GENERAL DESCRIPTION 

     The GEMC-OUT8 is an 8-channel active low interface 

accessory for use with GEMC-Series control panels.  The 
GEMC-OUT8 may be used with all control panels, 
regardless of housing.  It connects onto the remote panel 
Fire bus or models GEMC-BM (WI1701) or GEMC-BM/PS 
(WI1700) along with such other accessories as keypads and 
zone expansion modules.  Up to 11 GEMC-OUT8 units may 
be used. 

     The GEMC-OUT8 provides 8 independent programmable 

active low unsupervised external outputs for controlling bells, 
door latches, lights, supplemental lights and other similar 
devices.  The panel controls the activation of each external 
output.  Refer to the GEMC-Series installation instructions 
(WI1653) or the installation instructions of the control panel in 
use for wiring requirements in UL-listed applications. 

 

SPECIFICATIONS 

    Electrical Ratings 
       Input Power:

  12.5 - 7.5VDC, 35mA standby maximum. 

      

Current:

  Standby 35mA + current required for each ac-

tive output. 

       Output Power:

  Active low outputs. 

      

Maximum Single Output Current:

  50mA power-limited 

circuits 14VDC maximum. 

      

Maximum Combined Output Current:

  400mA power-

limited circuits 14VDC maximum. 

       Note:   

Output current must be deducted from either 

standby current or alarm current depending on the func-
tion of the output unless current is provided by a sepa-
rate UL Listed Burglary / Signaling power limited power 
supply at 12 volts. 

 

BOARD/MODULE ASSIGNMENT 

     The control panel must be able to identify the relay board or 

module.  This is accomplished by the proper placement of 
jumpers on Jumper Block J1 (see Wiring Diagram on page 2 
and table below). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

WIRING 

     Connect the wires to the control panel as shown in the 

Wiring Diagram.  The maximum distance for a single GEMC-
OUT8 wiring run is 1000 feet using #22AWG wire.  The 
maximum distance for up to 5 GEMC-OUT8 modules 
connected to a single wiring run is 300 feet using #22AWG 
wire. 
 

Examples:

 

1.  Wire an LED to Output # 1 (Terminal 5). 
2.  Wire a light to Output # 3 (Terminal 7). 
3.  Wire Output # 4 (Terminal 8) to the negative trigger input 

of a Supplemental communications device. 

 
 
 
 
 
 
 
 
 

OPERATION 

     The GEMC-OUT8 provides 8 "active low" open collector 

outputs.  Each output will provide a "floating" ground for the 
load device.  In a normal state, the output will float at 
approximately 12VDC relative to ground.  When active, the 
output will drop to a low state of approximately 1-4VDC, 
effectively providing a ground for the load device, which will 
then activate.  

Note:

 In order to measure or test the state of 

an output, a load must be applied to the output.  See 
Calculating Load Current. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

PROGRAMMING 

 

 

 

 

 Use PCD-Windows Quickloader Download software. 

 

Note:

  Outputs of the GEMC-OUT8 may not be pro-

grammed as SILENCE-ABLE. 

LED

1K

 

+12V 

BLA

C

+12V 

RED 

BLACK 

Supplemental  
communications 
device 

1

2

3

4

LED 

+12V DC 

SOURCE 

DVM = 

12V DC

DVM = 

12V DC

NORMAL 

+12V DC 

SOURCE 

DVM = 

12V DC

DVM =   

1-4V DC

ACTIVE 

Available Voltage 

= 0V DC 

Available Voltage 

= 8-11V DC 

Note:

 * Voltage measurements are relative to 

ground (negative DVM lead to module ground). 

GEMC-OUT8 

Programmable Output Module

 

INSTALLATION INSTRUCTIONS

 

WI1707  08/10 

R

333 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 

 

Publicly traded on NASDAQ      Symbol: NSSC

 

© NAPCO 2010 

MODULE 
NUMBER 

EXTERNAL  

OUTPUT # 

JUMPER BLOCK (J1)  

PANEL  

CAPACITY 

 

 

J1-4  J1-3  J1-2  J1-1 

 

1 - 8 

• 

• 

• 

• 

1 - 8 

• 

• 

• 

ON 

8 - 16 

• 

• 

ON 

• 

17 - 24 

• 

• 

ON  ON 

25 - 32 

• 

ON 

• 

• 

32 - 40 

• 

ON 

• 

ON 

41 - 48 

• 

ON  ON 

• 

49 - 56 

• 

ON  ON  ON 

57 - 64 

ON 

• 

• 

• 

65 - 72 

ON 

• 

• 

ON 

10 

73 - 80 

ON 

• 

ON 

• 

11 

81 - 88 

ON 

• 

ON  ON 

NOTE:  •

 Indicates Jumper is OFF. 