background image

SAVE THESE INSTRUCTIONS

LVM-125/25

0

(LVS Catalog #: CEPS-125/250)

INSTRUCTION MANUAL

EMERGENCY POWER EQUIPMENT

UNIVERSAL MICRO INVERTER

PURE SINUSOIDAL AC OUTPUT

OUTPUT VOLTAGE AUTO SETTING EQUAL TO INPUT VOLTAGE

AUTO DIMMING (0-10V) OF CONNECTED LOAD 

IMPORTANT SAFEGUARDS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, 

INCLUDING THE FOLLOWING

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1. To prevent electric shock, switch off the mains power until installation is complete and

AC input power is supplied to this product.

2. This product requires an unswitched AC power supply of 120-277V, 50/60Hz.

3. Ensure all connections are in accordance with National Electrical Code or Canadian

Electrical Code and all local regulations.

4. To reduce the risk of electrical shock, disconnect both normal power, emergency power

supplies and unit connector of this product before servicing.

5. For emergency operation of LED, incandescent, fluorescent fixtures and screw-base

lamps.

6. The product has a metallic housing and is suitable for installation in air handling/plenum

spaces in accordance with the National Electric Code.

7. Use this product in 0°C minimum, 50°C maximum ambient temperatures (Ta). To ensure

the emergency operating time over 90 minutes, the output emergency power of LVM-125

/250 should be maximum of 125W for the LVM-125 and 250W for the LVM-250.

8. Use with grounded, Listed, dry or damp location rated fixtures and the case should be

grounded.

9. Do not use outdoors. Do not mount near gas or electric heaters.

10. The use of accessory equipment not recommended by the manufacturer may cause an

unsafe condition and void warranty.

11. Do not use this product for other than intended use.

12. Installation and service should be performed by qualified service personnel.

13. This product should be mounted in locations and at heights where it will not readily be

subjected to tampering by unauthorized personnel.

10E22

44 South Commerce Way, Bethlehem, PA 18017

Technical Support: 610-868-5400

THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM IRON PHOSPHATE BATTERY.

THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

WWW.MYERSEPS.COM

WWW.LVSCONTROLS.COM

E95719

3KLH

INSTALLATION MANUAL

LFP

Summary of Contents for LVM-125

Page 1: ...uct has a metallic housing and is suitable for installation in air handling plenum spaces in accordance with the National Electric Code 7 Use this product in 0 C minimum 50 C maximum ambient temperatures Ta To ensure the emergency operating time over 90 minutes the output emergency power of LVM 125 250 should be maximum of 125W for the LVM 125 and 250W for the LVM 250 8 Use with grounded Listed dr...

Page 2: ...SCONNECTED UNTIL THE INSTALLATION IS COMPLETE WWW MYERSEPS COM WWW LVSCONTROLS COM 44 South Commerce Way Bethlehem PA 18017 Technical Support 610 868 5400 1 SPECIFICATION OF LVM 125 250 LVM 125 LVM 250 Output Output Power Voltage Input 230V 50Hz 120V 60Hz 125W 250W 230V 50Hz 120V 60Hz 277V 60Hz 277V 60Hz 1 2 3 4 9 10 5 6 7 ON 8 ...

Page 3: ...5 1 77 LVM 125 LVM 250 Item No W mm inch H mm inch L mm inch 292 11 50 398 15 67 M2 Mounting mm inch 282 11 10 388 15 28 175 6 89 85 3 35 175 6 89 85 3 35 Dimension unit mm inch Weight kg lb 4 2 9 24 7 0 15 4 M1 Hanging mm inch 252 9 92 358 14 09 SURFACE MOUNTING OPTIONAL MOUNTING ACCESSORIES AVAILABLE CONSULT FACTORY FOR DETAILS WALL MOUNT ADAPTOR CEILING GRID MOUNT ADAPTOR ...

Page 4: ...FLUORESCENT INCANDESCENT LUMINAIRE FOR EMERGENCY LED FLUORESCENT INCANDESCENT LUMINAIRE LED FLUORESCENT INCANDESCENT LUMINAIRE 0 10V DIMMER SWITCH HOT WIRING DIAGRAM FOR 0 10V DIMMABLE EMERGENCY LIGHTING SYSTEM ANY QUANTITY WIRING DIAGRAM FOR NON DIMMABLE EMERGENCY LIGHTING SYSTEM ANY QUANTITY MAX POWER 125W LVM 125 250W LVM 250 MAX DIMMABLE LOAD 750W GROU N D LED FLUORESCENT INCANDESCENT LUMINAIR...

Page 5: ...nd up to 7 days after initial power on Then monthly tests will be performed every 30 days b Annual Auto test will occur every 52 weeks after initial power on Monthly Auto Test The Monthly Auto Test shall be executed every 30 days and will test Normal to emergency transfer function emergency charging and discharging conditions are normal Monthly test time is approximately 60 seconds Annual Auto Tes...

Reviews: