USER GUIDE

RMX-10050/10051

Power Distribution Units 

Overview

The RMX-10050/10051 are a series of Power Distribution Units (PDUs) installed in integrated test 
equipment platforms. Each PDU receives mains power through an inlet, and distributes that power to 
various outlets. Some models may include an output sequencing feature, additional DC power 
outputs, or a remote EPO feature. All models are constructed of a steel chassis and designed for fixed 
mounting within an EIA-310 compliant rack enclosure.

There are two single-phase and two three-phase PDUs. The following tables provide 
environmental ratings and feature information.

Table 1.  

RMX-10050/10051 Environmental Ratings (All Models)

Category

Rating

Operational Maximum Altitude

3000 m

Operational Temperature Range

0 °C to 50 °C

Operational Humidity Range

5% to 85% relative humidity, noncondensing

Table 2.  

RMX PDU Family and Features

Product

Model

Part Number

Included Features

Single Phase PDU 
with DC Output

RMX-10050

(785341-01)

DC Output, Remote EPO, 
Sequencing

Single Phase PDU

RMX-10050

(785342-01)

Remote EPO

Three Phase PDU (Wye)

RMX-10051

(785344-01)

DC Output, Remote EPO, 
Sequencing

Three Phase PDU (

Delta)

RMX-10051

(785343-01)

DC Output, Remote EPO, 
Sequencing

Summary of Contents for RMX-10051

Page 1: ...e are two single phase and two three phase PDUs The following tables provide environmental ratings and feature information Table 1 RMX 10050 10051 Environmental Ratings All Models Category Rating Oper...

Page 2: ...A max with DC disabled RMX 10050 785342 01 Single Phase IEC 60320 C20 100 240 V 2P3W 16A 50 60 Hz C13 100 240V 10 A max per receptacle Total AC output 16 A max RMX 10051 785344 01 Three Phase Wye 4P5W...

Page 3: ...plug as well as a redundant chassis ground screw on the rear panel Ensure that the product is properly grounded before applying power Disconnect all power to the product prior to servicing Do no open...

Page 4: ...panel Ensure no external equipment or cables restrict the airflow through the intake or exhaust ports Chassis Ground The rear of the chassis includes a redundant chassis ground screw and ground wire...

Page 5: ...he rear panel The total DC output is always limited to 500 W This is divided evenly as 125 W per each of the four output channels The ratings table in this manual describes the specific outputs and ra...

Page 6: ...ctors use two low voltage signals as follows Shorting the ENABLE pin to the RETURN pin with a dry contact will trigger the Enable signal Opening the DISABLE pin from the RETURN pin will trigger the Di...

Page 7: ...n 44 196 mm 1 74 in Black 27038 All Outside Surfaces Exhaust Air 4 4 X 0 20 DP Holes 2X Both Sides Off Off On On Breaker Breaker Main Breaker Main Breaker GROUP A GROUP A On On Main Power Main Power P...

Page 8: ...d 4 4 X 0 20 DP Holes 3X Both Sides IEC 60309 6H Exhaust Air Main Breaker Main Breaker DC INHIBIT DC INHIBIT J 8 J 8 DC 1 DC 1 DC 2 DC 2 DC 3 DC 3 DC 4 DC 4 J 3 2 J 3 2 J 3 1 J 3 1 J 2 2 J 2 2 J 2 1 J...