PRODUCT OVERVIEW

The nLight 

nPP16 

family of power packs is the workhorse of an nLight system, delivering 

robust system performance and design versatility for commercial and industrial lighting 
control applications. The 

nPP16

 family is capable of switching loads up to 16 Amps via 

an internal latching relay designed with robust protection from the harsh switching 
requirements of T5 fluorescent and LED loads. These power packs also provide nLight system 
bus power - up to 40mA from each of its two RJ-45 ports - by transforming Class 1 line 
voltage (120/277 VAC or 347 VAC) to Class 2 15 VDC. This power is typically utilized by other 
nLight devices within the power pack’s local control zone; however, remaining power is also 
made available over the network for Bridges and devices in other zones to utilize. 

Besides switching, the 

nPP16

 family has an optional 0-10V dimming output. This output can 

be directly wired to 0-10 VDC dimmable ballasts or LED drivers, and is fully isolated internally 
from ingress noise or line voltage faults. Models are available with dimming wires running 
through the chase nipple  (

nPP16 D

) or out the side of the enclosure (

nPP16 DS

).

The 

nPP16 ER

 and 

nPP16 D ER

 version relay packs provide a UL 924 compliant solution for 

controlling luminaires powered via an emergency circuit. Packs are wired to both normal and 
emergency power feeds. A unit only monitors the normal feed, while the emergency feed 
is connected to the line side of its relay. The power feed to emergency lighting is connected 
to the load side of the unit’s relay. When normal power is present the relay is free to switch 
the emergency power feed as directed by sensors, switches, and schedules. However, if the 
normal power feed is lost the 

nPP16 (D) ER

 will override its relay closed and set its dimming 

output to full bright, thus ensuring emergency lighting is on. During this emergency 
operation period, the unit will not allow any switching or dimming to take place regardless 
of the presence of an occupancy, daylight, or other control signal. Emergency units power 
themselves from the emergency feed they are controlling, but they do not supply bus power 
out of the RJ-45 ports, and are often complemented with standard nPP16 power/relay packs 
that control a zone’s normal-powered lighting. 

To simplify installation, all 

nPP16

 family power packs are designed with an elongated chase 

nipple that allows them to be attached directly through a ½” knockout into a junction box or 
luminaire.

 

nLIGHT OPERATION

All 

nPP16 

family power/relay packs are native nLight devices, meaning they are individually 

addressable and communicate digitally over an nLight network to integrate with other nLight 
enabled devices, such as wall switches, sensors, and photocells. Creation of a local nLight 
control zone is done by simply wiring together nLight devices using CAT-5e cabling. When an 
nLight zone is linked to an nLight Gateway (nGWY2) - either directly via an nLight network 
backbone (nBRG 8) or wirelessly via nWiFi - the zone becomes capable of remote status 
monitoring and control with nLight SensorView software. 

 

All nLight switches and sensors can be configured to output on one of 16 local channels or 
128 global channels. 

nPP16

 family power/relay packs are configured to follow one or more of 

these channels via their tracking channel settings. By default, a standard 

nPP16 

is configured 

to follow all occupancy, photocell, and switch commands on Channel 1. 

Once powered, units close their relay. If an nLight occupancy sensor is connected, the pack 
will automatically start following the occupancy status of the sensor. The factory default 
sequence of operation of standard units is Auto On/Auto Off. Via the 

-SA

 option, Manual 

On / Auto Off is also available as the factory default operational sequence. Several other 
operational sequences are selectable via the unit’s push-button or SensorView software. 
If communication is lost between an 

nPP16

 family power/relay pack and all other nLight 

devices, the unit will revert back to its default state of relay closed (lights on). All factory 
defaults can be changed by using the unit’s push-button or via SensorView software.

1 of 3

Sensor Switch     900 Northrop Road, Wallingford, CT 06492     Phone: 1-800.PASSIVE      sensorswitch.com/nLight     ©2014 Acuity Brands Lighting, Inc.     All rights reserved 09/26/14

nPP16

FAMILY

POWER / RELAY PACK w/ 

OPTIONAL DIMMING and EMERGENCY OPERATION

KEY OPTIONS

DIMMING CONTROL (D, DS)

•   Provides dimming outputs to control 0-10 VDC dimmable ballasts or LED drivers
•   Follows dimming commands from nLight dimming WallPods, Photocells, Scene 

Controllers, and/or SensorView software

•   Adds 20 AWG (600V rated) violet & gray wires through chase nipple (

option) or via a 

separate side output (

DS 

option)

•    Isolated dimming circuitry provides robust network protection from ingress noise or line 

voltage faults

EMERGENCY OPERATION (ER) 

• 

Controls luminaires powered via an emergency circuit

• 

UL924 Listed

• 

Monitors normal power and overrides relay closed and sets dimming output (if present) 
to full bright if normal feed is lost regardless of current state or sensor status

DEFAULT MODE (SA, SA2, SW2, PL T24)

• 

SA

 option changes default operating mode to Manual On/Auto Off

• 

SA2

 and 

SW2 

change default switch tracking channel to 2

• 

PA 

(Partial On) mode changes default operation of dimming units to be Auto On to 50%

• 

PL T24

 option for 120 VAC plug load control. Changes default operation to track only 

occupancy sensors (not switches or photocells)

347 VAC (347)

•   Allows unit to be powered from and switch 347 VAC.   

LOW TEMP/HIGH HUMIDITY (LT)

•   Device electronics are coated for corrosion resistance - required for cold storage or 

humid areas

•    Unit operates down to -40º F/C 

OPERATIONAL SETTINGS

Several operational settings for the 

nPP16

 family are available, including:

•  Override (On/Off/Normal) & Relay Test Mode (Enable/Disable)
•  Occupancy, Photocell, & Switch Tracking (Enable/Disable)
•  Occupancy, Photocell, & Switch Tracking Channel (1-16 each)
• 

Idle Time to Dim

• 

Special Operating Modes:

       Manual On to Auto Off (Semi-Auto), Auto to (Timed) Override On, Manual to (Timed)  
      Override On, Manual On to Full Auto, Predictive Off

• 

Occupancy Expiration of Manual Off / Timed Expiration of Manual Off

• 

Maintain Dim Level When Vacant

•  Occupied Bright Level & Unoccupied Dim Level
•  High End & Low End Trim

Model #: nPP16 (D) 

Model #: nPP16 (D)  ER

Note: For information on current monitoring relay packs, see the nPP16 IM series datasheet.