background image

NOVUS AUTOMATION. 

1/3 

 

 

NP620 

RELATIVE PRESSURE TRANSMITTER – INSTRUCTIONS MANUAL – V1.0x G 

PRESENTATION 

The  NP620  positive  relative  pressure transmitter series are robust 

and reliable equipment suitable for general industrial applications. Its 

great advantage is the possibility of a fast and easy configuration of 

the operating range. With the aid of a software, the user has access 

to the most important information of the transmitter and can set the 

most appropriate configuration for the process. 

PRECAUTION 

Before operating the transmitter, carefully read its specifications and 

operating instructions. In case of damage caused by incorrect 

operation or inappropriate usage, and its consequences, the 

guarantee becomes ineffective and null. 
A specialized professional shall perform the installation. 
A specific electrical power supply network should be provided for 

instruments use only. 

UNPACKING 

After unpacking the product, besides the transmitter it must be 

available: 

 

A quick guide to installation and operation; 

 

A sealed electrical connector; 

 

A screw to adjust the transmitter and the connector. 

IDENTIFICATION 

An identification label is attached to the equipment housing. On this 

label, you can found detailed information about the transmitter. 
Fig. 1 shows the identification label with their respective information. 

 

Fig. 1 – Transmitter identification 

 
 
 
 
 
 
 
 
 

SPECIFICATIONS 

Type of Measure: 

Positive relative pressure 

Maximum Range (Max. Range): 

0.1 MPa (1 bar / 14.50 psi) 

0.4 MPa (4 bar / 58.02 psi) 

1 MPa (10 bar / 145.04 psi) 

4 MPa (40 bar / 580.15 psi) 

10 MPa (100 bar / 1450.38 psi)

 

(*) 

Rangeability

3:1 

Measurement Accuracy: 

< ±0.25 % of the maximum Range (Max. Range) 
Including linearity, hysteresis and repeatability, 25 °C 

Thermal Maximum Deviation

< ±0.05 % Max. Range / °C 

Overpressure Range

Twice the value specified for the Maximum Measurement Range 

Output Signal (Output)

Electric currente, 4-20 mA, 2 wires. 

Power Supply (Power)

11 to 33 Vdc 

Degree of Protection

IP65 

Electrical Connection

Connector for Type A valves (DIN EN 175301-803), IP65. 
Conductor 1.5 mm² (max.) and cables between 6 and 8 mm in 

diameter. 

Operating temperature

-20 to 70 °C / -4 a 158 °F 

Dinamic Response

< 30 ms 

Process Conection (Thread)

¼ NPT; ½ NPT; ½ BSP, G ¼ (*) 

Sensor features: 

Polysilicon Piezoresistive (silicone oil filled) 

Metal housing of the transmitter

Stainless 316 

Wetted parts

Sensor, stainless steel 316 
Sealing ring, FKM 
Metal connection, stainless steel 316 

Compatibility:  Any gas or liquid compatible with the constituent 

materials of the wetted parts. 
(*) Information available on the product identification label. 

Reviews: