Air-conditioner Control System

Touch Controller  TC-24A

 Initial Setting Manual

For distribution to dealers and contractors only

This  Initial  Setting  Manual  contains  information  about  the  settings  to  be  made  at  the  time  of  installation.  Please  read  the 
instructions  carefully  and  make  the  settings  accordingly.  Refer  to  the  Installation  Manual  for  how  to  install  the  TC-24A  Touch 
Controller, and refer to the air conditioning unit installation manuals for how to connect the controller cable to the air cond itioning 
units,  or  how  to  install  the  air  conditioning  units.  Please  remember  to  give  all  manuals  to  the  end  users  after  installation  is 
complete.

1

TC-24A Touch Controller 

Function

Sets the M-NET address for the TC-24A. 

Selects the type of controllers to prohibit access* from (remote controllers only 

or both remote controllers and system controllers).

 * Access to ON/OFF, Mode, Set Temp, and Filter Reset.

Selects the external input mode.

Displays or suppresses the Filter sign on the HOME screen. 

Includes or excludes Dry mode as an option for the operation mode. 

Selects the settable temperature range:

Standard: 67°F(19°C) to 83°F(28°C); Low: 46°F(8°C) to 87°F(30°C); 

Manual: Settable to any arbitrary range between 46°F(8°C) and 87°F(30°C).

Sends or does not send the clock synchronization signal once a day to the 

controllers and units. 

Makes the group settings for the indoor units, LOSSNAY units, DIDO 

controllers (PAC-YG66DCA), remote controllers, and sub-system controllers. 

Enters the interlock settings between indoor and LOSSNAY units.

Deletes all group and interlock settings collectively. 

Displays the information about the indoor units connected to each outdoor unit. 

Stores the latest errors. (up to 50)

Updates software. 

Runs a test on the connected air conditioning units.

Page

4

4

4

4

4

4

5

5

6

6

7

8

8

7

HOLD button with LED

SETBACK button with LED

Touch panel

Collective ON/OFF
button with LED

Power LED

Screen

Initial Settings

Basic System

Initial Settings

Groups

Maintenance

Test run

Setting

M-NET address

Remote controller

access

External input mode

Filter sign

Dry mode

Set temperature range

(Schedule)

Time notification

Groups

Interlocked operation

Batch deletion

System view 

Malfunction log

Software update

Test run

List of functions available under the “Service menu”

2

2 TC-24A Screen Configurations

(1) Screen sequence and Service menu configuration

*1  A password is required to access the Service menu.

 

•  The initial Service password is “9999.” Change the password as necessary to prevent unauthorized access. 

 

•  Make sure the password is available to the maintenance and other necessary personnel.

 

•  The password can be set to an arbitrary number between four and eight digits. 

 

•  If you forget your password, log in with the master password.

 

  Master password: 105638

 

•  The same master password is used to log in to specific screens under the “Main Menu” and the “Service Menu.”

Touch [

   ].

Touch [

Touch [

].

Touch [

Touch [

 ].

Touch [

 Touch [

 ].

 Touch [

].

 Touch [

].

Maintenance

Touch [

].

Touch [

].

Touch [

].

System view

Malfunction log

Software update

Test run

Groups

Interlocked LOSSNAY

Delete All

HOME screen

Service Menu screen

Touch [

].

Touch [

].

Initial settings/

Basic system

Initial settings/

Groups

Touch [

].

Main Menu screen

GRID (zoom-out) view

GRID (zoom-in) view

LIST view

GROUP view

Password Change screen

Icon

Button name

Main Menu

Service Menu

Password Change

Back

HOME

Cancel

Login

OK

Initial Settings/Basic system

Initial Settings/Groups

Maintenance

Test run

Groups

Interlocked LOSSNAY

Delete All

System view

Malfunction Log

Software Update

Login Page screen *1

Service Menu

*Touch [

] on each screen to return to a previous screen. 

Touch [

].

Touch [

].

Touch [

].

Touch [

].

 ] or [ 

 ].

].

].

 Touch [ 

 ].

3

3 Initial Settings

[Notes on using the TC-24A with the AG-150A controllers*]

In addition to making the group and interlock settings on the TC-24A, the same setting information must be entered on the AG-150A 

controllers. Also, enter the M-NET address for the TC-24A in the System Controller field on the Group Setting screen. Register the 

M-NET address of the AG-150A on the TC-24A's Group Setting screen.

