background image

SENTRY

®

RCBO

(Residual Current Operated
Circuit Breaker with Integral
Over-Current Protection)

Contents

A

Introduction

2

B

Product Range

3

C

Product Specification

4

D

Standards Compliance

6

E

Safety Instructions

6

F

Installation - General Notes 

8

G

Installation

10

H

Testing

11

I

Tripping in Service

14

J

Guarantee

15

Please leave this leaflet with the
end user for future reference

52778PL Rev BB

2

ln this range of Single Module Width RCBO’s, each
product provides dual protection; from Over-current via
its MCB section, and from Earth Leaking Fault Current
(Residual Current) via its RCD section.

These devices provide RCD protection in full
compliance with the requirements of the Standard
BS EN 61009-1.  They also provide very effective RCD
protection in the Supply Voltage Range of 

110V

to

253V a.c.,

meeting the requirements of the Standard

for sensitivity and trip speed at 

n and 

2

n.

They meet the requirement of the current edition of the
UK Wiring Regulations (BS 7671), as regards ability to
trip with Earth Loop Impedance of up to 1667

Ω

(for a

30mA RCD), by being able to operate with Earth Loop
Impedance of up to 10,000

Ω

.

A. INTRODUCTION

5

Mechanical

Terminal Capacity

Line in - 25mm

2

Line and Neutral out - 25mm

2

Product Width

18mm

Product Height above

76mm

Din Rail

Product Length

118mm

Suitable Mounting

MK Sentry Consumer Unit

Enclosure

(select from the MK range)

Method of Mounting

Top Hat Mounting (DIN)

in Enclosure

Rail to EN 50022

Environmental

Ambient Temperature Range

-5°C to +40°C

Storage Temperature Range

-30°C to +85°C

Protection, Un-installed Device

IP 20

Protection, Installed in the
Consumer Unit

IP 40

C. PRODUCT SPECIFICATION 

(Cont.)

6

The products in this range comply with the requirements of the
following standards:

BS EN 61009-1
BS IEC 61009-2-2
EN 61543 for EMC

D. STANDARDS COMPLIANCE

1.

This product must be installed by a competent person (e.g. a
qualified electrician) in accordance with these instructions and
the appropriate clauses of the current edition of the IEE Wiring
Regulations (BS7671) and Building Regulations.

2. The RCBO must be installed within a SENTRY

®

Consumer Unit

(select from the range of MK consumer units).

3. The RCBO should not be regarded as a substitute for basic safety

precautions.

4. Test the RCBO quarterly, as detailed in the current edition of the IEE

Wiring Regulations (BS 7671), by pressing the TEST BUTTON marked
T, provided on the product (see label on the Consumer Unit).

E. SAFETY INSTRUCTIONS

7

Do not use the product if 
it fails to trip during this
operation.  Failure to trip
indicates either no supply to
the RCBO or a faulty device.
Consult a qualified electrician
or contact MK Technical Sales
and Service Department.

Telephone:
01268 563720

(National)

+44 (0) 1268 563758 

(International)

5. Choose an RCBO from TABLE 1,

with the correct ratings, for the
circuit to be protected.

6. The RCBO’s in this range must

not be used in ambient
temperatures outside their
specified range.

L

IN

N

OUT

L

OUT

I

n  30mA

6000

3

230V

B32

7936s

ON

BS EN61009-1

Load

N

OUT

L

OUT

N

IN-Supply

(Blue)

FE

(White)

     L
IN-Supply

Blue Flying

Curled Neutral

Supply Lead

White or

Cream

Flying Earth

Supply Lead

Line Supply

E. SAFETY INSTRUCTIONS 

(Cont.)

8

1. The RCBO shall be installed at the source of the circuit

in which the Earth Fault and Over-current protection is
required.

2. The RCBO’s may be installed alongside other SENTRY

®

Modular Products, as part of a larger assembly.

3. The RCBO is a sensitive device designed for fixed

installation in a clean and dry environment.  The device
must not be installed as part of a portable system which
may be subject to mechanical shocks and vibration.

4. An adhesive label giving test instructions is provided

with each RCBO.  This label shall be placed in a
prominent position close to the RCBO (preferably on the
Consumer Unit Cover).

5. Upon completion of the installation, please leave this

instruction leaflet in close proximity to the RCBO, for
future reference.

F. INSTALLATION - GENERAL NOTES

4

Electrical

Number of Poles

Single Pole with Solid
Neutral

Rated Supply Voltage

230V a.c. +10%, -15%

Supply Voltage Range

110V to 253V a.c.

Supply Frequency Range

45 to 66Hz

Supply Voltage Range for

195V to 253V a.c.

Test Device Operation

RCD Trip Current Rating

30 mA

Operating Characteristics

Type AC

MCB

Type B, C

Rated Short Circuit

6 kA

Capacity Icn

Neutral Connection

Flying Lead

Earth Connection

Flying Lead

C. PRODUCT SPECIFICATION

3

The product range is given in Table 1 below. 

All products in the range have an RCD trip current
rating of 30mA.

Table 1

Type B RCBO

Type C RCBO

List No.

MCB Current

List No.

MCB Current

Rating A

Rating A

07932s

6

08932s

6

07933s

10

08933s

10

07934s

16

08934s

16

07935s

20

08935s

20

07936s

32

08936s

32

07937s

40

08937s

40

07938s

45

08938s

45

07939s

50

08939s

50