...

Page 206: ...ontroller System example Function Each group Batch only Not available X X X PAC YT40ANRA Control of up to 16 groups 50 indoor units Up to 16 groups 50 units can be operated with a single ON OFF remote controller A general purpose interface is also available for turning ON OFF general devices Just press a switch to start All units can be started and stopped by pressing the main switch and each unit...

Page 207: ...of items 1 3 above 5 Monitors the input output status of ALPHA2 via a remote controller or centralized controller Compatible controllers Remote controller PAR U02MEDA Centralized controller AE 200E AE 50E EW 50E Refer to the ALPHA2 manual for detailed information about ALPHA2 Use of the AHC adapter requires either a remote controller or centralized controller System structure Dimensions 116 W x 90...

Page 208: ...roller enables energy saving control Registration of the Energy management license pack is required Energy saving is achieved by controlling the capacity of the outdoor unit The charges for each tenant are calculated and output as a CSV file The PI controller counts pulses from a power meter gas meter water meter and calorimeter By combining the AE 200E AE 50E EW 50E the charges for each unit can ...

Page 209: ...tivated deactivated M NET LAN M NET LAN Temperature Pt100 4 to 20 mA DC 1 to 5 VDC 0 to 10 VDC Humidity 4 to 20 mA DC 1 to 5 VDC 0 to 10 VDC Icon display Lights ON OFF Error Schedule set AE 200E AE 200E System structure System structure Monitors the values measured by the temperature humidity sensor connected to the AI controller Measurement data trends can be displayed on a web browser An alarm c...

Page 210: ...LONWORKS Protocol converter between LONWORKS and M NET FUNCTION CONTENT ON OFF Cool Dry Heat Auto Fan Changes the set temperature Set temperature range varies depending on the indoor unit model High Mid 1 Mid 2 Low ON OFF Mode Set point ON OFF Cool Dry Heat Auto Fan Changes the set temperature Set temperature range varies depending on the indoor unit model High Mid 1 Mid 2 Low ON OFF Mode Set poin...

Page 211: ...Water Mode Apportioned Electric Energy PI controller Electric Energy Apportionment Parameter Night Purge State Thermo On Off State External Heat Source State Trend Log Monitoring ON OFF Cool Dry Heat Auto Fan Low Mid2 Mid1 High Auto Horizontal Downblow 60 80 100 Swing Changes the set temperature Set temperature range varies depending on the indoor unit model ON OFF ON OFF Mode Filter sign reset Se...

Page 212: ... Key DI Digital Input DO Digital Output AI Analogue Input AO Analogue Output Description Connect to Max Number of Units Power Supply Dimensions mm WxDxH Network BEMS Compatibility Air to Air Splits Modbus BACnet Interface Air Water to Water Modbus Interface Indoor 1 70 x 19 x 50 Modbus BACnet RS485 Compatibility M Series Mr Slim Ecodan Lossnay City Multi indoors CAHV CRHV QAHV Cylon Satchwell Cres...

Page 213: ...C YG82TB PAC YG84UTB PAC YG86TK PAC YG72CWL Mounting attachment for AE 200E wall mount installations Electrical box for AE 200E wall embed installations Mounting kit for AE 200E wall mount installations Surface cover with USB port for AE 200E Model Description Model Description Optional parts For CONTROL 213 VRF Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Serie...

Page 214: ...Hot Water Solution Air to Water Series 214 ...

Page 215: ...ring efficient heat recovery operation Air to Water ATW Series offers a choice between two types of units a booster unit and a HEX heat exchanger unit The booster unit offers hot water to a maximum of 70 C and the HEX unit offers 40 C for heating and down to 8 C for cooling Applying heat pump and heat recovery technology to provide hot water the units are suitable for residences office buildings r...

Page 216: ...ly Water supply CITY MULTI Series R2 WR2 BC controller COMP 1 3 2 High pressure gas refrigerant High pressure 2 phase refrigerant High pressure liquid refrigerant Low pressure gas refrigerant Red Orange Green Blue Connectable to CITY MULTI R2 WR2 Series Applications Sanitary water shower etc Operation Up to 70 C PWFY P100VM E BU ATW Unit Booster Unit The booster unit is connected to a BC controlle...