When combining TC-24A with the AG-150A controllers, the Setback, Hold, and External Input Function settings should be made 

only on the TC-24A. If using the Hold function on the TC-24A, schedule settings should not be made on the AG-150A controllers. 

To prohibit the operation of local remote controllers, set the prohibition settings either from the TC-24A or AG-150A, but not both.

 * AG-150A Controllers : AG-150A, GB-24A, GB-50A, G-50A

  

(1) Initial startup settings:

Before turning on the controller, first make sure that the controller, indoor units, and outdoor units have been installed

properly according to the instructions detailed in the respective manuals. 

Turn on the controller and the units. 

(a) The Language screen will appear

 Ԙ

Select the display language.

ԙ

Touch the button to select the language of your choice. 

Ԛ

Touch the OK button.

(b) The Date and Time screen will appear.

 

  

Ԙ

 Set the current date on the Date tab, and set the current time on the Time tab, 

using the ▼ and ▲ buttons to change the values.

ԙ

 Click on the checkbox next to the date/time format of your choice. 

Ԛ

 Touch the Save button to save the settings.

(c) The Service Menu screen will appear.

  

Ԙ

 Touch the Initial Settings/Basic System button to set the basic settings for the 

controller. (Refer to section 3(2)-1 for details.) 

ԙ

 When the settings have been chosen, touch the Initial Settings/Groups button.

(d) The Initial Settings/Groups screen will appear.

  

Ԙ

 Touch the Groups button to make the group settings. (Refer to 3(2)-2 for 

details.) 

ԙ

 Touch the Interlocked LOSSNAY button to make the interlocked operation 

settings. (Refer to 3(2)-3 for details.)
The initial startup settings are now complete.  

Ԛ

 Touch HOME button [       ] at the top right corner of the screen. 

ԛ

 Touch the OK button on the popup screen to start the initialization process.

(e) The message (shown left) will appear on the screen, displaying the 

initialization progress. When initialization is complete, the screen will 

automatically return to the HOME screen.

(Initialization will take up to five minutes.) 

* To change settings later, perform a test run, or verify the maintenance 

information

  

Ԙ

 Touch MAIN MENU button [        ] on the HOME screen. 

ԙ

 Touch SERVICE MENU button [       ] on the Main Menu screen.

Ԛ

 Enter the password to log on to the Service Menu screen. 

(Refer to Chapters 3, 4, and 5.)

4

External Input Mode

1)  Press  the  External  Input  setting  button  (labeled 

Ԙ

  in  the  figure)  to  select 

between  “Not  used”,“Emergency  Stop  (Level  signal),”  “ON/OFF  (Level 

signal),” and “ON/OFF/Prohibit/Permit (Pulse signal).”

* Refer to the Installation Manual for detailed information on how to connect 

the TC-24A to external devices.

Set Temperature Range (Schedule)

Set the temperature range that is available from the Set Schedule screen.

1) Touch the Set Temperature Range button (labeled 

Ԙ

 in the figure) to switch 

between Standard, Low, and Manual.

The temperature set range for each option is shown below: 

Standard : 67ºF(19ºC) to 83ºF(28ºC)

Low  

: 46ºF(8ºC) to 87ºF(30ºC)

Manual  : Can be set to any arbitrary range between 46ºF(8ºC) and 

87ºF(30ºC)

2)  When  “Manual”  is  selected,  set  the  lower  and  upper  temperature  limits 

using the up and down arrows (labeled 

ԙ

 in the figure). 

(2) Other Initial Settings

 

(2)-1. Basic controller setting

  

Touch Initial Settings/Basic System button [        ] on the Service menu screen to 
access the Initial Settings/Basic System screen.
Touch Page turn button [        ][        ] to turn the pages, and follow the directions 
below to make the settings for each group.

  

M-NET Address

1)  Touch  the  M-NET  Address  button  (labeled 

Ԙ

  in  the  figure),  and  set  the 

TC-24A Controller address on the screen that pops up.
● The address can be set to 000 or to a value between 201 and 250 (the 

factory setting is 201).

