User’s Manual

(Hardware)

AJ71E71N3-T, A1SJ71E71N3-T
AJ71E71N-B5, A1SJ71E71N-B5
AJ71E71N-B2, A1SJ71E71N-B2

Thank you for buying the Mitsubishi general-purpose programmable  
controller MELSEC-A Series

© 2004 MITSUBISHI ELECTRIC CORPORATION

A Series Ethernet

Interface Module

Prior to use, please read both this manual and detailed manual 
thoroughly and familiarize yourself with the product.

MODEL

AJ71E71N-U-HW

MODEL

CODE

13JP67

IB (NA)-0800308-C(1112)MEE

Summary of Contents for A1SJ71E71N-B2

Page 1: ...g the Mitsubishi general purpose programmable controller MELSEC A Series 2004 MITSUBISHI ELECTRIC CORPORATION A Series Ethernet Interface Module Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL AJ71E71N U HW MODEL CODE 13JP67 IB NA 0800308 C 1112 MEE ...

Page 2: ...gram or operation status remote RUN STOP in particular a PLC while it is running via a device such as a personal computer connected to the special function module configure an interlock circuit in the sequence program so that the safety of the overall system is always maintained Especially when performing the above control for a remote PLC from an external device troubles occurring on the PLC side...

Page 3: ...ke sure to switch all phases of the external power supply off before mounting or removing the module If you do not switch off the external power supply it may result in electric shock or may damage the product Insert the fixing latch on the bottom of the module into the fixing hole in the base unit and install the module using the hole point as a fulcrum The AnS series module shall be fastened by ...

Page 4: ... specified torque If the screws are loose it may result in short circuits or malfunction Tightening the screws to far may cause damage to the screw and or the module resulting in fallout short circuits or malfunction Do not grab on the cable when removing the communication cable connected to the module When removing the cable with a connector hold the connector on the side that is connected to the...

Page 5: ...Tightening the screws too far may cause damage to the screws and or the module resulting in fallout short circuits or erroneous operation CAUTION Do not disassemble or rebuild the module It may cause failure erroneous operation injury or fire Make sure to switch all phases of the external power supply off before mounting or removing the module If you do not switch off the external power supply it ...

Page 6: ...to the special function module read the manual carefully and confirm if the overall safety is maintained Failure to perform correct operations to change data program or the operation status may result in system malfunction machine damage or an accident Remote RUN STOP for the module installation station s PLC CPU is recommended to use the Data Exchange during PLC CPU STOP function after throughly ...

Page 7: ...ENDED OR EXCLUDED BY INSTRUCTIONS PRECAUTIONS OR WARNING CONTAINED IN MITSUBISHI S USER INSTRUCTION AND OR SAFETY MANUALS TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT Prohibited Application Prohibited Applications include but not limited to the use of the PRODUCT in Nuclear Power Plants and any other power plants operated by Power companies and or any other cases in which the public could be...

Page 8: ...ns provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail safe redundant or other safety features which exceed the general specifications of the PRODUCTs are required For details please contact the Mitsubishi representative in your region ...

Page 9: ...8 C SAFETY PRECAUTIONS COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES SAFETY PRECAUTIONS Chinese CONDITIONS OF USE FOR THE PRODUCT This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of usin...

Page 10: ... INSTALLATION 10 4 1 Handling Precautions 10 4 2 Installation Environment 10 5 CONNECTION TO A NETWORK 11 5 1 Connecting to the 10BASE T AJ71E71N3 T A1SJ71E71N3 T 12 5 2 Connecting to the 10BASE5 AJ71E71N B5 A1SJ71E71N B5 12 5 3 Connecting to the 10BASE2 AJ71E71N B2 A1SJ71E71N B2 12 6 EXTERNAL DIMENSIONS 13 ...

Page 11: ...equipment certain measures may be necessary Please refer to one of the following manuals User s manual for the CPU module used User s manual hardware for the CPU module or base unit used The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives 2 Additional measures To ensure that this product maintains EMC and Low Voltage Directives please ref...

Page 12: ...ed Model name Product name No of items AJ71E71N3 T AJ71E71N3 T type Ethernet Interface Module 1 AJ71E71N B5 AJ71E71N B5 type Ethernet Interface Module 1 AJ71E71N B2 AJ71E71N B2 type Ethernet Interface Module 1 F type Connector A6RCON F 1 A1SJ71E71N3 T A1SJ71E71N3 T type Ethernet Interface Module 1 A1SJ71E71N B5 A1SJ71E71N B5 type Ethernet Interface Module 1 A1SJ71E71N B2 A1SJ71E71N B2 type Etherne...

Page 13: ...connectors 8 connections Fixed buffer 1 k word 8 Random access buffer 3 k word 2 Number of remote nodes that can be communicated in a single initial processing No restrictions Number of occupied I O points 32 points 1 slot I O assignments special 32 points 5 V DC internal current consumption AJ71E71N3 T 0 69A A1SJ71E71N3 T 0 69A Connector Modular jack RJ45 Connection cable Unshielded twisted pair ...

Page 14: ...llowable simultaneously open connectors 8 connections Fixed buffer 1 k word 8 Random access buffer 3 k word 2 Number of remote nodes that can be communicated in a single initial processing No restrictions Number of occupied I O points 32 points 1 slot I O assignments special 32 points 5 V DC internal current consumption AJ71E71N B5 0 55A A1SJ71E71N B5 0 57A AJ71E71N B2 0 67A A1SJ71E71N B2 0 66A Co...