Page 217: ...d to the HEX unit and returns to the unit as high pressure liquid refrigerant Water entering the HEX unit exchanges heat with the R410A refrigerant and circulates to heat the water inside the tank Refrigerant flow Water supply 1 2 From the BC controller high pressure R410A liquid refrigerant is delivered to the HEX unit and returns to the unit as low pressure gas refrigerant Water entering the HEX...

Page 218: ... R410A liquid refrigerant is delivered to the HEX unit and returns to the unit as low pressure gas refrigerant Water entering the HEX unit exchanges heat with the R410A refrigerant and circulates to cool the water inside the tank Water supply Cold water supply 1 2 HEX unit Water supply Hot water supply 1 2 Indoor unit CITY MULTI Series Y WY HEX unit Indoor unit CITY MULTI Series Y WY High pressure...

Page 219: ...ving environment is created Unit information Outdoor unit Air cooled R2 Series 5 BC controller 5 ATW unit Booster unit 3 Indoor unit Floor mounted concealed type 18 Control AG 150A 1 ATW controller 3 ME remote controller 27 Power supply unit 1 Other OA processing unit 9 CASE STUDY CMB M104 1016V J1 CMB M108 1016V JA1 CMB P1016V KA1 CMB M104 108V KB1 WCB CMB M P104 1016V J 1 CMB M P108 1016V JA 1 C...

Page 220: ...l kitchens HEALTH CLUBS Reason for ATW Gym space requires year round cooling Swimming pools and shower rooms require hot water Reason for ATW Hot water is required throughout the year for the shower and kitchen Can be used for under floor heating in winter and cooling in summer The application examples here indicate why ATW systems are chosen and how the great potential offered by using ATW system...

Page 221: ... legs 17 3 4 11 13 16 59 131 Inverter rotary hermetic compressor Inverter 1 0 NEO22 0 6 2 15 High pressure sensor High pressure switch at 3 60 MPa 601 psi Over heat protection Over current protection Discharge thermo protection Over current protection R134a 1 1kg 0 50lb 1 430 1 6 LEV 4 15 3 60 1 00 WKB94L762 WKE94C229 Installation Manual Instruction Book Strainer Heat insulation material Wire x 1 ...

Page 222: ... Strainer Heat insulation material Expansion joint Flow switch 1 set Buffer material Solenoid valve kit PAC SV01PW E Details on foundation work duct work insulation work electrical wiring power source switch and other items shall be referred to the Installation Manual Note 1Nominal heating conditions PWFY conditions are indicated in the parentheses Y R2 Series Outdoor Temp 7 CDB 6 CWB 45 FDB 43 FW...

Page 223: ...F Y Series VRF Lineup VRF R2 Series VRF Zubadan VRF WY Series VRF WR2 Series VRF S Series VRF Indoor Units Ventilation Systems Technologies and Functions Remote Controller Hot Water Solution VRF BC Controllers VRF S Series ...

Page 224: ...ti freeze Cooling Available operation modes vary depending on the unit to be connected Switching limit setting can be made via a remote controller Temperature can be set within the ranges below in increments of 1 C or 1 F Booster unit Water HEX unit Heating 30 C 50 C 87 F 122 F Heating 30 C 45 C 87 F 113 F Heating ECO Invalid Heating ECO Invalid Hot Water 30 C 70 C 87 F 158 F Hot Wate Invalid Anti...

Page 225: ...nd collective ON OFF lamp will light up Switches between Hot Water Heating Heating ECO Anti freeze Cooling Available operation modes vary depending on the unit to be connected Temperature can be set within the ranges below in increments of 1 C or 1 F Booster unit Water HEX unit Heating 30 C 50 C 87 F 122 F Heating 30 C 45 C 87 F 113 F Heating ECO 30 C 45 C 87 F 113 F Heating ECO 30 C 45 C 87 F 113...

Page 226: ...ves helps to increase the heat conductive area allowing for better heat transfer and an impressive COP of 3 88 The continuous spiral groove design accelerates the turbulence effect of water and helps to reduce pressure loss within the heat exchanger enhancing efficiency Equipped with the latest inverter scroll compressor QAHV offers unparalleled efficiency when compared to fixed speed systems Supe...