  

Remote Controller Access

1) Touch the Remote Controller Access setting button (labeled 

ԙ

in the figure) 

to switch between “SC/RC” and “RC only.”
● Select “SC/RC” to prohibit access* from both the system controllers and 

remote controllers, and select “RC only” to prohibit access from only the remote controllers.
* Access to ON/OFF, Mode, Set Temp, and Filter Reset.

Filter Sign Display

1)  Press  the  Filter  Sign  Display  button  (labeled 

Ԙ

  in  the  figure)  to  switch 

between ON and OFF.

● Setting this item to OFF will remove the Filter Sign from the HOME screen 

display. 

This item can be set to OFF if there is no need for the sign to appear on the 

HOME screen; for example, in cases where filters are regularly changed 

regardless of the filter sign status.

  

Dry Mode

1) Press the Dry Mode Setting button (labeled 

ԙ

 in the figure) to switch between 

"Used" and “Not Used.”

● If this item is set to “Not Used,” the Dry mode will be unavailable for selection.

Ԙ

Ԙ

ԙ

Ԙ

ԙ

Ԙ

 

 

ԙ

Page turn button

Page No./No. of pages

Cannot set through TC-24A

Summary of Contents for TC-24A

Page 1: ...option for the operation mode Selects the settable temperature range Standard 67 F 19 C to 83 F 28 C Low 46 F 8 C to 87 F 30 C Manual Settable to any arbitrary range between 46 F 8 C and 87 F 30 C Sends or does not send the clock synchronization signal once a day to the controllers and units Makes the group settings for the indoor units LOSSNAY units DIDO controllers PAC YG66DCA remote controllers...

Page 2: ...Menu and the Service Menu Touch Touch Touch Touch Touch Touch Touch Touch Touch Maintenance Touch Touch Touch System view Malfunction log Software update Test run Groups Interlocked LOSSNAY Delete All HOME screen Service Menu screen Touch Touch Initial settings Basic system Initial settings Groups Touch Main Menu screen GRID zoom out view GRID zoom in view LIST view GROUP view Password Change scre...

Page 3: ...The Date and Time screen will appear Ԙ Set the current date on the Date tab and set the current time on the Time tab using the and buttons to change the values ԙ Click on the checkbox next to the date time format of your choice Ԛ Touch the Save button to save the settings c The Service Menu screen will appear Ԙ Touch the Initial Settings Basic System button to set the basic settings for the contro...

Page 4: ...he directions below to make the settings for each group M NET Address 1 Touch the M NET Address button labeled Ԙ in the figure and set the TC 24A Controller address on the screen that pops up The address can be set to 000 or to a value between 201 and 250 the factory setting is 201 Remote Controller Access 1 Touch the Remote Controller Access setting button labeled ԙ in the figure to switch betwee...

Page 5: ...h group 5 After all the settings have been made touch the Save button Ԙ Ԛ ԙ ԛ Ԝ ԝ Model selection screen Clock Setting Signal 1 Touch the Clock Setting Signal button labeled Ԙ in the figure to send or not send the clock synchronization signals to other controllers and units If the Clock Setting Signal is set to ON signals to synchronize the current time will periodically be sent to all system cont...

Page 6: ... LOSSNAY and OA processing units To interlock the ON OFF status of the ventilation units with the indoor units make the settings through the Interlocked LOSSNAY screen Touch the Initial Settings Groups button on the Service Menu and then touch the Interlocked LOSSNAY button on the Initial Settings Groups screen to access the Interlocked LOSSNAY screen ԙ Ԙ Ԙ Ԛ ԙ ԛ Ԟ ԝ Ԝ Model selection screen Group...

Page 7: ...Function Touch the OFF ON button to start a test run Touch the Test Run button to stop the test run These buttons are active only for the units that support the test run function Touch this button to switch between the Cooling mode and the Heating mode The pipe temperature of the indoor unit with the lowest address in a given group will appear Touch this button for advanced settings OFF ON Test Ru...

Page 8: ...utton If a message Unable to read the SD card appears check to make sure that the SD memory card is properly inserted If a message Update file was not found appears check to make sure the SD memory card contains the updated program 3 Following the instructions on the screen remove the cover on the controller by unscrewing the screws at the bottom turn DIP switch 4 to ON and then touch the OK butto...