Page 15: ...4 3 The weight of the A1SJ71E71N B5 is 0 19kg 0 42lb when the hardware version is A 4 The weight of the A1SJ71E71N B2 is 0 20kg 0 44lb when the hardware version is B or earlier ...

Page 16: ...en connected by 10BASE T 2 Hardware specifications for E71 are based on IEEE802 3 Node Node Node Node Node Repe ater Repe ater Segment length Terminator Transceiver Segment length Segment length Maximum distance between nodes Maximum 100 m 328 08 ft Maximum 100 m 328 08 ft Hub E71 Cascade connection is a maximum of 4 stages ...

Page 17: ...CH PART 1 The LED provided on the connector does not light up 1 4 3 2 1 7 6 5 3 2 1 8 3 2 1 AJ71E71N3 T AJ71E71N B2 AJ71E71N B5 1 Side view indicated by arrow A 3 A 3 4 2 1 6 7 2 1 8 3 2 1 A1SJ71E71N3 T A1SJ71E71N B2 A1SJ71E71N B5 ...

Page 18: ... of 10BASE5 use AUI cable transceiver cable 8 10BASE2 connector Connector for connecting the E71 to the 10BASE2 Display LED Display contents When lamp is lit Lamp is not lit RUN Normal operation display Normal Error RDY Exchange ready end display Starts flashing when On line Operations begin BSY Exchange processing executing display Turns on when exchange processing with remote node is being execu...

Page 19: ...ting switch Setting number Setting designation Setting contents 0 On line Performs exchange with remote node in the normal operation mode 1 Off line Disconnects the local station from the network 2 Test 1 Performs a self diagnosis test using a self loopback test 3 Test 2 Performs a RAM test 4 Test 3 Performs a ROM test 5 to F Usage not impossible A1SJ71E71N3 T A1SJ71E71N B5 AJ71E71N3 T AJ71E71N B5...

Page 20: ... during TCP timeout error Selects the line processing when the TCP ULP time out error occurrence 1 OFF Close the circuit ON Do not close the circuit SW2 Data code setting Selects the type of data code for exchanging data with the remote node OFF Conducts exchange in binary code ON Conducts exchange in ASCII code SW3 to SW6 Usage not possible Fixed to OFF SW7 CPU exchange timing setting Selects whe...

Page 21: ...g impact 2 Always make sure to touch the grounded metal to discharge the electricity charged in the body etc before touching the module Failure to do so may cause a failure or malfunctions of the module 3 Execute tightening of the module s installation screws within the range indicated below 4 2 Installation Environment Refer to User s Manual of CPU module to be used Screw position Tightening torq...

Page 22: ...ith TCP IP increase the count of communication retries When connecting to 10BASE T use a shielded twisted pair cable STP rated in category 3 4 or 5 When connecting to 10BASE2 use a double shielded coaxial cable When connecting to 10BASE5 or 10BASE2 ground the shield of the coaxial cable at both the local station and companion connected device Ground at a place near the connector 4 Below are the st...

Page 23: ...r cable and the hub 2 Connect the twisted pair cable to the E71 Connection procedure 1 1 Slide the retainer toward the direction A as shown in the figure 2 Push in the AUI cable connector all the way 3 Slide the retainer toward the direction B as shown in the figure 4 Confirm that the AUI cable is locked 5 Supply power to the transceiver 2 Refer to 2 in Chapter 2 Connection procedure 2 1 Push in t...

Page 24: ...icinity of the connector to cable outside diameter 4 or more 2 AJ71E71N B5 2 When connecting the AUI cable make the bend radius R2 scale value in the vicinity of the connector to cable outside diameter 4 or more Unit mm in 1 R1 37 5 1 48 250 9 84 106 4 17 4 2 0 17 2 R2 37 5 1 48 4 2 0 17 14 0 55 250 9 84 106 4 17 Unit mm in ...

Page 25: ...nnecting the twisted pair cable make the bend radius R1 scale value in the vicinity of the connector to cable outside diameter 4 or more Unit mm in 56 2 20 37 5 1 48 4 2 0 17 250 9 84 106 4 17 Unit mm in 3 130 5 12 34 5 1 36 6 5 0 26 94 3 70 R1 ...

Page 26: ...ctor to cable outside diameter 4 or more 6 A1SJ71E71N B2 Ethernet is the registered trademark of XEROX CO LTD 10BASE2 is the formal way to say Cheapernet There is no registered trademark for Cheapernet Unit mm in 4 R2 7 5 0 30 130 5 12 6 5 0 26 94 3 70 34 5 1 36 Unit mm in 56 2 20 130 5 12 6 5 0 26 94 3 70 34 5 1 36 ...

Page 27: ...16 MEMO ...

Page 28: ...17 MEMO ...

Page 29: ...18 MEMO ...

Page 30: ...es Bouvets F 92741 Nanterre Cedex France Tel 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 China Mitsubishi Electric Automation China Ltd 4 F Zhi Fu Plazz No 80 Xin Chang Road Shanghai 200003 China Tel 86 21 6120 0808 Taiwan Setsuyo Enterprise Co Ltd 6F No 105 Wu Kung 3rd Rd Wu Ku Hsiang Taipei Hsine Taiwan Tel 886 2 2299...