Page 227: ...HEX Refrigerant HEX LEV Air Refrigerant HEX Highly efficient inverter driven CO2 scroll compressor Oil HEX Water Inlet Flash Injection Circuit Capacity KW Outdoor Temp ºCDB 30 25 10 3 0 30 50 40 20 15 Full heating capacity even at 3 C Operable as low as 25 C 1 QAHV 2 Remote Controller optional Hermetic Type Storage Tank R e p r e s e n t a t i v e Water Temp Sensor optional Inlet Water Mains Water...

Page 228: ...ty 1 kW 40 Btu h 136480 Power Input kW 10 31 Current Input A 17 8 16 9 16 3 COP kW kW 3 88 Capacity 2 kW 40 Btu h 136480 Power Input kW 10 97 Current Input A 20 0 19 0 18 3 COP kW kW 3 65 Capacity 3 kW 40 Btu h 136480 Power Input kW 11 6 Current Input A 20 4 19 4 18 7 COP kW kW 3 44 Maximum Current Input 4 A 28 8 27 4 26 4 Allowable External Pump Head 77kPa Temperature Range Outlet Water Temp 55 9...

Page 229: ...m outdoor air Heat Heat Heat Heat Tank Heat Pump System Air Source Heat Pump Heat Heat Heat Input energy For hot water supply For floor heating Output energy Heat from outdoor air Heat Heat Heat Heat 1 2 CAHV P500YB HPB 229 HOT WATER HEAT PUMPS ...

Page 230: ... 6ºC WB Outlet water temp 35ºC Flash Injection Circuit The hot water heat pump ensures an exceptionally high level of reliability through a backup function If either of the compressors malfunctions the other compressor maintains operation to avoid a complete stop of the system A rotation function is also available When two or more units are in the system the unit runs alternately ensuring an optim...

Page 231: ...m the ground Heat Heat Heat Heat Tank Heat Heat Heat Input energy Output energy Heat from ground source Heat Heat Heat Heat 1 2 Input energy Rock Rock Surface soil Surface soil Ground water Ground water River Lake River Lake Heat Heat Heat CRHV P600YA HPB 231 HOT WATER HEAT PUMPS ...

Page 232: ...nt R410A High performance even at low water temp Built in inverter driven scroll compressor SCOP 4 33 Brine outlet temp 3ºC Outlet water temp 35ºC Flash Injection Circuit Flash Injection Circuit The hot water heat pump ensures an exceptionally high level of reliability through a backup function If either of the compressors malfunctions the other compressor maintains operation to avoid a complete s...

Page 233: ...pe External finish External dimension H W D Net weight Accessories Design Pressure Drawing Heat exchanger Compressor FAN HIC circuit HIC Heat inter Changer Protection Defrosting method Control Type GWP 6 Original charged 1 Under Normal heating conditions at outdoor temp 7ºC DB 6ºC WB 44 6 F DB 42 8 F WB outlet water temp 45ºC 113 F inlet water temp 40ºC 104 F 2 Under Heating conditions at outdoor t...

Page 234: ...emp range Circulating water volume range Sound pressure level measured in anechoic room at 1m 3 Sound power level measured in anechoic room 3 Installation location 5 Diameter of water pipe hot water side Diameter of water pipe heat source side External finish External dimension H W D Net weight Design Pressure Drawing Heat exchanger Compressor Protection Control Type GWP 8 Original charged 1 Under ...

Page 235: ... and stops the operation of a group of units Switches between Hot Water Heating Heating ECO Anti freeze Available operation modes vary depending on the unit to be connected Switching limit setting can be made via a remote controller Temperature can be set within the ranges below in increments of 1 C or 1 F Hot Water 30 C 65 C Heating 30 C 45 C Heating ECO 30 C 45 C Anti freeze 30 C The settable ra...

Page 236: ...d earthquakes to prevent the unit from being damaged toppling over or falling 1 3 Backup system In regions in which the malfunctioning of the air conditioner may have a critical effect it is recommended to have two or more systems made up of single outdoor heat source units and multiple indoor units 1 4 Unit characteristics The heat pump efficiency of the outdoor unit depends on the outdoor temper...

Page 237: ...red on the ground wire may not be accurate because the leakage current from other systems may be included in the measurement value Do not install a phase advancing capacitor on a unit connected to the same power system as an inverter type unit and its related equipment If a large current flows due to the malfunctioning of the product or faulty wiring both the earth leakage breaker on the product s...

