FieldPoint

™ 

and natinst.com

 are trademarks of National Instruments Corporation. Product and 

company names mentioned herein are trademarks or trade names of their respective companies.

322395A-01

©

 Copyright 1999 National Instruments Corp. All rights reserved.

July 1999

OPERATING INSTRUCTIONS

FP-1600

FieldPoint 10/100 Ethernet
Network Module

These operating instructions describe the installation, features, and 
characteristics of the FP-1600. For more detailed information on 
using the network module, refer to the FP-1600 user manual.

Features

The FP-1600 is a FieldPoint network module with the following 
features:

Autonegotiating 10/100 Ethernet network interface

Built-in high efficiency power supply powers I/O modules

Network watchdog timer

SnapShot capability and programmable power-up state

–40 to +55 °C operation

Connects to an Ethernet network using the TCP/IP protocol

Supports up to nine I/O modules

Runs on 11 to 30 VDC power

Kit Contents and Optional Equipment

Your kit contains the following items:

FP-1600 network module

Accessories: protective connector cover, two DIN rail stops, 
Device Description diskette

You can order the following optional equipment from National 
Instruments:

Panel mount accessory, part number 777609-01

Summary of Contents for FIELDPOINT FP-1600

Page 1: ...user manual Features The FP 1600 is a FieldPoint network module with the following features Autonegotiating 10 100 Ethernet network interface Built in high efficiency power supply powers I O modules...

Page 2: ...o install the FP 1600 1 Use a flat bladed screwdriver to open the DIN rail clip to the unlocked position as shown in Figure 1 Figure 1 DIN Rail Clip Note Write down the serial number from the back of...

Page 3: ...FP 1600 to the DIN rail by pushing the rail clip to the locked position Installing onto a panel mount accessory which you can order separately from National Instruments a Snap the panel mount accesso...

Page 4: ...the local bus connector of the last terminal base in the bank Figure 4 shows an installed FP 1600 network module on a DIN rail Figure 4 Installed Network Module Network Connection Connect the FP 1600...

Page 5: ...ng Connections Pin Connector 1 Connector 2 Normal Connector 2 Crossover 1 white orange white orange white green 2 orange white orange white green white 3 white green white green white orange 4 blue wh...

Page 6: ...11 30 VDC power supply The FP 1600 filters and regulates this supplied power and provides power for all the I O modules in the bank Therefore you do not need to provide power separately to each Field...

Page 7: ...s Network interface 10BaseT and 100BaseTX Ethernet Compatibility IEEE 802 3 Communications rate 10 Mbps 100 Mbps autonegotiated Cabling distance 100 m Power supply range 11 to 30 VDC Power consumption...

Page 8: ...eets applicable EU directive s as follows EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 meters Mechanical Dimensions Figure 8 shows the mechanical dimensions of...