Page 238: ...areas where the air conditioning load is large such as computer rooms Be sure to use a regular filter If an irregular filter is installed the unit may not operate properly and operating noise may increase The room temperature may increase above the preset temperature in environments in which the heating or air conditioning load is small 2 3 Unit installation The insulation for the gas pipe between...

Page 239: ...R E L R PEFY P VMX L E 1 PEFY P VMS1 L E PEFY P VMHS E PEFY P VMHS E F PEFY P VMH E F PEFY WP VMS1 E PEFY W VMS A 1 5m Measurement location Aux duct 1m 1 5m Measurement location 2m PEFY P VMA L E PEFY WP VMA E PEFY W VMA L A PEFY W VMA2 A 2m 1m Aux duct 1 5m Measurement location Measurement location Aux duct 2m 2m 1 5m PCFY P VKM E PKFY P VLM E PKFY P VKM E PKFY WL VLM E PKFY WL VKM E 1m Measureme...

Page 240: ...ring Thermo OFF operation which may cause dew condensation on the grilles and ducts Ensure that the grilles ducts and rooms are properly insulated to prevent dew condensation An air filter must be installed in the air intake side The filter should be attached where easy maintenance is possible if using locally procured filters For PEFY P VMH E F Outside air temperature ranges for the operation mus...

Page 241: ...ase of the units condensation may collect and drip from outdoor units Provide water proofing protection to the floor when installing the unit on the rooftop In regions where snowfall can be expected install the unit so that the outlet faces away from the direction of the wind and install a snow guard to protect the unit from snow Install the unit on a base approximately 50 cm higher than the expec...

Page 242: ...tal area 5 Repair all noticeable scratches after installation and during maintenance 6 Periodically check the unit and apply an anti rust agent and replace corroded parts as necessary 4 2 Circulating water Regularly check the quality of the water in the heat source unit following the guidelines published by JRAIA JRA GL02 1994 A cooling tower and heat source water circuit should be a closed circui...

Page 243: ...ement location PUHY E P Y S NW A BS PURY E P Y S NW A BS PUHY E P200 250 300YNW A1 BS PURY E P200 250 300YNW A1 BS PUHY E P350 400 450YNW A1 BS PURY E P350 400 450YNW A1 BS Measurement location 1m 1m Measurement location 1m 1m PUHY E P500YNW A1 BS PURY E P500YNW A1 BS Measurement location 1m 1m See the DATA BOOK for information on the combination models PQHY P Y S LM A1 PQRY P Y S LM A1 PQHY P200 ...

Page 244: ...S PUMY P VKM4 5 BS PUMY P YKMD A BS PUMY SP80 112 125 140VKMD A BS PUMY SP80 112 125 140YKMD A BS PUMY P112 125 140VKM5 YKM4 BS PUMY P200YKMD A BS 1 5m 1m Microphone Unit Ground 1 5m 1m Microphone Unit Ground 244 Installation Information ...

Page 245: ...t would put people s lives at risk Employ any methods or circuits that allow ON OFF operation using an external switch in case of failure 5 2 Installation environment Surge protection may be required for the transmission line in areas where lightning strikes occur frequently The receiver for a wireless remote controller may not work properly due to the effect of general lighting Leave a space of a...

Page 246: ... Electric board 25 000 hours Heat exchanger 5 years Major components Checking cycle Maintenance cycle Expansion valve 20 000 hours Valve 20 000 hours solenoid valve four way valve 1 year Sensor 5 years thermistor pressure sensor Drain pan 8 years Major components Checking cycle Replacement cycle Long life filter 5 years High performance filter 1 year Fan belt 1 year 5 000 hours Smoothing capacitor...

Page 247: ...Acrylics nitril styrene resin Motor Frame Spcc Zinc plating filming 8μm or more Shaft S35C Rust prevention coloured coating Motor support Galvanized sheet No treatment Polyester resin coating 70μm or more 70μm or more Heat exchanger Aluminum plate Cellulose series and ure thane series resin coating 1μm or more Only fin Cellulose series and ure thane series resin coating 3μm or more Electrical part...

Page 248: ...subishi Electric Heat Pumps please visit our website or call our Customer Service Team Black Diamond Technologies and Mitsubishi Electric an exclusive partnership since 1981 The Mitsubishi Electric Product Range has been exclusively distributed by 100 locally Owned and Operated Black Diamond Technologies Limited for over 39 years in New Zealand The combination of an internationally trusted brand w...

Reviews: